Line filter Siemens

Обзор
In conjunction with line reactors and a logically consistent configuration of the plant or system, line filters limit the interference conducted by the Basic Line Modules and Power Modules to the limit values of Category C2 acc. to EN 61800‑3.
The line filters are suitable for TN and TT supply systems grounded at the neutral point.
Технические данные
Line voltage 380 … 480 V 3 AC | Line filter | ||||||
---|---|---|---|---|---|---|---|
| 6SL3000-0BE32-5AA0 | 6SL3000-0BE34-4AA0 | 6SL3000-0BE36-0AA0 | 6SL3000-0BE41-2AA0 | 6SL3000-0BE41-6AA0 | ||
Rated current | A | 250 | 440 | 600 | 1200 | 1600 | |
Power loss 1) at 50/60 Hz | kW | 0.049 | 0.049 | 0.055 | 0.137 | 0.182 | |
Load/line supply connection |
| 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection | |
PE connection |
| Hole for M8 | Hole for M8 | Hole for M10 | Hole for M10 | Hole for M10 | |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 | |
Dimensions | |||||||
| mm | 360 | 360 | 400 | 425 | 505 | |
| mm | 240 | 240 | 265 | 265 | 265 | |
| mm | 116 | 116 | 140 | 145 | 145 | |
Weight, approx. | kg | 12.3 | 12.3 | 19.0 | 25.2 | 28.8 | |
Conformity |
| CE | CE | CE | CE | CE | |
Approvals, according to |
| cURus | cURus | cURus | cURus | cURus | |
Suitable for Power Module, chassis format | |||||||
|
| 6SL3310-1TE32-1AA3 (110 kW) | 6SL3310-1TE32-6AA3 (132 kW) 6SL3310-1TE33-1AA3 (160 kW) 6SL3310-1TE33-8AA3 (200 kW) | 6SL3310-1TE35-0AA3 (250 kW) | – | – | |
Suitable for Basic Line Module, chassis format | |||||||
|
| – | 6SL3330-1TE34-2AA3 (200 kW) | 6SL3330-1TE35-3AA3 (250 kW) | 6SL3330-1TE38-2AA3 (400 kW) 6SL3330-1TE41-2AA3 (560 kW) | 6SL3330-1TE41-5AA3 (710 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
Line voltage 500 ... 690 V 3 AC | Line filter | |||
---|---|---|---|---|
| 6SL3000-0BG34-4AA0 | 6SL3000-0BG36-0AA0 | 6SL3000-0BG41-2AA0 | |
Rated current | A | 440 | 600 | 1200 |
Power loss1) at 50/60 Hz | kW | 0.049 | 0.055 | 0.137 |
Load/line supply connection |
| 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection |
PE connection |
| Hole for M8 | Hole for M10 | Hole for M10 |
Degree of protection |
| IP00 | IP00 | IP00 |
Dimensions | ||||
| mm | 360 | 400 | 505 |
| mm | 240 | 265 | 265 |
| mm | 116 | 140 | 145 |
Weight, approx. | kg | 12.3 | 19.0 | 25.2 |
Conformity |
| CE | CE | CE |
Approvals, according to |
| cURus | cURus | cURus |
Suitable for Basic Line Module, chassis format | ||||
|
| 6SL3330-1TG33-0AA3 (250 kW) 6SL3330-1TG34-3AA3 (355 kW) | 6SL3330-1TG36-8AA3 (560 kW) | 6SL3330-1TG41-1AA3 (900 kW) 6SL3330-1TG41-4AA3 (1100 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.