With a high line short-circuit power (i.e. low line supply cable inductance) a line reactor is required in order to
- protect the drive converter itself from excessively high harmonic currents and therefore overload
- limit the harmonics to permissible values. The harmonic currents are limited by the total inductance comprising the line reactor and mains supply cable inductance.
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Технические данные
Line voltage 380 ... 480 V 3 AC | Line reactor | ||||||
---|---|---|---|---|---|---|---|
| 6SL3000-0CE32-3AA0 | 6SL3000-0CE32-8AA0 | 6SL3000-0CE33-3AA0 | 6SL3000-0CE35-1AA0 | 6SL3000-0CE36-3AA0 | 6SL3000-0CE37-7AA0 | |
Rated current | A | 224 | 278 | 331 | 508 | 628 | 773 |
Nominal inductance LN | μH | 76 | 62 | 52 | 42 | 27 | 22 |
Power loss 1) at 50/60 Hz | kW | 0.274 | 0.247 | 0.267 | 0.365 | 0.368 | 0.351 |
Line supply/load connection |
| 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection |
PE connection |
| M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | M6 screw |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 | IP00 |
Dimensions | |||||||
| mm | 270 | 270 | 270 | 300 | 300 | 300 |
| mm | 248 | 248 | 248 | 269 | 269 | 269 |
| mm | 200 | 200 | 200 | 212 | 212 | 212 |
Weight, approx. | kg | 24.5 | 26 | 27.8 | 38.0 | 41.4 | 51.3 |
Conformity |
| CE | CE | CE | CE | CE | CE |
Approvals, according to |
| cURus | cURus | cURus | cURus | cURus | cURus |
Suitable for Power Module, chassis format | |||||||
|
| 6SL3310-1TE32-1AA3 (110 kW) | 6SL3310-1TE32-6AA3 (132 kW) | 6SL3310-1TE33-1AA3 (160 kW) | 6SL3310-1TE33-8AA3 (200 kW) 6SL3310-1TE35-0AA3 (250 kW) | – | – |
|
| 6SL3315-1TE32-1AA3 (110 kW) | 6SL3315-1TE32-6AA3 (132 kW) | 6SL3315-1TE33-1AA3 (160 kW) | 6SL3315-1TE35-0AA3 (250 kW) | – | – |
Suitable for Basic Line Module, chassis format | |||||||
|
| – | – | – | 6SL3330-1TE34-2AA3 (200 kW) 6SL3330-1TE35-3AA3 (250 kW) | – | 6SL3330-1TE38-2AA3 (400 kW) |
|
| – | – | – | – | 6SL3335-1TE37-4AA3 (360 kW) | – |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
Line voltage 380 ... 480 V 3 AC | Line reactor | |||||
---|---|---|---|---|---|---|
| 6SL3000-0CE41-0AA0 | 6SL3000-0CE41-5AA0 | 6SL3000-0EE36-2AA0 | 6SL3000-0EE38-8AA0 | 6SL3000-0EE41-4AA0 | |
Rated current | A | 1022 | 1485 | 615 | 885 | 1430 |
Nominal inductance LN | μH | 16 | 13 | 55 | 35 | 25 |
Power loss 1) at 50/60 Hz | kW | 0,498 | 0,776 | 0,56 | 0,81 | 1,08 |
Line supply/load connection |
| 1 × hole for M12 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 2 × hole for M10 Provided for busbar connection |
PE connection |
| M6 screw | M6 screw | M6 thread | M6 thread | M6 thread |
Degree of protection | IP00 | IP00 | IP00 | IP00 | IP00 | |
Dimensions | ||||||
| mm | 350 | 460 | 300 | 442 | 544 |
| mm | 321 | 435 | 264 | 376 | 386 |
| mm | 211 | 235 | 203 | 263 | 232 |
Weight, approx. | kg | 69.6 | 118 | 57 | 85.5 | 220 |
Conformity |
| CE | CE | CE | CE | CE |
Approvals, according to |
| cURus | cURus | cURus | cURus | cURus |
Suitable for Basic Line Module, chassis format | ||||||
|
| 6SL3330-1TE41-2AA3 (560 kW) | 6SL3330-1TE41-5AA3 (710 kW) | – | – | – |
|
| 6SL3335-1TE41-2AA3 (600 kW) | 6SL3335-1TE41-7AA3 (830 kW) | – | – | – |
Suitable for Smart Line Module, chassis format | ||||||
|
| – | – | 6SL3330-6TE35-5AA3 (250 kW) 6SL3330-6TE37-3AA3 (355 kW) | 6SL3330-6TE41-1AA3 (500 kW) | 6SL3330-6TE41-3AA3 (630 kW) 6SL3330-6TE41-7AA3 (800 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
Line voltage 500 ... 690 V 3 AC | Line reactor | ||||||
---|---|---|---|---|---|---|---|
| 6SL3000-0CH32-7AA0 | 6SL3000-0CH33-4AA0 | 6SL3000-0CH34-8AA0 | 6SL3000-0CH36-0AA0 | 6SL3000-0CH41-2AA0 | 6SL3000-0EH41-6AA0 | |
Rated current | A | 270 | 342 | 482 | 597 | 1167 | 1600 |
Nominal inductance LN | μH | 100 | 81 | 65 | 46 | 30 | 17 |
Power loss 1) at 50/60 Hz | kW | 0.277 | 0.27 | 0.48 | 0.485 | 0.783 | 0.977 |
Line supply/load connection |
| 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection | 1 × hole for M12 Provided for busbar connection | 2 × hole for M12 Provided for busbar connection | 2 × hole for M12 Provided for busbar connection |
PE connection |
| M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | M6 screw |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 | IP00 |
Dimensions | |||||||
| mm | 270 | 270 | 350 | 350 | 460 | 416 |
| mm | 248 | 248 | 321 | 321 | 435 | 435 |
| mm | 200 | 200 | 232 | 232 | 235 | 250 |
Weight, approx. | kg | 27.9 | 38.9 | 55.6 | 63.8 | 147 | 134 |
Conformity |
| CE | CE | CE | CE | CE | CE |
Approvals 2), according to |
| cURus | cURus | cURus | cURus | cURus | cURus |
Suitable for Basic Line Module, chassis format | |||||||
|
| 6SL3330-1TG33-0AA3 (250 kW) | – | 6SL3330-1TG34-3AA3 (355 kW) | 6SL3330-1TG36-8AA3 (560 kW) | 6SL3330-1TG41-1AA3 (900 kW) 6SL3330-1TG41-4AA3 (1100 kW) | – |
|
| – | 6SL3335-1TG34-2AA3 (355 kW) | – | 6SL3335-1TG37-3AA3 (630 kW) | 6SL3335-1TG41-3AA3 (1100 kW) | 6SL3335-1TG41-7AA3 (1370 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
2) Only for line voltages 500 ... 600 V 3 AC.
Line voltage 500 ... 690 V 3 AC | Line reactor | |||
---|---|---|---|---|
| 6SL3000-0EH34-7AA0 | 6SL3000-0EH37-6AA0 | 6SL3000-0EH41-4AA0 | |
Rated current | A | 465 | 760 | 1430 |
Nominal inductance LN | μH | 115 | 70 | 40 |
Power loss 1) at 50/60 Hz | kW | 0,82 | 0,95 | 1,85 |
Line supply/load connection |
| 1 × hole for M10 Provided for busbar connection | 1 × hole for M10 Provided for busbar connection | 2 × hole for M10 Provided for busbar connection |
PE connection |
| M6 nut | M6 nut | M6 nut |
Degree of protection |
| IP00 | IP00 | IP00 |
Dimensions | ||||
| mm | 360 | 442 | 655 |
| mm | 325 | 370 | 383 |
| mm | 229 | 303 | 288 |
Weight, approx. | kg | 58 | 145 | 239 |
Conformity |
| CE | CE | CE |
Approvals 2), according to | cURus | cURus | cURus | |
Suitable for Smart Line Module, chassis format | ||||
|
| 6SL3330-6TG35-5AA3 (450 kW) | 6SL3330-6TG38-8AA3 (710 kW) | 6SL3330-6TG41-2AA3 (1000 kW) 6SL3330-6TG41-7AA3 (1400 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
2) Only for line voltages 500 ... 600 V 3 AC.