Braking resistors Siemens

Обзор



Excess energy in the DC link is dissipated in the braking resistor.

The braking resistor is connected to a Braking Module.

By positioning the braking resistor outside the cabinet or switchgear room, it is possible to extract the heat losses away from the Line Modules/Motor Modules. The level of air conditioning required is therefore reduced.

The maximum permissible cable length between the Braking Module and braking resistor is 100 m.

2 braking resistors with different rated and peak power values are available for the units.

The braking resistor is monitored on the basis of the duty cycle. A temperature switch (NC contact) is also fitted. This responds when the maximum permissible temperature is exceeded and can be evaluated by a controller.

Information about possible load cycles of the braking resistors and other notes are included in the SINAMICS Low Voltage Engineering Manual.

Характеристика



Load diagram for Braking Modules and braking resistors

Технические данные



Line voltage 380 … 480 V 3 AC
DC link voltage 510 … 720 V DC

Braking resistor

 

6SL3000-1BE31-3AA0

6SL3000-1BE32-5AA0

Resistance

Ω 

4.4 (±7.5 %)

2.2 (±7.5 %)

Rated power PDB
(continuous braking power)

kW

25

50

Power P15

kW

125

250

Power P20

kW

100

200

Power P40

kW

50

100

Current, max.

A

189

378

Power connection

 

M10 stud

M10 stud

  • Conductor cross-section, max. (IEC)

mm2

50

70

Degree of protection

 

IP20

IP20

Dimensions

   
  • Width

mm

740

810

  • Height

mm

600

1325

  • Depth

mm

486

486

Weight, approx.

kg

50

120

Conformity

 

CE

CE

Approvals, according to

 

cURus

cURus

Suitable for Braking Module

Type

6SL3300-1AE31-3AA0

6SL3300-1AE32-5 . A0



Line voltage 380 … 480 V 3 AC
DC link voltage 675 … 900 V DC

Braking resistor

 

6SL3000-1BF31-3AA0

6SL3000-1BF32-5AA0

Resistance

Ω 

6.8 (±7.5 %)

3.4 (±7.5 %)

Rated power PDB
(continuous braking power)

kW

25

50

Power P15

kW

125

250

Power P20

kW

100

200

Power P40

kW

50

100

Current, max.

A

189

378

Power connection

 

M10 stud

M10 stud

  • Conductor cross-section, max. (IEC)

mm2

50

70

Degree of protection

 

IP20

IP20

Dimensions

   
  • Width

mm

740

810

  • Height

mm

600

1325

  • Depth

mm

486

486

Weight, approx.

kg

50

120

Conformity

 

CE

CE

Approvals, according to

 

cURus

cURus

Suitable for Braking Module

Type

6SL3300-1AF31-3AA0

6SL3300-1AF32-5 . A0



Line voltage 660 … 690 V 3 AC
DC link voltage 890 … 1035 V DC

Braking resistor

 

6SL3000-1BH31-3AA0

6SL3000-1BH32-5AA0

Resistance

Ω 

9.8 (±7.5 %)

4.9 (±7.5 %)

Rated power PDB
(continuous braking power)

kW

25

50

Power P15

kW

125

250

Power P20

kW

100

200

Power P40

kW

50

100

Current, max.

A

125

255

Power connection

 

M10 stud

M10 stud

  • Conductor cross-section, max. (IEC)

mm2

50

70

Degree of protection

 

IP20

IP20

Dimensions

   
  • Width

mm

740

810

  • Height

mm

600

1325

  • Depth

mm

486

486

Weight, approx.

kg

50

120

Conformity

 

CE

CE

Approvals, according to

 

Suitable for Braking Module

Type

6SL3300-1AH31-3AA0

6SL3300-1AH32-5 . A0