Line-voltage sensing modules Siemens

Обзор



The line-voltage sensing submodule is an optional module for line-voltage sensing and correction.

The line-voltage sensing submodule is plugged from the front into the enclosure of the central interface module. The slot is located in the busbar area. If the line-voltage sensing submodule is not used, the opening is sealed by the busbar cover. If the line-voltage sensing submodule is used, the cover is used for shock-hazard protection.

Дизайн


  • Connection of phases L1, L2, L3 and the neutral conductor via Teflon-coated cable
  • Board connector for central interface module

Функции



Line voltage compensation

This function is required if the output power is to be corrected automatically in the case of strong line voltage fluctuations.

To implement this function, a line-voltage sensing submodule must be plugged in to at least one central interface module in a network of several HCS724I heater controllers.

The correction factors are calculated and transferred to the PROFIBUS DP master. The DP master then distributes these values to all HCS724I DP slaves.

Voltage measurement for enhanced diagnostics

To enable voltage values to be measured for enhanced diagnostics, a line-voltage sensing submodule is required for each central interface module.

The determined voltage value is used for detecting faults in emitters connected in parallel.

Note:

The central interface module is only supplied from the factory without a line-voltage sensing submodule. If you want to compensate for line voltage fluctuations, you must order both modules (line-voltage sensing submodule and central interface module) and connect them together on site.

Технические данные



Order number

 

6ES7171-1XX00-6AA0

product brand name

 

SIPLUS

Product designation

 

Line voltage compensation NE724

Supply voltage:

 

 

Design of the power supply

 

Power supply via central connection

Product function / Current detection

 

No

Product function / voltage detection

 

Yes

Operating voltage / with AC

 

 

  • at 50 Hz / Rated value

V

187 ... 264

  • at 60 Hz / Rated value

V

187 ... 264

Relative metering precision / relating to measured current

%

3

Operating frequency / Rated value

Hz

50 ... 60

Type of electrical connection / at the measurement inputs for voltage

 

Ring cable lug M6

Installation/ mounting/ dimensions:

 

 

Width

mm

86

Height

mm

22

Depth

mm

160