Power Output Module (POM) Siemens

Обзор
The power output modules (POMs) are an essential component of the SIPLUS HCS4200 heating control system.
Up to 12 power output modules can be operated on one CIM.
POM4220 low-end power output module:
- 16 outputs for switching ohmic loads.
- A current of up to 6.3 A can be used per output channel.
- Module simply slides into the rack.
- And is secured by one screw at the bottom and another screw at the top.
Дизайн
- The heat emitters are connected via two 8-pole connectors (mating connectors are included in the scope of delivery)
- Line feed (Lx/N/Ly) at the front by means of 3-pole connector (mating connector is included in the scope of delivery)
- 1 fuse per output for the heat emitter supply circuit, in open fuse holders
- Internal serial interface on the rear
- 3 diagnostic LEDs for indicating module faults
- 16 diagnostic LEDs for indicating channel faults
Функции
Power switching elements
- Power triacs
- Protection of triacs and opto-triacs against overvoltages by Transil diodes
- Transfer of the diagnostics information to the central interface module (CIM)
Control modes
- Half-wave control:
Here the channel is controlled depending on the parameterized manipulated variable for each zero point. The controller outputs are set in values from 0 to 100 %.
Output power
- 16 power channels of 230 V each (8 outputs per phase)
- Switching power per output: Max. 1449 W at 230 V
- Switching capacity per power output module: Max. 16100 W at 230 V
Ventilation
- A fan module can be optionally mounted at the top of the rack so that 4 POMs can be ventilated and controlled dependent on the internal temperature.
Temperature monitoring
- An NTC thermistor is installed in the device to monitor the internal temperature. An alarm threshold is defined for the internal temperature. The following reactions are triggered when the threshold is overshot:
- Signal to the higher-level controller.
- The channels are deactivated - regardless of which channel response was configured for error situations.
Diagnostic options
Implicit diagnostics functions are provided as standard to detect the following faults (diagnostics cycle does not affect the heating power):
- Leading fuse defective / triac at high resistance (exception: setpoint 0%)
- Triac failure (exception: setpoint 100%)
- Heating element cable is defective (short-circuit and interruption)
- Load defective (short-circuit and interruption)
Технические данные
Order number |
| 6BK1942-2AA00-0AA0 | |
---|---|---|---|
product brand name |
| SIPLUS | |
Product designation |
| HCS POM4220 Lowend | |
General technical data: |
|
| |
Type of load |
| Ohmic load | |
Equipment marking acc. to DIN EN 81346-2 |
| Q | |
Supply voltage: |
|
| |
Type of voltage of the supply voltage |
| AC | |
Supply voltage at AC Rated value | V | 230 | |
Relative negative tolerance of the supply voltage | % | 10 | |
Relative positive tolerance of the supply voltage | % | 10 | |
Supply voltage frequency 1 Rated value | Hz | 50 | |
Supply voltage frequency 2 Rated value | Hz | 60 | |
Relative symmetrical tolerance of the supply voltage frequency | % | 5 | |
Power capacity |
|
| |
| kW | 16.1 | |
| kW | 7.3 | |
| kW | 16.1 | |
Switching capacity current per phase maximum | A | 35 | |
Design of the electrical isolation |
| Optocoupler and/or protective impedance between main circuit and PELV | |
Recovery time after power failure typical | s | 1 | |
Type of electrical connection for supply voltage |
| Connector, 3-pin | |
Type of connectable conductor cross-section |
|
| |
|
| 1x (0,25 ... 6 mm²) | |
|
| 24 ... 8 | |
Power Electronics: |
|
| |
Control version of heat emitters |
| Half-wave control | |
Number of outputs for heating power |
| 16 | |
Number of heat emitters per output maximum |
| 1 | |
Output voltage at output for heating power | V | 230 | |
Power capacity per output |
| 100 ... 1 449 | |
Output current at output for heating power Rated value | A | 6.3 | |
Design of short-circuit protection for heating power per output |
| Safety fuse 6.3 A | |
Melting I2t value | A²·s | 57 | |
Design of the overvoltage protection |
| Transil Diode | |
Galvanic isolation between the outputs |
| No | |
Type of electrical connection at output for heating and fan |
| Connector, 8-pole | |
Type of connectable conductor cross-section |
|
| |
|
| 1x (0.2 ... 10 mm²) | |
|
| 1x (0,25 ... 6 mm²) | |
|
| 24 ... 8 | |
Communication: |
|
| |
Design of the interface |
| system interface | |
Display: |
|
| |
Number of status displays |
| 19 | |
Display version as status display by LED |
| LED green = ready, LED yellow = heating on/off, LED red = error display, LED red = error for each channel | |
Auxiliary circuit: |
|
| |
Design of the power supply |
| Power supply via rack | |
Active power consumption maximum | W | 1 | |
Protective and monitoring functions: |
|
| |
Product function Temperature monitoring |
| Yes | |
Type of the temperature monitoring |
| NTC thermistor | |
Diagnostics function |
| Voltage diagnostics | |
|
| Yes | |
|
| Yes | |
|
| Yes | |
Mechanical data: |
|
| |
mounting position |
| vertical | |
Mounting type |
| Screw mounting to rack | |
Type of ventilation |
| Self ventilation or forced ventilation | |
Vibration resistance |
|
| |
|
| 10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1g | |
|
| 5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1g | |
Shock resistance |
|
| |
|
| 25 g / 6 ms / 1000 shocks / axis | |
|
| 15g / 11 ms / 3 shocks / axis | |
Protection class IP |
| IP20 | |
Depth | mm | 281 | |
Height | mm | 285 | |
Width | mm | 36 | |
Electromagnetic compatibility: |
|
| |
EMC emitted interference |
| Limit value in accordance with IEC 61000-6-4:2007 + A1:2011 | |
Conducted interference due to burst acc. to IEC 61000-4-4 |
| 2 kV power supply lines, 2 kV load lines | |
Conducted interference due to surge acc. to IEC 61000-4-5 |
| Supply and load lines: 1 kV symmetric, 2 kV unsymmetric PROFINET cables: 1 kV unsymmetric | |
Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6 |
| 10 V (0.15 ... 80 MHz) | |
Field-bound parasitic coupling acc. to IEC 61000-4-3 |
| 10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz) | |
Electrostatic discharge acc. to IEC 61000-4-2 |
| 4 kV contact discharging, 8 kV air discharging | |
Overvoltage category |
| III | |
Ambient conditions: |
|
| |
Ambient temperature |
|
| |
|
| 0 ... 55 | |
|
| -25 ... +70 | |
|
| -25 ... +70 | |
Air pressure |
|
| |
|
| 860 ... 1 080 | |
|
| 660 ... 1 080 | |
Degree of pollution |
| 2 | |
Installation altitude at height above sea level maximum | m | 2 000 | |
Relative humidity |
|
| |
| % | 95 | |
| % | 50 | |
|
| 95% at 25 °C, decreasing linearly to 50% at 50 °C |
Дополнительно
The following accessories are available for the POM4220 low-end power output module:
- Connector set, 3-pole (block with 10 connectors) for connecting the line infeed
- Connector set 8-pole (block with 10 connectors) for connecting the heat emitters
- Fuse 6.3 A/250 V (set with 50 fuses) as spare part