CPU 412 Siemens

Область применения
The CPU 412-1 is the low-cost entry into the medium performance range. It can be used in smaller systems with limited I/O configuration. The combined MPI/DP interface also enables operation of a PROFIBUS DP line.
The CPU 412-2 is the CPU for applications in the mid-performance range with 2 PROFIBUS DP master systems.
For networking within a PROFINET network, the CPU 412-2 PN is available.
Обзор
- The low-cost starter solution for the medium performance range
- Can be used in small and medium-sized systems with requirements of the medium performance range
Дизайн
The CPU 412-1, CPU 412-2 and CPU 412-2 PN are equipped with the following:
- Powerful processor:
The CPUs achieve command runtimes down to 0.75 µs per binary instruction. - CPU 412-1: 288 KB RAM (of which 144 KB each for program and data);
CPU 412-2: 512 KB RAM (of which 256 KB each for program and data);
CPU 412-2: 1 MB RAM (of which 512 KB each for program and data);
fast RAM for parts of the user program relevant to execution. - Flexible expansion:
Up to 65536 digital and 4096 analog inputs/outputs. - Multi-point interface MPI:
With the MPI it is possible to establish simple networking of max. 32 stations at a data transmission rate of up to 12 Mbit/s. The CPUs can establish up to 16 connections to stations of the communication bus (C bus) and the MPI. - Mode selector switch:
Designed as toggle switch. - Diagnostics buffer:
The last 120 fault and interrupt events are retained in a ring buffer for diagnostic purposes. The number of entries can be parameterized. - Real-time clock:
The date and time are appended to diagnostic messages of the CPUs. - Memory card:
For expansion of the integrated load memory. The information in the load memory comprises S7-400 parameterization data in addition to the program and therefore requires twice as much memory space. The result is:- The integral load memory is sufficiently large, so a memory card is often not required.
The CPU 412-2 also features:
- PROFIBUS DP interface and combined MPI/DP interface:
The PROFIBUS DP master interface allows a distributed automation configuration offering high speed and ease of use. From the user''s point of view, the distributed I/O is treated as central I/O (same configuring, addressing, and programming). - Mixed configuration:
SIMATIC S5 and SIMATIC S7 as PROFIBUS master according to EN 50170.
Функции
- Block protection:
A password concept also protects the user program from unauthorized access - Integrated HMI services:
The user only has to specify the source and destination of the data with HMI devices. The data are then transported cyclically and automatically by the system. - Integrated communication functions:
- PG/OP communication
- Global data communication
- S7 standard communication
- S7 communication
Programmable properties
The STEP 7 tool "Hardware configuration" can be used to parameterize the properties and response of the S7-400 including the CPUs, e.g.
- Multipoint interface MPI:
- Definition of node addresses
- Startup/cycle behavior
- Stipulation of the maximum cycle time and communication load
- Address allocation:
Addressing of I/O modules - Retentive area:
Definition of the number of retentive bit memories, counters, timers, data blocks, and clock memories - Size of the process image, local data
- Length of the diagnostics buffer
- Protection level:
Definition of access authorizations to program and data - System diagnostics:
Definition of the handling and scope of diagnostics messages - Timed interrupts:
Setting of periodicity
Display and information functions
- Status and fault indicators:
LEDs indicate internal and external faults and operating modes such RUN, STOP, restart, test function, etc. - Test functions:
The PG can be used to display signal states in program execution, modify process tags irrespective of the user program, read out the contents of stack memories, run separate program steps and inhibit program components. - Information functions:
The PG can be used to provide the user with information about the memory capacity and operating mode of the CPU, and the current utilization of the working and load memories.
Технические данные
Order number | 6ES7412-1XJ05-0AB0 | 6ES7412-2XJ05-0AB0 | 6ES7412-2EK07-0AB0 | |
---|---|---|---|---|
CPU412-1, MPI/DP, 288 KB | CPU412-2, MPI/DP, 512 KB | |||
General information |
|
|
| |
Product type designation | CPU 412-1 | CPU 412-2 | CPU 412-2 PN | |
Engineering with |
|
|
| |
| STEP7 V 5.3 SP2 or higher with HW update | STEP7 V 5.3 SP2 or higher with HW update | STEP 7 V5.5 or higher with HSP 262 | |
Supply voltage |
|
|
| |
Rated value (DC) | ||||
| No; Power supply via system power supply | No; Power supply via system power supply | No; Power supply via system power supply | |
Power loss |
|
|
| |
Power loss, typ. | 2.5 W | 4.5 W | 5.5 W | |
Memory |
|
|
| |
Work memory |
|
|
| |
| 288 kbyte | 512 kbyte | 1 Mbyte | |
| 144 kbyte | 256 kbyte | 512 kbyte | |
| 144 kbyte | 256 kbyte | 512 kbyte | |
Load memory |
|
|
| |
| 64 Mbyte | 64 Mbyte | 64 Mbyte | |
| 512 kbyte | 512 kbyte | 512 kbyte | |
| 64 Mbyte | 64 Mbyte | 64 Mbyte | |
CPU processing times |
|
|
| |
for bit operations, typ. | 75 ns | 75 ns | 31.25 ns | |
for word operations, typ. | 75 ns | 75 ns | 31.25 ns | |
for fixed point arithmetic, typ. | 75 ns | 75 ns | 31.25 ns | |
for floating point arithmetic, typ. | 225 ns | 225 ns | 62.5 ns | |
Counters, timers and their retentivity |
|
|
| |
S7 counter |
|
|
| |
| 2 048 | 2 048 | 2 048 | |
IEC counter |
|
|
| |
| Yes | Yes | Yes | |
S7 times |
|
|
| |
| 2 048 | 2 048 | 2 048 | |
IEC timer |
|
|
| |
| Yes | Yes | Yes | |
Data areas and their retentivity |
|
|
| |
Flag |
|
|
| |
| 4 kbyte; Size of bit memory address area | 4 kbyte; Size of bit memory address area | 4 kbyte; Size of bit memory address area | |
Address area |
|
|
| |
I/O address area |
|
|
| |
| 4 kbyte | 4 kbyte | 4 kbyte | |
| 4 kbyte | 4 kbyte | 4 kbyte | |
Process image |
|
|
| |
| 4 kbyte | 4 kbyte | 4 kbyte | |
| 4 kbyte | 4 kbyte | 4 kbyte | |
Hardware configuration |
|
|
| |
Slots |
|
|
| |
| 1 | 1 | 1 | |
Time of day |
|
|
| |
Clock |
|
|
| |
| Yes | Yes | Yes | |
Operating hours counter |
|
|
| |
| 16 | 16 | 16 | |
Interfaces |
|
|
| |
Interfaces/bus type | 1 x MPI/PROFIBUS DP | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP | 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports) | |
Number of RS 485 interfaces | 1; Combined MPI / PROFIBUS DP | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 1; Combined MPI / PROFIBUS DP | |
1. Interface |
|
|
| |
Interface type | Integrated | Integrated | Integrated | |
Physics | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI | |
Functionality |
|
|
| |
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
DP master |
|
|
| |
| 32 | 32 | 32 | |
2. Interface |
|
|
| |
Interface type | Integrated | PROFINET | ||
Physics | RS 485 / PROFIBUS | Ethernet RJ45 | ||
Number of ports | 2 | |||
Functionality |
|
|
| |
| Yes | No | ||
| Yes | No | ||
| Yes | |||
| Yes | |||
| Yes | |||
DP master |
|
|
| |
| 64 | |||
PROFINET IO Controller |
|
|
| |
| 256 | |||
| 256 | |||
| 64 | |||
Isochronous mode |
|
|
| |
Isochronous operation (application synchronized up to terminal) | Yes; For PROFIBUS only | Yes; For PROFIBUS only | Yes; Via PROFIBUS DP or PROFINET interface | |
Communication functions |
|
|
| |
PG/OP communication | Yes | Yes | Yes | |
Data record routing | Yes | Yes | Yes | |
Global data communication |
|
|
| |
| Yes | Yes | Yes | |
S7 basic communication |
|
|
| |
| Yes | Yes | Yes | |
S7 communication |
|
|
| |
| Yes | Yes | Yes | |
S5 compatible communication |
|
|
| |
| Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | |
Standard communication (FMS) |
|
|
| |
| Yes; Via CP and loadable FB | Yes; Via CP and loadable FB | Yes; Via CP and loadable FB | |
Open IE communication |
|
|
| |
| Yes; via integrated PROFINET interface and loadable FBs | |||
| 46 | |||
|