CPU 414 Siemens

Область применения



CPU 414-2, CPU 414-3 and CPU 414-3 PN/DP are designed for high demands in the mid-level performance range. They meet higher demands for program scope and instruction processing speed.

The integrated PROFIBUS DP ports in the CPU 414-2 and CPU 414-3 make it possible to connect directly to the PROFIBUS DP fieldbus as a master or slave.

An additional DP master system can be connected to the CPU 414-3 and CPU 414-3 PN/DP using the IF 964-DP interface module.

For the PROFINET interface of the CPU 414-3 PN/DP, the switch functionality permits the formation of two externally accessible PROFINET ports. In addition to hierarchical network topologies, this also enables the creation of line structures in the new S7-400 controllers.

Note:
Only the 6ES7 964-2AA04-0AB0 interface submodule may be used.

Обзор


  • CPUs for high demands in the mid-level performance range
  • Applicable for plants with additional demands on programming scope and processing speed
  • Integrated PROFINET functions in CPU 414-3 PN/DP

Дизайн



The CPUs are equipped with the following:

  • Powerful processor:
    The CPUs achieve instruction execution times as low as 0.045 µs per binary instruction.
  • CPU 414-2: 1 MB RAM (of which 512 KB each for program and data);
    CPU 414-3: 2.8 MB RAM (of which 1.4 MB each for program and data);
    CPU 414-3 PN/DP: 4 MB RAM (of which 2 MB each for program and data);
    fast RAM for parts of the user program relevant to execution.
  • Flexible expansion:
    Up to 131072 digital and 81932 analog inputs/outputs.
  • Multi-point interface MPI:
    With the MPI it is possible to establish simple networking of max. 32 stations at a data transmission rate of up to 12 Mbit/s. The CPUs can establish up to 32 connections to stations of the communication bus (C bus) and the MPI
  • Mode selector switch:
    Designed as toggle switch.
  • Diagnostics buffer:
    The last error and interrupt events are retained in a ring buffer for diagnostic purposes. The number of entries can be parameterized.
  • Real-time clock:
    The date and time are appended to diagnostic messages of the CPUs.
  • Memory Card:
    For expansion of the integrated load memory. The information in the load memory comprises S7-400 parameterization data in addition to the program and therefore requires twice as much memory space. The result is:
    • The integral load memory for large programs is not sufficient, therefore a memory card is frequently required. RAM and FEPROM cards (FEPROM for retentive storage) are available.
  • PROFIBUS DP interface and combined MPI/DP interface:
    The PROFIBUS DP master interface allows a distributed automation configuration offering high speed and ease of use. From the user''s point of view, the distributed I/O is treated as central I/O (same configuring, addressing and programming).
    Mixed configuration: SIMATIC S5 and SIMATIC S7 as PROFIBUS master according to EN 50170.

CPU 414-3 and CPU 414-3 PN/DP also include:

  • Additional module slot:
    An additional PROFIBUS DP master system can be connected via the IF 964-DP interface module.

CPU 414-3 PN/DP additionally includes:

  • PROFINET interface with 2 ports (switch):
    • PROFINET I/O, 256 IO devices connectable
    • PROFINET CBA

Функции


  • Block protection:
    A password concept protects the user program from unauthorized access.
  • Integral HMI services:
    The user only has to specify the source and destination of the data with HMI devices; the data are then transported cyclically and automatically by the system.
  • Integrated communications functions:
    • PG/OP communication
    • Shared data communication
    • S7 standard communication
    • S7 Communication

CPU 414-3 PN/DP additional:

  • Open communication over TCP/IP, UDP and ISO-on-TCP (RFC1006)
  • Distributed intelligence in Component Based Automation (CBA) on PROFINET
  • Additional diagnostic options with integrated webserver
  • Firmware update using network

Parameterizable attributes

The STEP 7 tool "Hardware Configuration" can be used to program the properties and response of the S7-400 including the CPUs, e.g.

  • Multi-point interface MPI:
    • Definition of station addresses.
    • Startup/cycle behavior
    • Stipulation of the maximum cycle time and communications load
  • Address assignment:
    Addressing of I/O modules.
  • Retentive ranges:
    Definition of the number of retentive bit memories, counters, timers, data blocks and clock memories.
  • Size of the process image, local data.
  • Length of the diagnostics buffer
  • Protection level:
    Definition of access authorization for program and data
  • System diagnostics:
    Definition of the handling and scope of diagnostic messages
  • Timed interrupts:
    Setting of periodicity

CPU 414-3 PN/DP additional:

  • PROFINET Interface
  • Parameterization of time synchronization using NTP procedure

Indication and information functions

  • Status and error indicators:
    LEDs indicate internal and external errors and operating states such as RUN, STOP, Restart, Test function, for example.
  • Test functions:
    The programming device can be used to display signal states in program execution, modify process tags irrespective of the user program, read out the contents of stack memories, run separate program steps and inhibit program components.
  • Information functions:
    The programming device can be used to provide the user with information on the memory capacity and operating mode of the CPU and the current utilization of the working and load memories

Технические данные



Order number

6ES7414-2XK05-0AB0

6ES7414-3XM05-0AB0

6ES7414-3EM07-0AB0

CPU414-2, MPI/DP, 1 MB

CPU414-3, 2.8 MB, 3 INTERFACES

General information

 

 

 

Product type designation

CPU 414-2

CPU 414-3

CPU414-3 PN/DP

Engineering with

 

 

 

  • Programming package

STEP7 V 5.3 SP2 or higher with HW update

STEP7 V 5.3 SP2 or higher with HW update

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

Power loss, typ.

4.5 W

5.5 W

6.5 W

Memory

 

 

 

Work memory

 

 

 

  • integrated

1 Mbyte

2.8 Mbyte

4 Mbyte

  • integrated (for program)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

  • integrated (for data)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

Load memory

 

 

 

  • expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • integrated RAM, max.

512 kbyte

512 kbyte

512 kbyte

  • expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

for bit operations, typ.

45 ns

45 ns

18.75 ns

for word operations, typ.

45 ns

45 ns

18.75 ns

for fixed point arithmetic, typ.

45 ns

45 ns

18.75 ns

for floating point arithmetic, typ.

135 ns

135 ns

37.5 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • Number

2 048

2 048

2 048

IEC counter

 

 

 

  • present

Yes

Yes

Yes

S7 times

 

 

 

  • Number

2 048

2 048

2 048

IEC timer

 

 

 

  • present

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

Flag

 

 

 

  • Number, max.

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

Address area

 

 

 

I/O address area

 

 

 

  • Inputs

8 kbyte

8 kbyte

8 kbyte

  • Outputs

8 kbyte

8 kbyte

8 kbyte

Process image

 

 

 

  • Inputs, adjustable

8 kbyte

8 kbyte

8 kbyte

  • Outputs, adjustable

8 kbyte

8 kbyte

8 kbyte

Hardware configuration

 

 

 

Slots

 

 

 

  • required slots

1

2

2

Time of day

 

 

 

Clock

 

 

 

  • Hardware clock (real-time clock)

Yes

Yes

Yes

Operating hours counter

 

 

 

  • Number

16

16

16

Interfaces

 

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable)

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

1; Combined MPI / PROFIBUS DP

Number of other interfaces

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

 

 

Interface type

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

  • MPI

Yes

Yes

Yes

  • DP master

Yes

Yes

Yes

  • DP slave

Yes

Yes

Yes

DP master

 

 

 

  • Number of DP slaves, max.

32

32

32

2. Interface

 

 

 

Interface type

Integrated

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Ethernet RJ45

Number of ports

2

Functionality

 

 

 

  • DP master

Yes

Yes

No

  • DP slave

Yes

Yes

No

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • PROFINET CBA

Yes

DP master

 

 

 

  • Number of DP slaves, max.

96

96

PROFINET IO Controller

 

 

 

  • Number of connectable IO Devices for RT, max.

256

  • Number of IO Devices with IRT and the option "high flexibility"

256

  • Number of IO Devices with IRT and the option "high performance", max.

64

3. Interface

 

 

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Functionality

 

 

 

  • MPI

No

No

  • DP master

Yes

Yes

  • DP slave

Yes

Yes

DP master

 

 

 

  • Number of DP slaves, max.

96

96

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Global data communication

 

{"prefetch":[{"source":"document","where":{"and":[{"href_matches":"\/*"},{"not":{"href_matches":["\/wp-*.php","\/wp-admin\/*","\/wp-content\/uploads\/*","\/wp-content\/*","\/wp-content\/plugins\/*","\/wp-content\/themes\/pzip\/*","\/*\\?(.+)"]}},{"not":{"selector_matches":"a[rel~=\"nofollow\"]"}},{"not":{"selector_matches":".no-prefetch, .no-prefetch a"}}]},"eagerness":"conservative"}]}

Запрос коммерческого предложения

×


    * Поля, обязательные для заполнения.

    Сообщение отправлено

    ×

    В ближайшее время сообщение будет обработано.

    Письмо с номером обращения отправлено на Ваш почтовый ящик.

    Спасибо за то, что выбрали Первый ZIP!

    Что-то пошло не так...

    ×

    К сожалению, наша система расценила Ваше сообщение как спам.

    Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте.

    Приносим извинения за возможные неудобства.