PM240M Power Modules Siemens

Обзор



SINAMICS G110M PM240M Power Module FSA 1.5 kW (2 hp)

SINAMICS G110M PM240M Power Module FSB 4 kW (5 hp)

The PM240M Power Modules are suitable for safety-related applications. In conjunction with the CU240M Control Unit, the drive can be transformed into a Safety Integrated drive (see Control Units).

The PM240M Power Modules with integrated line filter class A are suitable for connection to TN and TT supply systems.

Характеристика



Derating data

Rated power at 400 V 3 AC

Rated output current in A

for a pulse frequency of
(derating as a function of the pulse frequency 1))

kW

hp

4 kHz

6 kHz

8 kHz

10 kHz

12 kHz

14 kHz

16 kHz

0.37

0.5

1.3

1.3

1.11

0.91

0.78

0.65

0.59

0.75

1

2.2

1.9

1.5

1.3

1.1

1

0.9

1.1

1.5

3.1

2.6

2.2

1.9

1.6

1.4

1.2

1.5

2

4.1

3.5

2.9

2.5

2.1

1.8

1.6

2.2

3

5.6

4.8

3.9

3.4

2.8

2.5

2.2

3

4

7.3

6.2

5.1

4.4

3.7

3.3

2.9

4

5

8.8

7.5

6.2

5.3

4.4

4

3.5



1) The permissible motor cable length also depends on the cable type and the selected pulse frequency.

Ambient temperature

Permissible output current as a function of ambient temperature for PM240M Power Modules, frame sizes FSA and FSB

Note:

The operating temperature ranges of the Control Units must be taken into account. The temperature ranges are specified in the technical specifications under Control Units.

Installation altitude

Permissible output current as a function of installation altitude for PM240M Power Modules, frame sizes FSA and FSB

Permissible input voltage as a function of installation altitude for PM240M Power Modules, frame sizes FSA and FSB

Интеграция



PM240M Power Modules feature the following interfaces as standard:

  • PM‑IF interface for connection of the PM240M Power Module and Control Unit
  • Motor connection including control of the motor brake and temperature sensor
  • Line connection via cable gland or HAN Q4/2 (connector)
  • Line supply loop-through via cable gland/terminal or HAN Q4/2 (socket)
  • USB connection for connection of a PC
  • Analog potentiometer for setting a speed
  • SD card slot for the use of memory cards

Connection diagram for PM240M Power Module with integrated line filter class A

Чертеж



Dimensions of PM240M Power Modules (including CU240M Control Unit)

Frame size

Dimensions in mm (inches)

 

h

l

d1

d2

d3

FSA

135 (5.31)

270 (10.63)

208 (8.19)

216 (8.5)

161 (6.34)

FSB

135 (5.31)

309 (12.17)

208 (8.19)

216 (8.5)

181 (7.13)



Технические данные



General technical specifications

 

PM240M Power Modules

System operating voltage

380 V (-10 %) ... 480 V (+10 %) 3 AC

Grid requirements
Short-circuit power ratio RSC

>100

Input frequency

47 ... 63 Hz

Output frequency

 

  • Control mode V/f

0 ... 550 Hz

  • Control type Vector

0 ... 200 Hz

Pulse frequency

4 kHz (standard); 4 ... 16 Hz (in steps of 2 kHz) see derating data

Power factor

0.95

Inverter efficiency

95 ... 97 %

Output voltage, max.

in % of the input voltage

87%

Overload capability

 

  • High overload (HO)

0.37 ... 3 kW (0.5 ... 4 hp):

2 × rated output current for 3 s,
followed by 1.5 × rated output current for 57 s,
over a cycle time of 300 s (110 % on average)

4 kW (5 hp):

1.6 × rated output current for 3 s,
followed by 1.5 × rated output current for 57 s,
over a cycle time of 300 s (110 % on average)

Electromagnetic compatibility

Integrated line filter class A according to EN 55011

Possible braking methods

Dynamic braking with internal braking resistors
DC brake
Integrated brake control supplies DC power supply for the brake

Line input voltage

380 V AC

400 V AC

440 V AC

480 V AC

500 V AC

Resulting brake voltage

171 V DC

180 V DC

198 V DC

216 V DC

225 V DC

Disconnection on the DC side permits "fast" braking (max. output current 1 A)

Degree of protection

IP65/66 (applicable to Power Module and Control Unit in mounted state)

Operating temperature

-10 ... +55 °C (14 ... +131 °F)

Storage temperature

-40 ... +70 °C (-40 ... +158 °F)

Permissible mounting positions

All

Relative humidity

<95 % RH, condensation not permissible

Cooling

External cooling with motor fan

Installation altitude

Up to 1000 m (3281 ft) above sea level without derating
Over 1000 m (3281 ft) see derating data

Short Circuit Current Rating
(SCCR) 1)

40 kA

Protection functions

  • Undervoltage
  • Phase failure detection
  • Overvoltage
  • Overload
  • Ground fault
  • Short-circuit
  • Stall protection
  • Motor blocking protection
  • Motor overtemperature
  • Inverter overtemperature
  • Parameter locking

Compliance with standards

UL, cUL, CE, C-Tick

CE marking, according to

EC Low Voltage Directive 73/23/EEC;
filtered variants also: EC Low Voltage Directive 89/336/EEC



1) Applies to industrial control panel installations to NEC Article 409 or UL 508A.

Line voltage
380 … 480 V 3 AC

 

PM240M Power Modules

 

 

6SL3517-1BE11-3AM0

6SL3517-1BE12-3AM0

6SL3517-1BE13-3AM0

6SL3517-1BE14-3AM0

Rated output current Irated1)

A

1.3

2.2

3.1

4.1

Maximum output current Imax

A

2.6

4.4

6.2

8.2

Rated power

kW (hp)

0.37 (0.5)

0.75 (1)

1.1 (1.5)

1.5 (2)

Rated pulse frequency

kHz

4

4

4

4

Efficiency η

%

96.8

98.1

98.2

97.3

Power loss 2)

At rated output current

kW

0.025

0.032

0.041

0.052

Cooling air requirement

m3/s (ft3/s)

0.0048 (0.02)

0.0048 (0.02)

0.0048 (0.02)

0.0048 (0.02)

Sound pressure level LpA (1 m)

dB

Rated input current 3)

A

1.3

2

2.8

3.6

Line supply connection
U1/L1, V1/L2, W1/L3, PE

 

 

 

 

 

  • Conductor cross-section (recommended)

mm2

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

PE connection

(external connection)

 

 

 

 

 

  • Conductor cross-section (recommended)

mm2

10

10

10

10

Motor connection
U2, V2, W2, PE, motor brake, temperature sensor

 

 

 

 

 

  • Conductor cross-section

mm2

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

Motor cable length, max.

Shielded

m (ft)

5 (16.41)

5 (16.41)

5 (16.41)

5 (16.41)

Degree of protection

 

IP66

IP66

IP66

IP66

Dimensions

 

 

 

 

 

  • Width

mm (in)

161 (6.34)

161 (6.34)

161 (6.34)

161 (6.34)

  • Height

mm (in)

135 (5.31)

135 (5.31)

135 (5.31)

135 (5.31)

  • Depth

mm (in)

270 (10.63)

270 (10.63)

270 (10.63)

270 (10.63)

Frame size

 

FSA

FSA

FSA

FSA

Weight, approx.

kg (lb)

2.1 (4.63)

2.1 (4.63)

2.1 (4.63)

2.1 (4.63)



1) The rated output current Irated is based on the duty cycle for high overload (HO).

2) Typical values. You can find additional information on the Internet at http://support.automation.siemens.com/WW/view/en/94059311.

3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %.

Line voltage
380 … 480 V 3 AC

 

PM240M Power Modules

 

 

6SL3517-1BE16-3AM0

6SL3517-1BE17-7AM0

6SL3517-1BE21-0AM0

Rated output current Irated1)

A

5.6

7.3

8.8

Maximum output current Imax

A

11.2

14.6

14.1

Rated power

kW (hp)

2.2 (3)

3 (4)

4 (5)

Rated pulse frequency

kHz

4

4

4

Efficiency η

%

97.6

97.6

97.7

Power loss 2)

At rated output current

kW

0.078

0.103

0.126

Cooling air requirement

m3/s (ft3/s)

0.024 (0.8)

0.024 (0.8)

0.024 (0.8)

Sound pressure level LpA (1 m)

dB

Rated input current 3)

A

5.3

6.9

8

Line supply connection
U1/L1, V1/L2, W1/L3, PE

 

 

 

 

  • Conductor cross-section (recommended)

mm2

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

PE connection

(external connection)

 

 

 

 

  • Conductor cross-section (recommended)

mm2

10

10

10

Motor connection
U2, V2, W2, PE, motor brake, temperature sensor

 

 

 

 

  • Conductor cross-section

mm2

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

1 ... 2.5
18 ... 14 AWG

Motor cable length, max.

Shielded

m (ft)

5 (16.41)

5 (16.41)

5 (16.41)

Degree of protection

 

IP66

IP66

IP66

Dimensions

 

 

 

 

  • Width

mm (in)

181 (7.13)

181 (7.13)

181 (7.13)

  • Height

mm (in)

135 (5.31)

135 (5.31)

135 (5.31)

  • Depth

mm (in)

309 (12.17)

309 (12.17)

309 (12.17)

Frame size

 

FSB

FSB

FSB

Weight, approx.

kg (lb)

3.4 (7.50)

3.4 (7.50)

3.4 (7.50)



1) The rated output current Irated is based on the duty cycle for high overload (HO).

2) Typical values. You can find additional information on the Internet at http://support.automation.siemens.com/WW/view/en/94059311.

3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %.