Input voltage | 3 × 324...572 V AC/480...745 V DC |
---|---|
Input current | 0.45 A (3×360 V AC); 0.3 A (3×520 V AC) |
Inrush current after 1 ms | max. 10 A |
Primary fusing external | max. 3 × 10 A |
Frequency | 50...60 Hz |
Standards | EN 60950-1, EN 61204-3, EN 55022 B, EN 61000-3-2, SEMI F47 |
---|---|
Relative humidity | 5...95 %, no condensation |
Efficiency | 86 % |
Mounting method | DIN-rail mountable TH35 (EN 60715) |
Dimensions H × W × D | 132×83×98 mm |
Protection | IP20 |
Temperature range | -25...+70 °C (storage temperature -40...+85 °C) |
Output voltage | 24 V DC (SELV), ±1 %; 22...28 V adjustable |
---|---|
Output current | 5 A (+55 °C); 3 A (+70 °C) |
Power Boost | Iout N × 150 % (min. 4 s) |
Mains failure bridging time | min. 30 ms (400 V AC) |
Ripple | max. 50 mVrms |
Unit protection | short-circuit and overload protected |
Spikes | max. 100 mV p-p |
LED display | LED (green): OK; LED (red): overload |
Parallel usage/serial usage | max. 5 units/max. 2 units |
country of origin | CZ |
---|---|
customs tariff number | 85044090 |
minimum order quantity | 1 |