Measuring relays for voltage monitoring DOLD
Показано товаров: 10 из 34
Артикул: 1325004
• According to IEC/EN 60 255, DIN VDE 0435-303
• Monitoring of undervoltage
• Without auxiliary supply
• Optionally fixed or settable response value
• N.C. circuit operation
• Optionally with off-delay t1
• Optionally with on-delay t2
• LED indicator for state of output relay
• 1 changeover contact
• Devices available in 2 enclosure versions:
IK 9173: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SK 9173: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width 17.5 mm
• Monitoring of undervoltage
• Without auxiliary supply
• Optionally fixed or settable response value
• N.C. circuit operation
• Optionally with off-delay t1
• Optionally with on-delay t2
• LED indicator for state of output relay
• 1 changeover contact
• Devices available in 2 enclosure versions:
IK 9173: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SK 9173: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width 17.5 mm
Артикул: 1325003
• According to IEC/EN 60 255, DIN VDE 0435-303
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
Артикул: 1325002
• According to IEC/EN 60 255, DIN VDE 0435-303
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
Артикул: 1325001
• According to IEC/EN 60 255, DIN VDE 0435-303
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
Артикул: 1325000
• According to IEC/EN 60 255, DIN VDE 0435-303
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
• Monitoring of undervoltage in 3-phase system
• Also for single phase
• Without auxiliary supply
• Optionally for 3p3w systems
• LED indicator for state of output relay
• Independent of phase sequence
• 1 or 2 changeover contacts
• Optionally fixed or settable response value
• As option with phase sequence detection
• Optionally with or without N
• Optionally with off-delay t1
• Opionally with on delay t2
• Devices available in 2 enclosure versions:
I-model: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
S-model: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width:
IK 9171, SK 9171: 17.5 mm
IL 9171, SL 9171: 35 mm
Артикул: 1324999
• According to IEC/EN 60 255, DIN VDE 0435-303
• Fast detection of undervoltage and phase failure in AC voltage
systems
• Detects voltage drops (reaction time ≤ 20 ms)
• Response value 0.8 or 0.7 UN selectable by wire link
• Without auxiliary supply
• De-energized on trip
• LED indicator for contact position
• Adjustable operate delay after return of voltage
• As option adjustable fleeting on make pulse after return of voltage
(variant BC 9190N.11/001)
• 1 changeover contact
• Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or
2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3/-4
• Width 22.5 mm
• Fast detection of undervoltage and phase failure in AC voltage
systems
• Detects voltage drops (reaction time ≤ 20 ms)
• Response value 0.8 or 0.7 UN selectable by wire link
• Without auxiliary supply
• De-energized on trip
• LED indicator for contact position
• Adjustable operate delay after return of voltage
• As option adjustable fleeting on make pulse after return of voltage
(variant BC 9190N.11/001)
• 1 changeover contact
• Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or
2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3/-4
• Width 22.5 mm
Артикул: 1324998
• According to EC/EN 60255-1, IEC/EN 60255-26, VDE 0435 part 303
• 3-phase
• For nominal voltage of 3 AC 100 / 57 to 690 / 400 V
• Measures arithmetic mean value
• Adjustable operate and release value
• For 3p3w or 3p4w systems
• BA 9043 optionally with adjustable time delay
• Closed circuit operation
• LED indicator for operation and state of contact
• Insensitive to harmonics
• Frequency up to 400 Hz
• Width 45 mm
• 3-phase
• For nominal voltage of 3 AC 100 / 57 to 690 / 400 V
• Measures arithmetic mean value
• Adjustable operate and release value
• For 3p3w or 3p4w systems
• BA 9043 optionally with adjustable time delay
• Closed circuit operation
• LED indicator for operation and state of contact
• Insensitive to harmonics
• Frequency up to 400 Hz
• Width 45 mm
Артикул: 1324997
• According to EC/EN 60255-1, IEC/EN 60255-26, VDE 0435 part 303
• 3-phase
• For nominal voltage of 3 AC 100 / 57 to 690 / 400 V
• Measures arithmetic mean value
• Adjustable operate and release value
• For 3p3w or 3p4w systems
• BA 9043 optionally with adjustable time delay
• Closed circuit operation
• LED indicator for operation and state of contact
• Insensitive to harmonics
• Frequency up to 400 Hz
• Width 45 mm
• 3-phase
• For nominal voltage of 3 AC 100 / 57 to 690 / 400 V
• Measures arithmetic mean value
• Adjustable operate and release value
• For 3p3w or 3p4w systems
• BA 9043 optionally with adjustable time delay
• Closed circuit operation
• LED indicator for operation and state of contact
• Insensitive to harmonics
• Frequency up to 400 Hz
• Width 45 mm
Артикул: 1325008
• According to IEC/EN 60255-1
• For installations according to DIN VDE 0100-718 and DIN VDE 0108-100
(replacement of DIN VDE 0108 )
• Detection of undervoltage in 3-phase systems
• Without separately auxiliary voltage
(internal supply from all 3 phases)
• LED indication for für operation voltage and contact position
• De-energised on trip
• RK 9871.71: 1 changeover contact
RK 9871.72: 2 changeover contacts
• With fixed time delay of 0.5s for fault indication
• With fixed time delay of 1min for reset
• With fixed response value at AC 195.5V
• As option with test-button for function control
• Width 17,5 mm
• For installations according to DIN VDE 0100-718 and DIN VDE 0108-100
(replacement of DIN VDE 0108 )
• Detection of undervoltage in 3-phase systems
• Without separately auxiliary voltage
(internal supply from all 3 phases)
• LED indication for für operation voltage and contact position
• De-energised on trip
• RK 9871.71: 1 changeover contact
RK 9871.72: 2 changeover contacts
• With fixed time delay of 0.5s for fault indication
• With fixed time delay of 1min for reset
• With fixed response value at AC 195.5V
• As option with test-button for function control
• Width 17,5 mm
Артикул: 1324996
• According to IEC/EN 60 255, DIN VDE 0435-303
• Monitoring of overvoltage
• Without auxiliary supply
• Settable response value
• De-energized on trip
• LED indicator for state of output relay
• 1 changeover contact
• As option energized on trip
• As option with delay t1 on trip
• As option with delay t2 on reset
• Devices available in 2 enclosure versions:
IK 9171: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SK 9171: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width 17.5 mm
• Monitoring of overvoltage
• Without auxiliary supply
• Settable response value
• De-energized on trip
• LED indicator for state of output relay
• 1 changeover contact
• As option energized on trip
• As option with delay t1 on trip
• As option with delay t2 on reset
• Devices available in 2 enclosure versions:
IK 9171: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SK 9171: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
• Width 17.5 mm