Emergency stop modules DOLD
Показано товаров: 7 из 17
Артикул: 1324745
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• Output: max. 3 NO contacts, see contacts
• Single and 2-channel operation
• Line fault detection on On-button
• Manual restart or automatic restart, switch S2
• With or without cross fault monitoring in the E-stop loop, switch S1
• LED indicator for channel 1 and 2 and Power
• Removable terminal strips
• Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• Width 22.5 mm
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• Output: max. 3 NO contacts, see contacts
• Single and 2-channel operation
• Line fault detection on On-button
• Manual restart or automatic restart, switch S2
• With or without cross fault monitoring in the E-stop loop, switch S1
• LED indicator for channel 1 and 2 and Power
• Removable terminal strips
• Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• Width 22.5 mm
Артикул: 1324744
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• Output: 2 NO contacts for AC 250 V
• 1-channel or 2-channel connection
• LED displays for channels 1 and 2
• Overvoltage and short circuit protection
• Wire connection: also 2 x 1,5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or
2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• Width 45 mm
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• Output: 2 NO contacts for AC 250 V
• 1-channel or 2-channel connection
• LED displays for channels 1 and 2
• Overvoltage and short circuit protection
• Wire connection: also 2 x 1,5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or
2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• Width 45 mm
Артикул: 1324743
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• 1- or 2-channel operation
• Output: 1 NO contact and 1 semiconductor monitoring output
• LED-indicator for relay 1 / 2 and supply voltage
• Width 17.5 mm and 64 mm depth
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• 1- or 2-channel operation
• Output: 1 NO contact and 1 semiconductor monitoring output
• LED-indicator for relay 1 / 2 and supply voltage
• Width 17.5 mm and 64 mm depth
Артикул: 1324742
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• According to EN 50156-1 for furnaces
• Single channel or two-channel operation
• Output: max. 4 NO contacts
• AC 230 V model with galvanic separation
• LED indicator for channel 1 / 2 and state of operation
• Short circuit detection between terminal Y1 and common
• BG 5924 with:
- Removable terminal strips
- Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• BG 5924: width 22.5 mm
• IP 5924: width 70 mm
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• According to EN 50156-1 for furnaces
• Single channel or two-channel operation
• Output: max. 4 NO contacts
• AC 230 V model with galvanic separation
• LED indicator for channel 1 / 2 and state of operation
• Short circuit detection between terminal Y1 and common
• BG 5924 with:
- Removable terminal strips
- Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• BG 5924: width 22.5 mm
• IP 5924: width 70 mm
Артикул: 1324740
• According to
- Performance Level (PL) d and category 3 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 2 to IEC/EN 62061
- Safety Integrity Level (SIL 2) to IEC/EN 61508
• Single channel operation
• Output: max. 4 NO contacts
• AC 230 V model with galvanic separation
• LED indicator for channel 1 / 2 and state of operation
• Short circuit detection between terminal Y1 and common
• Wire connection: also 2 x 1.5 mm2 stranded ferruled, or
2 x 2.5 mm2 solid DIN 46 228-1/-2/-3/-4
• as option with pluggable terminal blocks for easy exchange
of devices
- with screw terminals
- or with cage clamp terminals
• Width 22.5 mm
- Performance Level (PL) d and category 3 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 2 to IEC/EN 62061
- Safety Integrity Level (SIL 2) to IEC/EN 61508
• Single channel operation
• Output: max. 4 NO contacts
• AC 230 V model with galvanic separation
• LED indicator for channel 1 / 2 and state of operation
• Short circuit detection between terminal Y1 and common
• Wire connection: also 2 x 1.5 mm2 stranded ferruled, or
2 x 2.5 mm2 solid DIN 46 228-1/-2/-3/-4
• as option with pluggable terminal blocks for easy exchange
of devices
- with screw terminals
- or with cage clamp terminals
• Width 22.5 mm
Артикул: 1324741
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• According to EN 50156-1 for furnaces
• Single channel or two-channel operation
• Output: max. 4 NO contacts
• AC 230 V model with galvanic separation
• LED indicator for channel 1 / 2 and state of operation
• Short circuit detection between terminal Y1 and common
• BG 5924 with:
- Removable terminal strips
- Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• BG 5924: width 22.5 mm
• IP 5924: width 70 mm
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• According to EN 50156-1 for furnaces
• Single channel or two-channel operation
• Output: max. 4 NO contacts
• AC 230 V model with galvanic separation
• LED indicator for channel 1 / 2 and state of operation
• Short circuit detection between terminal Y1 and common
• BG 5924 with:
- Removable terminal strips
- Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• BG 5924: width 22.5 mm
• IP 5924: width 70 mm
Артикул: 1324738
• According to
-- Performance Level (PL) e and category 4 to EN ISO 13849-1
-- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
-- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• According to EN 50156-1 for furnaces
• 2-channel operation
• Forcibly guided output contacts
• With or without cross fault monitoring in the E-stop loop, switch S1
• Manual restart or automatic restart, switch S2
• LED indicator for channel 1, 2 and Netz
• Width 17,5 mm
-- Performance Level (PL) e and category 4 to EN ISO 13849-1
-- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
-- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• According to EN 50156-1 for furnaces
• 2-channel operation
• Forcibly guided output contacts
• With or without cross fault monitoring in the E-stop loop, switch S1
• Manual restart or automatic restart, switch S2
• LED indicator for channel 1, 2 and Netz
• Width 17,5 mm