1-phase, 24 V DC (for S7-300 and ET200M) Siemens

Обзор
The design and functionality of the SIMATIC PS 305 and 307 single-phase load power supplies (system and load current supply) with automatic range switchover of the input voltage are an optimal match for the SIMATIC S7-300 PLC. By means of the connecting comb that is supplied with the system and load current supply, the supply to the CPU is quickly established. It is also possible to provide a 24 V supply to other S7-300 system components, input/output circuits of the input/output modules and, if necessary, the sensors and actuators. Comprehensive certifications, such as UL, ATEX or GL facilitate universal use (does not apply to outdoor use).
Note
SIPLUS extreme products are based on Siemens standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
SIPLUS PS 305, PS 307 | |||
Article No. | 6AG1305-1BA80-2AA0 | 6AG1307-1EA01-7AA0 | 6AG1307-1KA02-7AA0 |
Article number based on | 6ES7305-1BA80-0AA0 | 6ES7307-1EA01-0AA0 | 6ES7307-1KA02-0AA0 |
Ambient temperature range | -25 ... +70 °C | ||
Conformal coating | Coating of the printed circuit boards and the electronic components | ||
Technical specifications | The technical specifications of the standard product apply, except for the ambient conditions. | ||
Ambient conditions | |||
Extended range of environmental conditions | |||
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // | ||
Relative humidity | |||
| 100 %; RH incl. bedewing/frost (no commissioning in bedewed state) | ||
Resistance | |||
| Yes; Class 3B2 mold and fungal spores (except fauna); the supplied plug covers must remain in place on the unused interfaces during operation. | ||
| Yes; Class 3C4 (RH < 75%) incl. salt spray in accordance with EN 60068-2-52 (severity 3); the supplied plug covers must remain in place on the unused interfaces during operation. | ||
| Yes; Class 3S4 incl. sand, dust; the supplied plug covers must remain in place on unused interfaces during operation. | ||
Дизайн
- The system and load current supplies are screwed directly onto the S7-300 standard mounting rail and can be mounted directly to the left of the CPU (no installation clearance required)
- Diagnostic LED for indicating “Output voltage 24 V DC O.K."
- ON/OFF switches (operation/stand-by) for possible swapping of modules
- Strain-relief assembly for input voltage connection cable
Функции
- Connection to all 1-phase 50/60 Hz networks (120 / 230 V AC) through automatic range switching (PS307) or manual switching (PS307, outdoor)
- Short-term power failure backup
- Output voltage 24 V DC, stabilized, short circuit-proof, open circuit-proof
- Parallel connection of two power supplies for enhanced performance
Технические данные
Order number | 6AG1305-1BA80-2AA0 | 6AG1307-1EA01-7AA0 | 6AG1307-1KA02-7AA0 | |
|---|---|---|---|---|
SIPLUS PS S7-300 PS305 (EN50155) | SIPLUS PS307 AC 120/230V / DC 24 V/5 A | SIPLUS_PS307_10A | ||
Supply voltage |
|
|
| |
Rated value (DC) | ||||
| Yes | |||
| Yes | |||
| Yes | |||
| Yes | |||
| Yes; Rated value 110 V DC | |||
permissible range, lower limit (DC) | 16.8 V | |||
permissible range, upper limit (DC) | 138 V | |||
Rated value (AC) | ||||
| Yes; 85 to 132 V AC | Yes; 85 to 132 V AC | ||
| Yes; 170 to 264 V AC | Yes; 170 to 264 V AC | ||
Overvoltage strength | 2.3x Ue rated, 1.3 ms | 2.3x Ue rated, 1.3 ms | ||
Line frequency |
|
|
| |
| 47 Hz | 47 Hz | ||
| 63 Hz | 63 Hz | ||
Mains buffering |
|
|
| |
| 10 ms | 20 ms; min., for Ia rated | 20 ms; min., for Ia rated and Ue = 93 / 187 V | |
| 1 s | 1 s | 1 s | |
Input current |
|
|
| |
Rated value at 24 V DC | 2.7 A | |||
Rated value at 48 V DC | 1.3 A | |||
Rated value at 72 V DC | 0.9 A | |||
Rated value at 96 V DC | 0.65 A | |||
Rated value at 110 V DC | 0.6 A | |||
Rated value at 120 V AC | 2.3 A | 4.2 A | ||
Rated value at 230 V AC | 1.2 A | 1.9 A | ||
Inrush current, max. | 20 A | 20 A; max. at 25 °C, duration max. 3 ms | 55 A; max. at 25 °C, duration max. 3 ms | |
I²t | 5 A²·s | 1.2 A²·s | 3.3 A²·s | |
Leakage current, typ. | 0.7 mA | 0.5 mA | 0.6 mA | |
Leakage current, max. | 3.5 mA | 3.5 mA | 3.5 mA | |
Overload capability overload current | 270 ms on short circuit during startup and operation | 80 ms on short circuit during startup and operation | ||
Output voltage |
|
|
| |
Rated value (DC) | 24 V | 24 V | 24 V; stable at no-load max. 2.5 s | |
permissible range, lower limit (DC) | 23.27 V | 23.27 V | 23.27 V | |
permissible range, upper limit (DC) | 24.72 V | 24.72 V | 24.72 V | |
Power up time, max. | 3 s | 2 ms | 2 s | |
Voltage rise time, typ. | 10 ms | 10 ms | ||
Overvoltage protection | Additional control circuit, cutoff at < 28.8 V, automatic restart | Additional control circuit, cutoff at < 28.8 V, automatic restart | ||
Short-circuit strength | electronic trip, automatic restart | electronic trip, automatic restart | ||
Output current |
|
|
| |
Current output (rated value) | 2 A; can be switched in parallel | 5 A; 3 A @ > 60 °C, can be switched in parallel | 10 A; 7 A @ > 60 °C, can be switched in parallel | |
short-circuit protection | Yes; Electronic | Yes; Electronic | ||
Residual ripple, typ. | 30 mV; Peak - peak | 10 mV; Peak - peak | 15 mV; Peak - peak | |
Residual ripple, max. | 150 mV; Peak - peak | 50 mV; Peak - peak | 50 mV; Peak - peak | |
Continuous short-circuit current, max. | 12 A | |||
Power |
|
|
| |
Power consumption, typ. | 64 W | 138 W | 240 W | |
Efficiency | 75 % | 90 %; approx., at Ua rated, Ia rated | ||
Power loss |
|
|
| |
Power loss, typ. | 16 W | 18 W; approx., at Ua rated, Ia rated | 27 W; approx., at Ua rated, Ia rated | |
Interrupts/diagnostics/status information |
|
|
| |
Diagnostics indication LED |
|
|
| |
| Yes; OK for 24 V | Yes; OK for 24 V | Yes; OK for 24 V | |
Potential separation |
|
|
| |
primary/secondary | Yes; SELV output voltage Ua according to EN 60950-1 and EN 50178 | Yes; SELV output voltage Ua according to EN 60950-1 and EN 50178 | Yes; SELV output voltage Ua according to EN 60950-1 and EN 50178 | |
SELV | Yes | Yes | ||
Isolation |
|
|
| |
Isolation tested with | Rated insulation voltage (24 V against input): 150 V AC tested with: 2800 V DC | Rated insulation voltage (24 V against L1) 250 V AC, tested with 4200 V DC | Rated insulation voltage (24 V against L1) 250 V AC, tested with 4200 V DC | |
EMC |
|
|
| |
EMC interference immunity | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 | |
EMC interference emission | EN 55011 Class A | EN 55022 Class B | EN 55022 Class B | |
Degree and class of protection |
|
|
| |
IP degree of protection | IP20 | IP20 | IP20 | |
Protection class | 1 | 1 | 1; with protective conductor | |
Standards, approvals, certificates |
|
|
| |
CE mark | Yes | Yes | Yes | |
EN 50155 | Yes; T1 Cat. 1 Cl. A/B horizontal mounting position | |||
Standard for line harmonics limit | EN 61000-3-2 | EN 61000-3-2 | ||
Ambient conditions |
|
|
| |
Ambient temperature during operation |
|
|
| |
| -25 °C; = Tmin | -25 °C; = Tmin | -25 °C; = Tmin | |
| 70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/UL hazardous use applies | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | |
Extended ambient conditions |
|
|
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity |
|
|
| |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance |
|
|
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions |
|
|
| |
Width | 80 mm | 60 mm | 80 mm | |
Height | 125 mm | 125 mm | 125 mm | |
Depth | 120 mm | 120 mm | 120 mm | |
Weights |
|
|
| |
Weight, approx. | 740 g | 0.6 kg | 0.8 kg | |






Ответ от производителя может занять до 5 дней и более.