Технические данные
Comparison of SIMATIC PCS 7 OS Clients 427D and 477D
SIMATIC PCS7 OS Clients based on Microbox | ||
---|---|---|
Types | SIMATIC PCS 7 OS Client 427D | SIMATIC PCS 7 OS Client 477D |
Design and equipment features | ||
Design |
|
|
Degree of protection in accordance with IEC 60529 | IP20 | IP65 front; IP20 rear (enclosure) |
CPU | ||
| Intel Core i7-3517UE 1.7 GHz | Intel Core i7-3517UE 1.7 GHz |
| 4 MB | 4 MB |
Main memory (module up to 8 GB operable without/with ECC) | 4 GB DDR3-SDRAM 1066 (1 SO‑DIMM module without ECC) | 4 GB DDR3-SDRAM 1066 (1 SO‑DIMM module without ECC) |
Graphic | ||
| Intel HD4000 integrated in the chipset | Intel HD4000 integrated in the chipset |
| 32 ... 512 MB shared memory | 32 ... 512 MB shared memory |
| ||
| Up to 1920 × 1200, 60 Hz | Up to 1920 × 1200, 60 Hz |
| Up to 1920 × 1200, 60 Hz | Up to 1920 × 1200, 60 Hz |
| – | 22" Touch Panel with LED backlight |
| – | 1920 × 1080, 24-bit colors |
| – | 30 000 h |
Storage media, alternative | ||
| 1 × 2.5" SATA-HDD 320 GB | 1 × 2.5" SATA-HDD 320 GB |
| 1 × 2.5" SATA-SSD 160 GB (eMLC) | 1 × 2.5" SATA-SSD 160 GB (eMLC) |
Storage media, additive | ||
| Connectable via USB (not included in scope of delivery) | Connectable via USB (not included in scope of delivery) |
Interfaces | ||
| 2 × Ethernet interfaces (RJ45) Intel 82579LM and Intel 82574L; 10/100/1000 Mbps, isolated, teaming-capable | 2 × Ethernet interfaces (RJ45) Intel 82579LM and Intel 82574L; 10/100/1000 Mbps, isolated, teaming-capable |
| 4 × USB 3.0 rear, max. 2 × high-current can be operated simultaneously | 4 × USB 3.0 rear, max. 2 × high-current can be operated simultaneously 1 × USB 2.0 front, high current |
| 1 × COM1 RS 232, 115 Kbps max., 9-pin D-sub connector | 1 × COM1 RS 232, 115 Kbps max., 9-pin D-sub connector |
| – | – |
| 1 × DVI-I (DVI/VGA combined) 1 × display port (DPP); DVI via DPP-to-DVI adapter | 1 × DVI-I (DVI/VGA combined) 1 × display port (DPP); DVI via DPP-to-DVI adapter |
| Connectable via USB (keyboard and mouse not included in scope of delivery) | Connectable via USB (keyboard and mouse not included in scope of delivery) |
LED displays |
| – |
Operating system, basic software | ||
Operating system | Windows 7 Ultimate SP1, 64-bit, multi-language (English, German, French, Italian, Spanish, Chinese) | Windows 7 Ultimate SP1, 64-bit, multi-language (English, German, French, Italian, Spanish, Chinese) |
System-tested SIMATIC industrial software | SIMATIC IPC DiagMonitor integrated in pre-installation | SIMATIC IPC DiagMonitor integrated in pre-installation |
Monitoring and diagnostics functions | ||
Watchdog |
|
|
Temperature |
(via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management) |
(via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management) |
Storage media | S.M.A.R.T. functionality | S.M.A.R.T. functionality |
Battery monitoring | Status readable via battery status register; remaining life after reaching the warning level at least 1 month | Status readable via battery status register; remaining life after reaching the warning level at least 1 month |
Operating hours counter | (via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management) | (via SIMATIC IPC DiagMonitor and SIMATIC PCS 7 Asset Management) |
Noise emission | ||
Operating noise | < 40 dB (A) according to DIN 45635‑1 | < 40 dB (A) according to DIN 45635‑1 |
Electromagnetic compatibility (EMC) | ||
Interference emission | EN 61000‑6‑3, EN 61000‑6‑4, CISPR220 Class B; FCC Class A | EN 61000-6-4; CISPR 22 Class A; FCC Class A |
Immunity to conducted interference on the supply cables | ±2 kV (according to IEC 61000-4‑4; burst) ±1 kV (according to IEC 61000-4‑5; symmetrical surge) ±2 kV (according to IEC 61000-4‑5; asymmetrical surge) | ±2 kV (according to IEC 61000-4‑4; burst) ±1 kV (according to IEC 61000-4‑5; symmetrical surge) ±2 kV (according to IEC 61000-4‑5; asymmetrical surge) |
Noise immunity on signal cables | ±1 kV (according to IEC 61000-4‑4; burst; length < 3 m) ±2 kV (according to IEC 61000-4‑4; burst; length > 3 m) ±2 kV (according to IEC 61000-4‑5; surge; length > 30 m) | ±1 kV (according to IEC 61000-4‑4; burst; length < 3 m) ±2 kV (according to IEC 61000-4‑4; burst; length > 3 m) ±2 kV (according to IEC 61000-4‑5; surge; length > 30 m) |
Immunity to static discharge in accordance with IEC 61000-4-2 | ±6 kV contact discharge ±8 kV air discharge | ±6 kV contact discharge at front ±4 kV contact discharge at enclosure rear ±8 kV air discharge |
Immunity to radio frequency interference | 10 V/m, 80 ... 1 000 MHz and 1.4 ... 2 GHz, 80 % AM to IEC 61000‑4‑3 1 V/m, 2 ... 2.7 GHz, 80 % AM to IEC 61000‑4‑3 10 V, 10 kHz ... 80 MHz, 80 % AM to IEC 61000‑4‑6 | 10 V/m, 80 ... 1 000 MHz, 80 % AM to IEC 61000‑4‑3 1 V/m, 2 ... 2.7 GHz 3 V/m, 2 ... 2.7 GHz 10 V, 10 kHz ... 80 MHz to IEC 61000‑4‑6 |
Immunity to magnetic fields | 100 A/m, 50/60 Hz according to IEC 61000‑4‑8 | 100 A/m, 50/60 Hz according to IEC 61000‑4‑8 |
Climatic conditions | ||
Temperature | Tested according to IEC 60068‑2‑1, IEC 60068‑2‑2, IEC 60068‑2‑14 | Tested according to IEC 60068‑2‑1, IEC 60068‑2‑2 |
| ||
| +5 ... +40 °C1) | – |
| 0 … +40 °C | – |
| 0 ... +50 °C1) | – |
| ||
| +5 ... +35 °C1) | – |
| 0 … +40 °C | – |
| 0 … +45 °C1) | – |
| ||
| – | +5 ... +40 °C |
| – | 0 … +45 °C |
| ||
| – | +5 ... +35 °C |
| – | 0 … +40 °C |
| ||
| -40 … +60 °C | -20 … +60 °C |
| -40 … +70 °C | -20 … +60 °C |
| ||
| Max. 10 °C/h | – |
| 20 °C/h; no condensation | 20 °C/h; no condensation |
Relative humidity | Tested according to IEC 60068‑2‑78, IEC 60068‑2‑30 | Tested according to IEC 60068‑2‑78, IEC 60068‑2‑30 |
| 5 ... 80 % at 25 °C (no condensation) | 5 ... 85 % at 30 °C (no condensation) |
| 5 ... 95 % at 25 °C (no condensation) | 5 ... 95 % at 25 °C (no condensation) |
Air pressure | Tested according to IEC 60068-2-13 | Tested according to IEC 60068-2-13 |
| 1080 ... 795 hPa, corresponds to an altitude of ‑1000 … 2000 m | 1080 ... 795 hPa, corresponds to an altitude of ‑1000 … 2000 m |
| 1080 ... 660 hPa, corresponds to an altitude of ‑1000 … 3500 m | 1080 ... 660 hPa, corresponds to an altitude of ‑1000 … 3500 m |
Mechanical environmental conditions | ||
Vibrations | Tested according to IEC 60068‑2‑6 | Tested according to IEC 60068‑2‑6 |
| ||
| 5 … 9 Hz: 3.5 mm 9 … 500 Hz: 9.8 m/s² | 5 … 8.4 Hz: 3.5 mm 8.4 … 500 Hz: 9.8 m/s² |
| 10 … 58 Hz: 0.0375 mm | 10 … 58 Hz: 0.375 mm 58 ... 200 Hz: 4.9 m/s² |
| Starting prohibited | – |
| 5 … 9 Hz: 3.5 mm 9 … 500 Hz: 9.8 m/s² | 5 … 8.4 Hz: 3.5 mm 8.4 … 500 Hz: 9.8 m/s² |
Shock resistance | Tested according to IEC 60068‑2‑27 | Tested according to IEC 60068‑2‑27, IEC 60068‑2‑29 |
| Without hard disk: 150 m/s², 11 ms With hard disk: 50 m/s², 30 ms | 50 m/s², 30 ms |
| 250 m/s², 6 ms | 250 m/s², 6 ms |
Standards, specifications, approvals | ||
CE according to 2004/108/EC, 2006/95/EC | Yes | Yes |
Industrial area of application | ||
| EN 61000-6-4: 2007 | EN 61000-6-4: 2007 |
| EN 61000-6-2: 2005 | EN 61000-6-2: 2005 |
Application in apartments, business, trade, small enterprises | ||
| EN 61000-6-3: 2007 | – |
| EN 61000-6-1: 2007 | – |
cUlus | Underwriters Laboratories (UL) according to standard UL 60950‑1 and UL 508 as well as Canadian National Standard CAN/CSA-C22.2 No. 60950-1 (I.T.E) and CAN/CSA-C22.2 No. 142 (IND.CONT.EQ) | Underwriters Laboratories (UL) according to standard UL 508 and Canadian National Standard CAN/CSA-C22.2 No. 142 (IND.CONT.EQ) |
USA: FCC Rules, Part 15, Class A | Yes | Yes |
Canada: ICES-003, Class A; NMB‑003, Class A | Yes | Yes |
Australia/New Zealand: EN 61000-6-4:2007 | Yes | Yes |
Korea: Korean Certification (KC Mark) | Yes | Yes |
Special features | ||
Quality assurance | According to ISO 9001 | According to ISO 9001 |
Power supply (electrically isolated) | ||
Supply voltage | 24 V DC (19.2 ... 28.8 V) | 24 V DC (19.2 ... 28.8 V) |
Short-term voltage interruption | Min. 15 ms (at 20.4 V) Max. 10 events per hour; recovery time of at least 1 s | Min. 20 ms Max. 10 events per hour; recovery time of at least 1 s |
Max. power consumption (at 24 V DC) | 64.8 W | 74 W |
Dimensions and weights | ||
External dimensions (W × H × D in mm) | 262 × 133 × 50.5 | 560 × 380 × 84 |
Mounting cutout (W × H in mm) | – | 540 × 360 |
Mounting depth (D in mm) | – | 75.5 |
Weight | Approx. 2 kg | Approx. 7 kg |
1) If the "Turbo Mode Level" setting in the BIOS Setup "Power" menu is not set to "Temperature optimized", the maximum ambient temperature must be reduced by 5 °C.
2) RAL = Restricted Access Location: Installation of device in operating environment with restricted access, e.g. a locked control cabinet