Motor reactors Siemens

Обзор
Motor reactors reduce the voltage load on the motor windings by reducing the voltage gradients on the motor terminals generated when the converter is used. At the same time, the capacitive charge/discharge currents that place an additional load on the converter output when long motor cables are used are reduced. For group drives, output reactors should always be used. The maximum permissible output frequency when a motor reactor is used is150 Hz.
The motor reactor must be installed as close as possible to the Motor Module or Power Module. Up to 2 motor reactors can be connected in series.
Motor reactors are approved for use only in conjunction with Vector and V/f control modes.
For additional notes on the use of motor reactors, please refer to the SINAMICS Low Voltage Engineering Manual.
Технические данные
Line voltage 380 … 480 V 3 AC | Motor reactor (for pulse frequencies of 2 kHz to 4 kHz) | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
| 6SL3000-2BE32-1AA0 | 6SL3000-2BE32-6AA0 | 6SL3000-2BE33-2AA0 | 6SL3000-2BE33-8AA0 | 6SL3000-2BE35-0AA0 | ||||||
Rated current | A | 210 | 260 | 310 | 380 | 490 | |||||
Power loss, max. 1) | kW | 0.486 | 0.5 | 0.47 | 0.5 | 0.5 | |||||
Load connection |
| 1 × hole for M10 | 1 × hole for M10 | 1 × hole for M10 | 1 × hole for M10 | 1 × hole for M12 | |||||
PE connection |
| M8 screw | M8 screw | M8 screw | M8 screw | M8 screw | |||||
Cable length, max. between the motor reactor and motor | |||||||||||
(number of reactors in series) |
| (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) |
| m | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 |
| m | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 | |||||
Dimensions | |||||||||||
| mm | 300 | 300 | 300 | 300 | 300 | |||||
| mm | 285 | 315 | 285 | 285 | 365 | |||||
| mm | 257 | 277 | 257 | 277 | 277 | |||||
Weight, approx. | kg | 66 | 66 | 66 | 73 | 100 | |||||
Conformity | CE | CE | CE | CE | CE | ||||||
Approvals, according to |
| cURus | cURus | cURus | cURus | cURus | |||||
Suitable for Power Module |
| 6SL3310-1TE32-1AA3 6SL3315-1TE32-1AA3 | 6SL3310-1TE32-6AA3 6SL3315-1TE32-6AA3 | 6SL3310-1TE33-1AA3 6SL3315-1TE33-1AA3 | 6SL3310-1TE33-8AA3 | 6SL3310-1TE35-0AA3 6SL3315-1TE35-0AA3 | |||||
Suitable for Motor Module |
| 6SL3320-1TE32-1AA3 6SL3325-1TE32-1AA3 | 6SL3320-1TE32-6AA3 6SL3325-1TE32-6AA3 | 6SL3320-1TE33-1AA3 6SL3325-1TE33-1AA3 | 6SL3320-1TE33-8AA3 | 6SL3320-1TE35-0AA3 6SL3325-1TE35-0AA3 | |||||
| A | 210 | 260 | 310 | 380 | 490 | |||||
| kW | 110 | 132 | 160 | 200 | 250 |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
Line voltage 380 … 480 V 3 AC | Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 6SL3000-2AE36-1AA0 | 6SL3000-2AE38-4AA0 | 6SL3000-2AE41-0AA0 | 6SL3000-2AE41-4AA0 | |||||||||
Rated current | A | 605 | 745 | 840 | 985 | 1260 | 1405 | ||||||
Power loss, max. 1) | kW | 0.9 | 0.84 | 0.943 | 1.062 | 0.9 | 1.054 | ||||||
Load connection |
| 1 × hole for M12 | 1 × hole for M12 | 1 × hole for M12 | 1 × hole for M12 | 2 × hole for M12 | 2 × hole for M12 | ||||||
PE connection |
| M10 screw | M10 screw | M10 screw | M10 screw | M10 screw | M10 screw | ||||||
Cable length, max. between the motor reactor and motor | |||||||||||||
(number of reactors in series) |
| (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) |
| m | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 |
| m | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 | IP00 | ||||||
Dimensions | |||||||||||||
| mm | 410 | 410 | 410 | 410 | 460 | 460 | ||||||
| mm | 392 | 392 | 392 | 392 | 392 | 392 | ||||||
| mm | 292 | 292 | 292 | 302 | 326 | 326 | ||||||
Weight, approx. | kg | 130 | 140 | 140 | 146 | 179 | 179 | ||||||
Conformity | CE | CE | CE | CE | CE | CE | |||||||
Approvals, according to |
| cURus | cURus | cURus | cURus | cURus | cURus | ||||||
Suitable for Motor Module |
| 6SL3320-1TE36-1AA3 6SL3325-1TE36-1AA3 | 6SL3320-1TE37-5AA3 | 6SL3320-1TE38-4AA3 6SL3325-1TE38-4AA3 | 6SL3320-1TE41-0AA3 6SL3325-1TE41-0AA3 | 6SL3320-1TE41-2AA3 | 6SL3320-1TE41-4AA3 6SL3325-1TE41-4AA3 | ||||||
| A | 605 | 745 | 840 | 985 | 1260 | 1405 | ||||||
| kW | 315 | 400 | 450 | 560 | 710 | 800 |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
Line voltage 500 … 690 V 3 AC | Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 6SL3000-2AH31-0AA0 | 6SL3000-2AH31-5AA0 | 6SL3000-2AH31-8AA0 | 6SL3000-2AH32-4AA0 | |||||||||
Rated current | A | 85 | 100 | 120 | 150 | 175 | 215 | ||||||
Power loss, max. 1) | kW | 0.257 | 0.3 | 0.318 | 0.335 | 0.4 | 0.425 | ||||||
Load connection |
| Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | ||||||
PE connection |
| M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | ||||||
Cable length, max. between the motor reactor and motor | |||||||||||||
(number of reactors in series) |
| (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) |
| m | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 |
| m | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 | IP00 | ||||||
Dimensions | |||||||||||||
| mm | 270 | 270 | 270 | 270 | 300 | 300 | ||||||
| mm | 248 | 248 | 248 | 248 | 285 | 285 | ||||||
| mm | 200 | 200 | 200 | 200 | 212 | 212 | ||||||
Weight, approx. | kg | 25 | 25 | 25,8 | 25,8 | 34 | 34 | ||||||
Conformity | CE | CE | CE | CE | CE | CE | |||||||
Approvals, according to 2) |
| cURus | cURus | cURus | cURus | cURus | cURus | ||||||
Suitable for Motor Module |
| 6SL3320-1TG28-5AA3 | 6SL3320-1TG31-0AA3 6SL3325-1TG31-0AA3 | 6SL3320-1TG31-2AA3 | 6SL3320-1TG31-5AA3 6SL3325-1TG31-5AA3 | 6SL3320-1TG31-8AA3 | 6SL3320-1TG32-2AA3 6SL3325-1TG32-2AA3 | ||||||
| A | 85 | 100 | 120 | 150 | 175 | 215 | ||||||
| kW | 75 | 90 | 110 | 132 | 160 | 200 |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
2) Only for line voltages 500 ... 600 V 3 AC.
Line voltage 500 … 690 V 3 AC | Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 6SL3000-2AH32-6AA0 | 6SL3000-2AH33-6AA0 | 6SL3000-2AH34-5AA0 | 6SL3000-2AH34-7AA0 | 6SL3000-2AH35-8AA0 | 6SL3000-2AH38-1AA0 | |||||||
Rated current | A | 260 | 330 | 410 | 465 | 575 | 735 | ||||||
Power loss, max. 1) | kW | 0.44 | 0.45 | 0.545 | 0.72 | 0.8 | 0.96 | ||||||
Load connection |
| Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M12 screw | Flat connector for M12 screw | Flat connector for M12 screw | Flat connector for M12 screw | ||||||
PE connection |
| M6 screw | M6 screw | M8 screw | M8 screw | M8 screw | M8 screw | ||||||
Cable length, max. between the motor reactor and motor | |||||||||||||
(number of reactors in series) |
| (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) |
| m | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 |
| m | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | IP00 | IP00 | ||||||
Dimensions | |||||||||||||
| mm | 300 | 300 | 350 | 410 | 410 | 410 | ||||||
| mm | 285 | 285 | 330 | 392 | 392 | 392 | ||||||
| mm | 212 | 212 | 215 | 292 | 292 | 279 | ||||||
Weight, approx. | kg | 40 | 46 | 68 | 80 | 80 | 146 | ||||||
Conformity | CE | CE | CE | CE | CE | CE | |||||||
Approvals, according to 2) |
| cURus | cURus | cURus | cURus | cURus | cURus | ||||||
Suitable for Motor Module |
| 6SL3320-1TG32-6AA3 | 6SL3320-1TG33-3AA3 6SL3325-1TG33-3AA3 | 6SL3320-1TG34-1AA3 | 6SL3320-1TG34-7AA3 | 6SL3320-1TG35-8AA3 6SL3325-1TG35-8AA3 | 6SL3320-1TG37-4AA3 | ||||||
| A | 260 | 330 | 410 | 465 | 575 | 735 | ||||||
| kW | 250 | 315 | 400 | 450 | 560 | 710 |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
2) Only for line voltages 500 ... 600 V 3 AC.
Line voltage 500 … 690 V 3 AC | Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz) | ||||||||
---|---|---|---|---|---|---|---|---|---|
| 6SL3000-2AH38-1AA0 | 6SL3000-2AH41-0AA0 | 6SL3000-2AH41-3AA0 | ||||||
Rated current | A | 810 | 910 | 1025 | 1270 | ||||
Power loss, max. 1) | kW | 1.0 | 0.97 | 1.05 | 0.95 | ||||
Load connection |
| Flat connector for M12 screw | Flat connector for M12 screw | Flat connector for M12 screw | Flat connector for M12 screw | ||||
PE connection |
| M8 screw | M8 screw | M8 screw | M8 screw | ||||
Cable length, max. between the motor reactor and motor | |||||||||
(number of reactors in series) |
| (1) | (2) | (1) | (2) | (1) | (2) | (1) | (2) |
| m | 300 | 525 | 300 | 525 | 300 | 525 | 300 | 525 |
| m | 450 | 787 | 450 | 787 | 450 | 787 | 450 | 787 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 | ||||
Dimensions | |||||||||
| mm | 410 | 410 | 410 | 460 | ||||
| mm | 392 | 392 | 392 | 392 | ||||
| mm | 279 | 279 | 317 | 296 | ||||
Weight, approx. | kg | 146 | 150 | 163 | 153 | ||||
Conformity | CE | CE | CE | CE | |||||
Approvals, according to 2) |
| cURus | cURus | cURus | cURus | ||||
Suitable for Motor Module |
| 6SL3320-1TG38-1AA3 6SL3325-1TG38-1AA3 | 6SL3320-1TG38-8AA3 | 6SL3320-1TG41-0AA3 6SL3325-1TG41-0AA3 | 6SL3320-1TG41-3AA3 6SL3325-1TG41-3AA3 | ||||
| A | 810 | 910 | 1025 | 1270 | ||||
| kW | 800 | 900 | 1000 | 1200 |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
2) Only for line voltages 500 ... 600 V 3 AC.