Motor reactors Siemens

Обзор



Motor reactors reduce the voltage load on the motor windings by reducing the voltage gradients on the motor terminals generated when the converter is used. At the same time, the capacitive charge/discharge currents that place an additional load on the converter output when long motor cables are used are reduced. For group drives, output reactors should always be used. The maximum permissible output frequency when a motor reactor is used is150 Hz.

The motor reactor must be installed as close as possible to the Motor Module or Power Module. Up to 2 motor reactors can be connected in series.

Motor reactors are approved for use only in conjunction with Vector and V/f control modes.

For additional notes on the use of motor reactors, please refer to the SINAMICS Low Voltage Engineering Manual.

Технические данные



Line voltage 380 … 480 V 3 AC

Motor reactor (for pulse frequencies of 2 kHz to 4 kHz)

 

6SL3000-2BE32-1AA0

6SL3000-2BE32-6AA0

6SL3000-2BE33-2AA0

6SL3000-2BE33-8AA0

6SL3000-2BE35-0AA0

Rated current

A

210

260

310

380

490

Power loss, max. 1)

kW

0.486

0.5

0.47

0.5

0.5

Load connection

 

1 × hole for M10

1 × hole for M10

1 × hole for M10

1 × hole for M10

1 × hole for M12

PE connection

 

M8 screw

M8 screw

M8 screw

M8 screw

M8 screw

Cable length, max.

between the motor reactor and motor

           

(number of reactors in series)

 

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

  • Shielded

m

300

525

300

525

300

525

300

525

300

525

  • Unshielded

m

450

787

450

787

450

787

450

787

450

787

Degree of protection

 

IP00

IP00

IP00

IP00

IP00

Dimensions

      
  • Width

mm

300

300

300

300

300

  • Height

mm

285

315

285

285

365

  • Depth

mm

257

277

257

277

277

Weight, approx.

kg

66

66

66

73

100

Conformity

 

CE

CE

CE

CE

CE

Approvals, according to

 

cURus

cURus

cURus

cURus

cURus

Suitable for Power Module

 

6SL3310-1TE32-1AA3

6SL3315-1TE32-1AA3

6SL3310-1TE32-6AA3

6SL3315-1TE32-6AA3

6SL3310-1TE33-1AA3

6SL3315-1TE33-1AA3

6SL3310-1TE33-8AA3

6SL3310-1TE35-0AA3

6SL3315-1TE35-0AA3

Suitable for Motor Module

 

6SL3320-1TE32-1AA3

6SL3325-1TE32-1AA3

6SL3320-1TE32-6AA3

6SL3325-1TE32-6AA3

6SL3320-1TE33-1AA3

6SL3325-1TE33-1AA3

6SL3320-1TE33-8AA3

6SL3320-1TE35-0AA3

6SL3325-1TE35-0AA3

  • Rated current of the Motor Module or Power Module

A

210

260

310

380

490

  • Type rating of the Motor Module or Power Module

kW

110

132

160

200

250



1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.

Line voltage 380 … 480 V 3 AC

Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

 

6SL3000-2AE36-1AA0

6SL3000-2AE38-4AA0

6SL3000-2AE41-0AA0

6SL3000-2AE41-4AA0

Rated current

A

605

745

840

985

1260

1405

Power loss, max. 1)

kW

0.9

0.84

0.943

1.062

0.9

1.054

Load connection

 

1 × hole for M12

1 × hole for M12

1 × hole for M12

1 × hole for M12

2 × hole for M12

2 × hole for M12

PE connection

 

M10 screw

M10 screw

M10 screw

M10 screw

M10 screw

M10 screw

Cable length, max.

between the motor reactor and motor

             

(number of reactors in series)

 

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

  • Shielded

m

300

525

300

525

300

525

300

525

300

525

300

525

  • Unshielded

m

450

787

450

787

450

787

450

787

450

787

450

787

Degree of protection

 

IP00

IP00

IP00

IP00

IP00

IP00

Dimensions

       
  • Width

mm

410

410

410

410

460

460

  • Height

mm

392

392

392

392

392

392

  • Depth

mm

292

292

292

302

326

326

Weight, approx.

kg

130

140

140

146

179

179

Conformity

 

CE

CE

CE

CE

CE

CE

Approvals, according to

 

cURus

cURus

cURus

cURus

cURus

cURus

Suitable for Motor Module

 

6SL3320-1TE36-1AA3

6SL3325-1TE36-1AA3

6SL3320-1TE37-5AA3

6SL3320-1TE38-4AA3

6SL3325-1TE38-4AA3

6SL3320-1TE41-0AA3

6SL3325-1TE41-0AA3

6SL3320-1TE41-2AA3

6SL3320-1TE41-4AA3

6SL3325-1TE41-4AA3

  • Rated current of the Motor Module

A

605

745

840

985

1260

1405

  • Type rating of the Motor Module

kW

315

400

450

560

710

800



1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.

Line voltage 500 … 690 V 3 AC

Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

 

6SL3000-2AH31-0AA0

6SL3000-2AH31-5AA0

6SL3000-2AH31-8AA0

6SL3000-2AH32-4AA0

Rated current

A

85

100

120

150

175

215

Power loss, max. 1)

kW

0.257

0.3

0.318

0.335

0.4

0.425

Load connection

 

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

PE connection

 

M6 screw

M6 screw

M6 screw

M6 screw

M6 screw

M6 screw

Cable length, max.

between the motor reactor and motor

             

(number of reactors in series)

 

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

  • Shielded

m

300

525

300

525

300

525

300

525

300

525

300

525

  • Unshielded

m

450

787

450

787

450

787

450

787

450

787

450

787

Degree of protection

 

IP00

IP00

IP00

IP00

IP00

IP00

Dimensions

       
  • Width

mm

270

270

270

270

300

300

  • Height

mm

248

248

248

248

285

285

  • Depth

mm

200

200

200

200

212

212

Weight, approx.

kg

25

25

25,8

25,8

34

34

Conformity

 

CE

CE

CE

CE

CE

CE

Approvals, according to 2)

 

cURus

cURus

cURus

cURus

cURus

cURus

Suitable for Motor Module

 

6SL3320-1TG28-5AA3

6SL3320-1TG31-0AA3

6SL3325-1TG31-0AA3

6SL3320-1TG31-2AA3

6SL3320-1TG31-5AA3

6SL3325-1TG31-5AA3

6SL3320-1TG31-8AA3

6SL3320-1TG32-2AA3

6SL3325-1TG32-2AA3

  • Rated current of the Motor Module

A

85

100

120

150

175

215

  • Type rating of the Motor Module

kW

75

90

110

132

160

200



1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.

2) Only for line voltages 500 ... 600 V 3 AC.

Line voltage 500 … 690 V 3 AC

Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

 

6SL3000-2AH32-6AA0

6SL3000-2AH33-6AA0

6SL3000-2AH34-5AA0

6SL3000-2AH34-7AA0

6SL3000-2AH35-8AA0

6SL3000-2AH38-1AA0

Rated current

A

260

330

410

465

575

735

Power loss, max. 1)

kW

0.44

0.45

0.545

0.72

0.8

0.96

Load connection

 

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

PE connection

 

M6 screw

M6 screw

M8 screw

M8 screw

M8 screw

M8 screw

Cable length, max.

between the motor reactor and motor

             

(number of reactors in series)

 

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

  • Shielded

m

300

525

300

525

300

525

300

525

300

525

300

525

  • Unshielded

m

450

787

450

787

450

787

450

787

450

787

450

787

Degree of protection

 

IP00

IP00

IP00

IP00

IP00

IP00

Dimensions

       
  • Width

mm

300

300

350

410

410

410

  • Height

mm

285

285

330

392

392

392

  • Depth

mm

212

212

215

292

292

279

Weight, approx.

kg

40

46

68

80

80

146

Conformity

 

CE

CE

CE

CE

CE

CE

Approvals, according to 2)

 

cURus

cURus

cURus

cURus

cURus

cURus

Suitable for Motor Module

 

6SL3320-1TG32-6AA3

6SL3320-1TG33-3AA3

6SL3325-1TG33-3AA3

6SL3320-1TG34-1AA3

6SL3320-1TG34-7AA3

6SL3320-1TG35-8AA3

6SL3325-1TG35-8AA3

6SL3320-1TG37-4AA3

  • Rated current of the Motor Module

A

260

330

410

465

575

735

  • Type rating of the Motor Module

kW

250

315

400

450

560

710



1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.

2) Only for line voltages 500 ... 600 V 3 AC.

Line voltage 500 … 690 V 3 AC

Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

 

6SL3000-2AH38-1AA0

6SL3000-2AH41-0AA0

6SL3000-2AH41-3AA0

Rated current

A

810

910

1025

1270

Power loss, max. 1)

kW

1.0

0.97

1.05

0.95

Load connection

 

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

PE connection

 

M8 screw

M8 screw

M8 screw

M8 screw

Cable length, max.

between the motor reactor and motor

         

(number of reactors in series)

 

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

  • Shielded

m

300

525

300

525

300

525

300

525

  • Unshielded

m

450

787

450

787

450

787

450

787

Degree of protection

 

IP00

IP00

IP00

IP00

Dimensions

     
  • Width

mm

410

410

410

460

  • Height

mm

392

392

392

392

  • Depth

mm

279

279

317

296

Weight, approx.

kg

146

150

163

153

Conformity

 

CE

CE

CE

CE

Approvals, according to 2)

 

cURus

cURus

cURus

cURus

Suitable for Motor Module

 

6SL3320-1TG38-1AA3

6SL3325-1TG38-1AA3

6SL3320-1TG38-8AA3

6SL3320-1TG41-0AA3

6SL3325-1TG41-0AA3

6SL3320-1TG41-3AA3

6SL3325-1TG41-3AA3

  • Rated current of the Motor Module

A

810

910

1025

1270

  • Type rating of the Motor Module

kW

800

900

1000

1200



1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.

2) Only for line voltages 500 ... 600 V 3 AC.