dv/dt filters plus VPL (Voltage Peak Limiter) limits the voltage rate-of-rise to values < 500 V/μs, and the typical voltage peaks to the following values according to the limit value curve to IEC/TS 60034-17: 2006:
< 1000 V at Uline < 575 V
< 1250 V at 660 V < Uline < 690 V
Standard motors with standard insulation and without insulated bearings with a supply voltage of up to 690 V can be used for converter operation if a dv/dt filter plus VPL is used.
dv/dt filters plus VPL are designed for the following maximum motor cable lengths:
- Shielded cables: 300 m (e.g. Protodur NYCWY)
- Unshielded cables: 450 m (e.g.Protodur NYY)
For shorter cable lengths (100 m shielded, 150 m unshielded) also refer to dv/dt filter compact plus VPL.
Notice: The maximum permissible cable length between the dv/dt filter plus VPL and the Power Module/Motor Module is 5 m.
Дизайн
The dv/dt filter plus VPL consists of two components, which are also separately supplied as mechanical units:
- dv/dt reactor
- Voltage limiting network, which cuts-off the voltage peaks and feeds the energy back into the DC link.
Технические данные
Line voltage 380 … 480 V 3 AC | dv/dt filter plus VPL | ||||
---|---|---|---|---|---|
|
| 6SL3000-2DE32-6AA0 | 6SL3000-2DE35-0AA0 | 6SL3000-2DE38-4AA0 | 6SL3000-2DE41-4AA0 |
Ith max | A | 260 | 490 | 840 | 1405 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 |
Cable length, max. between dv/dt filter and motor 1) | |||||
| m | 300 | 300 | 300 | 300 |
| m | 450 | 450 | 450 | 450 |
Conformity |
| CE | CE | CE | CE |
Approvals, according to |
| cURus | cURus | cURus | cURus |
dv/dt reactor | |||||
Power loss | |||||
| kW | 0.701 | 0.874 | 1.106 | 1.111 |
| kW | 0.729 | 0.904 | 1.115 | 1.154 |
| kW | 0.78 | 0.963 | 1.226 | 1.23 |
Connections | |||||
|
| 1 × hole M10 | 1 × hole M12 | 1 × hole M12 | 2 × hole M12 |
|
| 1 × hole M10 | 1 × hole M12 | 1 × hole M12 | 2 × hole M12 |
|
| M6 screw | M6 screw | M6 screw | M6 screw |
Dimensions | |||||
| mm | 410 | 460 | 460 | 445 |
| mm | 370 | 370 | 385 | 385 |
| mm | 229 | 275 | 312 | 312 |
Weight, approx. | kg | 66 | 122 | 149 | 158 |
Voltage Peak Limiter (VPL) | |||||
Power loss, max. | |||||
| kW | 0.029 | 0.042 | 0.077 | 0.134 |
| kW | 0.027 | 0.039 | 0.072 | 0.125 |
| kW | 0.025 | 0.036 | 0.066 | 0.114 |
Connections | |||||
|
| M8 nut | 70 mm2 terminals | 1 × hole M8 | 1 × hole M10 |
|
| M8 nut | 70 mm2 terminals | 1 × hole M8 | 1 × hole M10 |
|
| M8 stud | 35 mm2 terminals | M8 stud | M8 stud |
Dimensions | |||||
| mm | 263 | 392 | 309 | 309 |
| mm | 265 | 285 | 1313 | 1313 |
| mm | 188 | 210 | 400 | 400 |
Weight, approx. | kg | 6 | 16 | 48 | 72 |
Suitable for Power Module (type rating) |
| 6SL3310-1TE32-1AA3 (110 kW) 6SL3315-1TE32-1AA3 (110 kW) 6SL3310-1TE32-6AA3 (132 kW) 6SL3315-1TE32-6AA3 (132 kW) | 6SL3310-1TE33-1AA3 (160 kW) 6SL3315-1TE33-1AA3 (160 kW) 6SL3310-1TE33-8AA3 (200 kW) 6SL3310-1TE35-0AA3 (250 kW) 6SL3315-1TE35-0AA3 (250 kW) | ||
Suitable for Motor Module (type rating) |
| 6SL3320-1TE32-1AA3 (110 kW) 6SL3325-1TE32-1AA3 (110 kW) 6SL3320-1TE32-6AA3 (132 kW) 6SL3325-1TE32-6AA3 (132 kW) | 6SL3320-1TE33-1AA3 (160 kW) 6SL3325-1TE33-1AA3 (160 kW) 6SL3320-1TE33-8AA3 (200 kW) 6SL3320-1TE35-0AA3 (250 kW) 6SL3325-1TE35-0AA3 (250 kW) | 6SL3320-1TE36-1AA3 (605 kW) 6SL3325-1TE36-1AA0 (605 kW) 6SL3320-1TE37-5AA0 (745 kW) 6SL3320-1TE38-4AA0 (840 kW) 6SL3325-1TE38-4AA0 (840 kW) | 6SL3320-1TE41-0AA3 (985 kW) 6SL3325-1TE41-0AA3 (985 kW) 6SL3320-1TE41-2AA3 (1260 kW) 6SL3320-1TE41-2AA3 (1405 kW) 6SL3325-1TE41-2AA3 (1405 kW) |
1) Longer cable lengths for specific configurations are available on request.
Note: For power ratings 560 kW (380 … 480 V) or 710 kW (500 … 690 V) and higher, a filter includes two dv/dt reactors.
The listed technical data refer to one dv/dt reactor.
For additional information on dv/dt filters, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 ... 690 V 3 AC | dv/dt filter plus VPL | |||||
---|---|---|---|---|---|---|
|
| 6SL3000-2DH31-0AA0 | 6SL3000-2DH31-5AA0 | 6SL3000-2DH32-2AA0 | 6SL3000-2DH33-3AA0 | |
Ith max | A | 100 | 150 | 215 | 330 | |
Degree of protection | IP00 | IP00 | IP00 | IP00 | ||
Cable length, max. between dv/dt filter and motor 1) | ||||||
| m | 300 | 300 | 300 | 300 | |
| m | 450 | 450 | 450 | 450 | |
Conformity | CE | CE | CE | CE | ||
Approvals, according to 2) | cURus | cURus | cURus | cURus | ||
dv/dt reactor | ||||||
Power loss, max. | ||||||
| kW | 0.49 | 0.389 | 0.578 | 0.595 | |
| kW | 0.508 | 0.408 | 0.604 | 0.62 | |
| kW | 0.541 | 0.436 | 0.645 | 0.661 | |
Connections | ||||||
|
| 1 × hole M10 | 1 × hole M10 | 1 × hole M10 | 1 × hole M10 | |
|
| 1 × hole M10 | 1 × hole M10 | 1 × hole M10 | 1 × hole M10 | |
|
| M6 screw | M6 screw | M6 screw | M6 screw | |
Dimensions | ||||||
| mm | 350 | 350 | 460 | 460 | |
| mm | 320 | 320 | 360 | 360 | |
| mm | 227 | 227 | 275 | 275 | |
Weight, approx. | kg | 48 | 50 | 83 | 135 | |
Voltage Peak Limiter (VPL) | ||||||
Power loss, max. | ||||||
| kW | 0.016 | 0.02 | 0.032 | 0.042 | |
| kW | 0.015 | 0.019 | 0.03 | 0.039 | |
| kW | 0.013 | 0.018 | 0.027 | 0.036 | |
Connections | ||||||
|
| M8 nut | M8 nut | 70 mm2 terminals | 70 mm2 terminals | |
|
| M8 nut | M8 nut | 70 mm2 terminals | 70 mm2 terminals | |
|
| M8 stud | M8 stud | 35 mm2 terminals | 35 mm2 terminals | |
Dimensions | ||||||
| mm | 263 | 263 | 392 | 392 | |
| mm | 265 | 265 | 285 | 285 | |
| mm | 188 | 188 | 210 | 210 | |
Weight, approx. | kg | 6 | 6 | 16 | 16 | |
Suitable for Motor Module (type rating) |
| 6SL3320-1TG28-5AA3 (75 kW) 6SL3320-1TG31-0AA3 (90 kW) 6SL3325-1TG31-0AA3 (90 kW) | 6SL3320-1TG31-2AA3 (110 kW) 6SL3320-1TG31-5AA3 (132 kW) 6SL3325-1TG31-5AA3 (132 kW) | 6SL3320-1TG31-8AA3 (160 kW) 6SL3320-1TG32-2AA3 (200 kW) 6SL3325-1TG32-2AA3 (200 kW) | 6SL3320-1TG32-6AA3 (250 kW) 6SL3320-1TG33-3AA3 (315 kW) 6SL3325-1TG33-3AA3 (315 kW) |
1) Longer cable lengths for specific configurations are available on request.
2) Only for line voltages 500 ... 600 V 3 AC.
Note: For power ratings 560 kW (380 … 480 V) or 710 kW (500 … 690 V) and higher, a filter includes two dv/dt reactors.
The listed technical data refer to one dv/dt reactor.
For additional information on dv/dt filters, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 ... 690 V 3 AC | dv/dt filter plus VPL | ||||
---|---|---|---|---|---|
|
| 6SL3000-2DH34-1AA0 | 6SL3000-2DH35-8AA0 | 6SL3000-2DH38-1AA0 | 6SL3000-2DH41-4AA0 |
Ith max | A | 410 | 575 | 810 | 1270 |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 |
Cable length, max. between dv/dt filter and motor 1) | |||||
| m | 300 | 300 | 300 | 300 |
| m | 450 | 450 | 450 | 450 |
Conformity |
| CE | CE | CE | CE |
Approvals, according to 2) |
| cURus | cURus | cURus | cURus |
dv/dt reactor | |||||
Power loss, max. | |||||
| kW | 0.786 | 0.862 | 0.828 | 0.865 |
| kW | 0.826 | 0.902 | 0.867 | 0.904 |
| kW | 0.884 | 0.964 | 0.927 | 0.966 |
Connections | |||||
|
| 1 × hole M12 | 1 × hole M12 | 2 × hole M12 | 2 × hole M12 |
|
| 1 × hole M12 | 1 × hole M12 | 2 × hole M12 | 2 × hole M12 |
|
| M6 screw | M6 screw | M6 screw | M6 screw |
Dimensions | |||||
| mm | 460 | 460 | 445 | 445 |
| mm | 385 | 385 | 385 | 385 |
| mm | 312 | 312 | 312 | 312 |
Weight, approx. | kg | 147 | 172 | 160 | 164 |
Voltage Peak Limiter (VPL) | |||||
Power loss, max. | |||||
| kW | 0.051 | 0.063 | 0.106 | 0.15 |
| kW | 0.048 | 0.059 | 0.1 | 0.14 |
| kW | 0.043 | 0.054 | 0.091 | 0.128 |
Connections | |||||
|
| 1 × hole M8 | 1 × hole M8 | 1 × hole M10 | 1 × hole M10 |
|
| 1 × hole M8 | 1 × hole M8 | 1 × hole M10 | 1 × hole M10 |
|
| M8 stud | M8 stud | M8 stud | M8 stud |
Dimensions | |||||
| mm | 309 | 309 | 309 | 309 |
| mm | 1313 | 1313 | 1313 | 1313 |
| mm | 400 | 400 | 400 | 400 |
Weight, approx. | kg | 48 | 48 | 72 | 73 |
Suitable for Motor Module (type rating) |
| 6SL3320-1TG34-1AA3 (400 kW) | 6SL3320-1TG34-7AA3 (450 kW) 6SL3320-1TG35-8AA3 (560 kW) 6SL3325-1TG35-8AA3 (560 kW) | 6SL3320-1TG37-4AA3 (710 kW) 6SL3320-1TG38-1AA3 (800 kW) 6SL3325-1TG38-1AA3 (800 kW) | 6SL3320-1TG38-8AA3 (900 kW) 6SL3320-1TG41-0AA3 (1000 kW) 6SL3325-1TG41-0AA3 (1000 kW) 6SL3320-1TG41-3AA3 (1200 kW) 6SL3325-1TG41-3AA3 (1200 kW) |
1) Longer cable lengths for specific configurations are available on request.
2) Only for line voltages 500 ... 600 V 3 AC.
Note: For power ratings 560 kW (380 … 480 V) or 710 kW (500 … 690 V) and higher, a filter includes two dv/dt reactors.
The listed technical data refer to one dv/dt reactor.
For additional information on dv/dt filters, please refer to the SINAMICS Low Voltage Engineering Manual.