dv/dt filters compact plus VPL Siemens

Обзор



dv/dt filters compact plus VPL (Voltage Peak Limiter) limits the voltage rate-of-rise dv/dt to values < 1600 V/μs, and the typical voltage peaks to the following values according to the limit value curve A according to IEC 60034‑25: 2007:

< 1150 V at Uline < 575 V

< 1400 V at 660 V < Uline < 690 V

Standard motors with standard insulation and without insulated bearings with a supply voltage of up to 690 V can be used for converter operation if a dv/dt filter compact plus VPL is used.

dv/dt filters compact plus VPL are designed for the following maximum motor cable lengths:

  • Shielded cables: 100 m (e.g. Protodur NYCWY)
  • Unshielded cables: 150 m (e.g. Protodur NYY)

For longer cable lengths (> 100 m shielded, > 150 m unshielded) refer to dv/dt filter plus VPL.

Notice:

  • The max. permissible cable length between the dv/dt filter and Motor Module is 5 m
  • Operation with output frequencies < 10 Hz is permissible for max. 5 min

Дизайн



The dv/dt filter compact plus VPL consists of two components, which are supplied together as a compact mechanical unit:

  • dv/dt reactor
  • Voltage limiting network, which cuts-off the voltage peaks and feeds the energy back into the DC link.

Технические данные



Line voltage 380 … 480 V 3 AC

dv/dt filter compact plus VPL

 

 

6SL3000-2DE32-6EA0

6SL3000-2DE35-0EA0

6SL3000-2DE38-4EA0

6SL3000-2DE41-1EA0

Rated current

A

260

490

840

1405

Ith max

A

260

490

840

1405

Power loss, max.

     
  • At 50 Hz 400 V

kW

0.21

0.29

0.518

Reactor: 1.027
VPL: 0.127
Total: 1.154

  • At 60 Hz 460 V

kW

0.215

0.296

0.529

Reactor: 1.077
VPL: 0.12
Total: 1.197

  • At 150 Hz 400 V

kW

0.255

0.344

0.609

Reactor: 1.354
VPL: 0.09
Total: 1.444

Power connection

input and output sides

 

Hole for M10

Hole for M10

Hole for M12

2 × elongated hole, 14 × 18 mm

  • Conductor cross-section, max. (IEC)

 

Provided for busbar connection

Provided for busbar connection

Provided for busbar connection

Provided for busbar connection

DC link connection

DCPS, DCNS

 

Threaded socket M8

Threaded socket M8

Hole for M8

Hole for M8

  • Conductor cross-section, max. (IEC)

mm2

16

16

25

25

PE/GND connection

 

Threaded socket M8

Threaded socket M6

Threaded socket M6

Threaded socket M6
(reactor and VPL)

Motor cable length, max.

     
  • Shielded

m

100

100

100

100

  • Unshielded

m

150

150

150

150

Degree of protection

 

IP00

IP00

IP00

IP00

Dimensions

     
  • Width

mm

310

350

440

Reactor: 430
VPL: 277

  • Height

mm

283

317

369

Reactor: 385
VPL: 360

  • Depth

mm

238

260

311

Reactor: 323
VPL: 291

Weight, approx.

kg

41

61

103

Reactor: 168.8
VPL: 19.2
Total: 188

Conformity

 

CE

CE

CE

CE

Approvals, according to

 

cURus

cURus

cURus

cURus

Suitable for Motor Module

(type rating)

 

6SL332 . -1TE32-1AA3 (110 kW)

6SL332 . -1TE32-6AA3 (132 kW)

6SL332 . -1TE33-1AA3 (160 kW)

6SL3320-1TE33-8AA3 (200 kW)

6SL332 . -1TE35-0AA3 (250 kW)

6SL332 . -1TE36-1AA3 (315 kW)

6SL3320-1TE37-5AA3 (400 kW)

6SL332 . -1TE38-4AA3 (450 kW)

6SL332 . -1TE41-0AA3 (560 kW)

6SL3320-1TE41-2AA3 (710 kW)

6SL332 . -1TE41-4AA3 (800 kW)



Line voltage 500 ... 690 V 3 AC

dv/dt filter compact plus VPL

 

 

6SL3000-2DG31-0EA0

6SL3000-2DG31-5EA0

6SL3000-2DG32-2EA0

6SL3000-2DG33-3EA0

Rated current

A

100

150

215

330

Ith max

A

100

150

215

330

Power loss, max.

     
  • At 50 Hz 500/690 V

kW

0.227

0.27

0.305

0.385

  • At 60 Hz 575 V

kW

0.236

0.279

0.316

0.399

  • At 150 Hz 500/690 V

kW

0.287

0.335

0.372

0.48

Power connection

input and output sides

 

Hole for M10

Hole for M10

Hole for M10

Hole for M10

  • Conductor cross-section, max. (IEC)

 

Provided for busbar connection

Provided for busbar connection

Provided for busbar connection

Provided for busbar connection

DC link connection

DCPS, DCNS

 

Threaded socket M8

Threaded socket M8

Hole for M8

Hole for M8

  • Conductor cross-section, max. (IEC)

mm2

16

16

25

25

PE/GND connection

 

Threaded socket M6

Threaded socket M6

Threaded socket M6

Threaded socket M6

Motor cable length, max.

     
  • Shielded

m

100

100

100

100

  • Unshielded

m

150

150

150

150

Degree of protection

 

IP00

IP00

IP00

IP00

Dimensions

     
  • Width

mm

310

310

350

350

  • Height

mm

283

283

317

317

  • Depth

mm

238

238

260

260

Weight, approx.

kg

34

36

51

60

Conformity

 

CE

CE

CE

CE

Approvals, according to

 

cURus

cURus

cURus

cURus

Suitable for Motor Module

(type rating)

 

6SL3320-1TG28-5AA3 (75 kW)

6SL332 . -1TG31-0AA3 (90 kW)

6SL3320-1TG31-2AA3 (110 kW)

6SL332 . -1TG31-5AA3 (132 kW)

6SL3320-1TG31-8AA3 (160 kW)

6SL332 . -1TG32-2AA3 (200 kW)

6SL3320-1TG32-6AA3 (250 kW)

6SL332 . -1TG33-3AA3 (315 kW)



1) Only for line voltages 500 ... 600 V 3 AC.

Line voltage 500 ... 690 V 3 AC

dv/dt filter compact plus VPL

 

 

6SL3000-2DG34-1EA0

6SL3000-2DG35-8EA0

6SL3000-2DG38-1EA0

6SL3000-2DG41-3EA0

Rated current

A

410

575

810

1270

Ith max

A

410

575

810

1270

Power loss, max.

     
  • At 50 Hz 500/690 V

kW

0.55

0.571

Reactor: 0.88
VPL: 0.084
Total: 0.964

Reactor: 0.926
VPL: 0.124
Total: 1.050

  • At 60 Hz 575 V

kW

0.568

0.586

Reactor: 0.918
VPL: 0.08
Total: 0.998

Reactor: 0.993
VPL: 0.111
Total: 1.104

  • At 150 Hz 500/690 V

kW

0.678

0.689

Reactor: 1.137
VPL: 0.059
Total: 1.196

Reactor: 1.23
VPL: 0.089
Total: 1.319

Power connection

input and output sides

 

Hole for M12

Hole for M12

2 × elongated hole, 14 × 18 mm

2 × elongated hole, 14 × 18 mm

  • Conductor cross-section, max. (IEC)

 

Provided for busbar connection

Provided for busbar connection

Provided for busbar connection

Provided for busbar connection

DC link connection

DCPS, DCNS

 

Hole for M8

Hole for M8

Hole for M8

Hole for M8

  • Conductor cross-section, max. (IEC)

mm2

50

50

95

95

PE/GND connection

 

Threaded socket M6

Threaded socket M6

Threaded socket M6
(reactor and VPL)

Threaded socket M6
(reactor and VPL)

Motor cable length, max.

     
  • Shielded

m

100

100

100

100

  • Unshielded

m

150

150

150

150

Degree of protection

 

IP00

IP00

IP00

IP00

Dimensions

     
  • Width

mm

440

440

Reactor: 430
VPL: 277

Reactor: 430
VPL: 277

  • Height

mm

369

369

Reactor: 385
VPL: 360

Reactor: 385
VPL: 360

  • Depth

mm

311

311

Reactor: 323
VPL: 291

Reactor: 323
VPL: 291

Weight, approx.

kg

87

100

Reactor: 171.2
VPL: 18.8
Total: 190

Reactor: 175.8
VPL: 19.2
Total: 195

Conformity

 

CE

CE

CE

CE

Approvals, according to

 

cURus

cURus

cURus

cURus

Suitable for Motor Module

(type rating)

 

6SL3320-1TG34-1AA3 (400 kW)

6SL3320-1TG34-7AA3 (450 kW)

6SL332 . -1TG35-8AA3 (560 kW)

6SL3320-1TG37-4AA3 (710 kW)

6SL332 . -1TG38-1AA3 (800 kW)

6SL3320-1TG38-8AA3 (900 kW)

6SL332 . -1TG41-0AA3 (1000 kW)

6SL332 . -1TG41-3AA3 (1200 kW)



1) Only for line voltages 500 ... 600 V 3 AC.