Transmitter for rel. pressure, abs. pressure, diff. pressure, flow and level Siemens

Обзор



Transmitters for pressure, absolute pressure, differential pressure, flow and level, from 1mbar to 400 bar

Different requirements need different transmitters.

With different connection options and different housings - with or without a display.

Whether operation is conventional, smart or operated through PROFIBUS PA or Foundation Fieldbus - SITRANS P offers extensive user-friendliness and outstanding performance.

    Z series:
    • Single-range transmitters, only for pressure and absolute pressure
    • Standard ranges
    • Stainless steel version with DIN plug
    P250 series:
    • Single-range transmitters for differential pressure
    • Analog electronics
    • Available ex stock
    P Compact series:
    • Single-range transmitters
    • Standard ranges
    • Hygienic design
    • Range of different aseptic connections available
    P280 series:
    • Wireless communication with WirelessHART
    • Battery power supply
    • Parameterization with SIMATIC PDM via WirelessHART or local with HART modem and using local push buttons
    P300 series:
    • Smart and conventional operation
    • Hygienic design
    • Range of different aseptic connections available
    • With ATEX, FM and CSA approval
    P300 series (PROFIBUS):
    • Operation through PROFIBUS-PA
    • Hygienic design
    • Range of different aseptic connections available
    • With ATEX, FM and CSA approval
    P300 series (Foundation Fieldbus):
    • Operation over Fieldbus Foundation
    • Hygienic design
    • Range of different aseptic connections available
    • With ATEX, FM and CSA approval
    DS III series:
    • Smart and conventional operation
    • Preferably for horizontal differential pressure lines
    • Intrinsically safe in zone 1 or 2n or flameproof enclosure
    • With ATEX, FM and CSA approval
    DS III PA (PROFIBUS) series:
    • Operation through PROFIBUS-PA
    • Preferably for horizontal differential pressure lines
    • Intrinsically safe in zone 1 or flameproof enclosure
    • With ATEX, FM and CSA approval
    DS III FF series (Foundation Fieldbus):
    • Operation over Fieldbus Foundation
    • Preferably for horizontal differential pressure lines
    • Intrinsically safe in zone 1 or flameproof enclosure
    • ATEX approval
    MPS series (submersible sensor):
    • Transmitters for hydrostatic level measurements

Интеграция



Measuring setups with remote seals

The following pages show examples of typical measuring setups for using SITRANS P pressure transmitters with and without remote seals.

Installation

Remote seals of sandwich design are fitted between the connection flange of the measuring point and a dummy flange.

Remote seals of flange design are fitted directly on the connection flange of the measuring point.

The respective pressure rating of the dummy flange or the flanged remote seal must be observed.

The pressure transmitter should always be installed below the connection flange (and always below the lower connection flange in the case of differential pressure transmitters). When measuring at pressures above atmospheric, the pressure transmitter can also be installed above the connection flange. When measuring at pressures below atmospheric, the transmitter must always be installed below the connection flange (and always below the lower connection flange in the case of differential pressure transmitters).

Offset of measuring range

If there is a difference in height between the two connection flanges when measuring with two remote seals, an additional differential pressure will result from the oil filling of the remote seal capillaries. This results in a measuring range offset which has to be taken into account when you set the pressure transmitter.

An offset of the measuring range also arises when pressure transmitters and remote seals are not installed at the same height

Pressure transmitter output

If the level, separation layer or density increase in closed vessels, the differential pressure and hence the output signal of the pressure transmitter also increase.

If the output signal is to fall as the differential pressure rises, you must swap the start of scale with the end of scale.

With open vessels, a rising pressure is usually assigned to an increasing level, separation layer or density.

Influence of ambient temperature

The capillaries between the remote seal and the pressure transmitter should be kept as short as possible to obtain a good transmission response. Steps should also be taken to avoid temperature differences between the individual remote seals.

If the complete setup is exposed to temperature variations, temperature errors will result from the thermally induced change of volume of the filling liquid in the capillaries, in the remote seals and in the connection parts.

Notes

When measuring separation layers, ensure that:

  • The separation layer is positioned between the two spigots.
  • The level in the vessel is always above the top spigot.

Possible combinations of pressure transmitters and remote seals

Type of installation

Pressure transmitters

Remote seals

A / B

  • 7MF4010
  • 7MF4013
  • 7MF4033
  • 7MF4034
  • 7MF4035
  • 7MF8023
  • 7MF8024
  • 7MF4900
  • 7MF4910
  • 7MF4920

C1 / C2

  • 7MF4233
  • 7MF4234
  • 7MF4235
  • 7MF4900
  • 7MF4910
  • 7MF4920

(vacuum-proof design in each case)

  • 7MF4333
  • 7MF4334
  • 7MF4335
  • 7MF4901
  • 7MF4921

D

  • 7MF4433
  • 7MF4434
  • 7MF4435
  • 7MF4903
  • 7MF4923

E

  • 7MF4433
  • 7MF4434
  • 7MF4435
  • 7MF4913

G / H / J

  • 7MF4433
  • 7MF4434
  • 7MF4435
  • 7MF4903
  • 7MF4923


Types of installation for pressure and level measurements (open vessels)

 

Installation type A

 

Start-of-scale:

pMA = ρFL · g · HU - ρoil · g · H1

Full-scale:

pME = ρFL · g · HO - ρoil · g · H1

Installation type B

Start-of-scale:

pMA = ρFL · g · HU + ρoil · g · H1

Full-scale:

pME = ρFL · g · HO + ρoil · g · H1

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

ρFL

Density of medium in vessel

ρoil

Density of filling oil in the capillary to the remote seal

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level

H1

Distance between vessel flange and pressure transmitter



Types of installation for absolute level measurements (closed vessels)

 

Installation type C1 and C2

 

Start-of-scale:

pMA = pSTART + ρoil · g · H1

Full-scale:

pME = pEND + ρoil · g · H1

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

pSTART

Pressure at start-of-scale

pEND

Pressure at end-of-scale

ρoil

Density of filling oil in the capillary to the remote seal

g

Local acceleration due to gravity

H1

Distance between vessel flange and pressure transmitter



Types of installation for differential pressure and flow measurements

 

Installation type D

 

Start-of-scale:

pMA = pSTART - ρoil · g · HV

Full-scale:

pME = pEND - ρoil · g · HV

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

pSTART

Pressure at start-of-scale

pEND

Pressure at end-of-scale

ρoil

Density of filling oil in the capillary to the remote seal

g

Local acceleration due to gravity

HV

Distance between spigots



Types of installation for level measurements

 

Installation type E

 

Start-of-scale:

pMA = pFL · g · HU - ρoil · g · HV

Full-scale:

pME = pFL · g · HO - ρoil · g · HV

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

pFL

Density of medium in vessel

ρoil

Density of filling oil in the capillary to the remote seal

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level

HV

Distance between spigots



 

Installation types G, H and J

 

Start-of-scale:

pMA = pFL · g · HU - ρoil · g · HV

Full-scale:

pME = pFL · g · HO - ρoil · g · HV

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

pFL

Density of medium in vessel

ρoil

Density of filling oil in the capillary to the remote seal

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level

HV

Distance between spigots



Measuring setups without remote seals

The following types of installation are used to measure level, separation level and density in open and closed vessels without the application of remote seals.

Notes

When measuring separation layers, ensure that:

  • The separation layer is positioned between the two spigots.
  • The level in the vessel must always be above the top spigot.

When measuring density, ensure that:

At the end of this section is a questionnaire which you can use is used for hydrostatic level measurements, e.g. for measuring the level in steam boilers, steam drums, condensation vessels, etc.

Setup for pressure transmitters for differential pressure, flange mounting (open vessels)

Level measurement

 

Start-of-scale:

pMA = ρ · g · HU

Full-scale:

pME = ρ · g · HO

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

ρ

Density of medium in vessel

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level



Separation layer measurement

 

Start-of-scale:

pMA = g · (HU · ρ1 + (HO - HU) · ρ2)

Full-scale:

pME = ρ1 · g · HO

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

ρ1

Density of the heavier liquid

ρ2

Density of the lighter liquid

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level



Density measurement

 

Start-of-scale:

pMA = ρMIN · g · HO

Full-scale:

pME = ρMAX · g · HO

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

ρMIN

Minimum density of medium in vessel

ρMAX

Maximum density of medium in vessel

g

Local acceleration due to gravity

HO

Maximum level



Setup for pressure transmitters for differential pressure, flange mounting (closed vessels)

Level measurement, version 1

 

Start-of-scale:

ΔpMA = ρ · g · HU

Full-scale:

ΔpME = ρ · g · HO

Legend

ΔpMA

Pressure to be set at start-of-scale

ΔpME

Pressure to be set at end-of-scale

ρ

Density of medium in vessel

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level



Level measurement, version 2

 

Start-of-scale:

pMA = g · (HU · ρ - HV · ρ′)

Full-scale:

pME = g · (HO · ρ - HV · ρ′)

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

ρ

Density of medium in vessel

ρ′

Density of liquid in the negative pressure line, corresponding to the temperature existing there

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level

 

HV

Distance between spigots



Separation layer measurement

 

Start-of-scale:

ΔpMA = g · (HU · ρ1 + (HO-HU) · ρ2 - HV · ρ′2)

Full-scale:

ΔpMA = g · (HO · ρ1 - HV · ρ′2)

Legend

pMA

Pressure to be set at start-of-scale

pME

Pressure to be set at end-of-scale

ρ1

Density of heavier liquid with separation layer in vessel

ρ2

Density of lighter liquid with separation layer in vessel

ρ′2

Density of liquid in the negative pressure line for separation layer measurement, corresponding to the temperature existing there

g

Local acceleration due to gravity

HU

Minimum level

HO

Maximum level

HV

Distance between spigots