SITRANS P300 (gauge pressure and absolute pressure) Siemens
Область применения
The pressure transmitter is available in versions for gauge pressure and for absolute pressure. The output signal is always a load-independent direct current from 4 to 20 mA or a PROFIBUS PA signal, which is linearly proportional to the input pressure. The pressure transmitter measures aggressive, non-aggressive and hazardous gases, as well as vapors and liquids.
It can be used for the following measurement types:
- Gauge pressure
- Absolute pressure
With appropriate parameter settings, it can also be used for the following additional measurement types:
- Level
- Volume
- Mass
The "intrinsically-safe" EEx version of the transmitter can be installed in hazardous areas (zone 1). The transmitters are provided with an EC type examination certificate and comply with the respective harmonized European standards of ATEX.
Gauge pressure
This variant measures aggressive, non-aggressive and hazardous gases, vapors and liquids.
The smallest measuring span is 0.01 bar g, the largest 400 bar g (0.15 psi g, the largest 5802 psi g).
Level
With appropriate parameter settings, the gauge pressure variant measures the level of aggressive, non-aggressive and hazardous liquids.
For measuring the level in an open container you require one device; for measuring the level in a closed container, you require two devices and a process control system.
Absolute pressure
This variant measures the absolute pressure of aggressive, non-aggressive and hazardous gases, vapors and liquids.
The smallest measuring span is 0.008 bar a, the largest 30 bar a (0.12 psi a, the largest 435 psi a).
Обзор
The SITRANS P300 is a digital pressure transmitter for gage and absolute pressure. All conventional thread versions are available as process connections. In addition, various hygiene-based connections and flange connections with front-flush diaphragms meet the requirements of a dead space free process connection.
The output signal is a load-independent direct current from 4 t 20 mA or a PROFIBUS PA signal, which is linearly proportional to the input pressure. Communication is over HART protocol or over PROFIBUS PA interface. Convenient buttons for easy local operation of the basic settings of the pressure transmitter.
The SITRANS P300 has a single-chamber stainless steel casing. The pressure transmitter is approved with "intrinsically safe" type of protection It can be used in zone 1 or zone 0.
Дизайн
The device comprises:
- Electronics
- Housing
- Measuring cell
Perspective view of the SITRANS P300
The housing has a screw-on cover (3) and, depending on the version, is with or without an inspection window. The electrical terminal housing, the buttons for operation of the device are located under this cover and, depending on the version, the digital display. The connections for the auxiliary power UH and the shield are in the terminal housing. The cable gland is mounted on the side of the housing. The measuring cell with the process connection (5) is located on the bottom of the housing. The measuring cell with the process connection may differ from the one shown in the diagram, depending on the device version.
Measuring point label
Функции
Operation of electronics with HART communication
Function diagram of electronics
The input pressure is converted into an electrical signal by the sensor (1). This signal is amplified by the measuring amplifier (2) and digitalized in an analog-to-digital converter (3). The digital signal is analyzed in a microcontroller (4) and corrected according to linearity and thermal characteristics. In a digital-to-analog converter (5) it is then converted into the output current of 4 to 20 mA. A diode circuit provides reverse polarity protection. You can make an uninterrupted current measurement with a low-ohm ammeter at the connection (10). The data specific to the measuring cell, the electronic data and parameter settings are stored in two non-volatile memories (6). The first memory is linked to the measuring cell, the second to the electronics.
The buttons (8) can be used to call up individual functions, so-called modes. If you have a device with a digital display (9), you can use this to track mode settings and other messages. The basic mode settings can be changed with a computer via the HART modem (7).
Operation of electronics with PROFIBUS PA communication
Function diagram of electronics
The input pressure is converted into an electrical signal by the sensor (1). This signal is amplified by the measuring amplifier (2) and digitalized in an analog-to-digital converter (3). The digital signal is analyzed in a microcontroller (4) and corrected according to linearity and thermal characteristics. It is then made available at the PROFIBUS PA over an electrically isolated PROFIBUS PA interface (7). The data specific to the measuring cell, the electronic data and parameter settings are stored in two non-volatile memories (6). The first memory is linked to the measuring cell, the second to the electronics.
The buttons (8) can be used to call up individual functions, so-called modes. If you have a device with a digital display (9), you can use this to track mode settings and other messages. The basic mode settings can be changed with a computer over the bus master (12).
Operation of electronics with FOUNDATION fieldbus communication
Function diagram of electronics
The bridge output voltage created by the sensor (1, Figure "Function diagram of electronics") is amplified by the measuring amplifier (2) and digitized in the analog-to-digital converter (3). The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the FOUNDATION fieldbus through an electrically isolated FOUNDATION fieldbus interface (7).
The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other.
Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error messages and the operating modes on the digital display (9).
The results with status values and diagnostic values are transferred by cyclic data transmission on the FOUNDATION fieldbus. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as National Instruments Configurator is required for this.
Mode of operation of the measuring cells
The process connections available include the following:
- G½
- ½-14 NPT
- Flush-mounted diaphragm:
- Flanges to EN
- Flanges to ASME
- NuG and pharmaceutical connections
Measuring cell for gauge pressure
Measuring cell for gauge pressure, function diagram
The input pressure (pe) is transferred to the gauge pressure sensor (6) via the seal diaphragm (4) and the filling liquid (5), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure.
Transmitters with spans ≤ 63 bar (≤ 926.1 psi) measure the input pressure compared to atmospheric, those with spans ≥ 160 bar (≥ 2352 psi) compared to a vacuum.
Measuring cell for absolute pressure
Measuring cell for absolute pressure, function diagram
The input pressure (pe) is transferred to the absolute pressure sensor (5) via the seal diaphragm (3) and the filling liquid (4), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure.
Measuring cell for gauge pressure, flush-mounted diaphragm
Measuring cell for gauge pressure, flush-mounted diaphragm, function diagram
The input pressure (pe) is transferred to the gauge pressure sensor (6) via the seal diaphragm (4) and the filling liquid (5), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure.
Transmitters with spans ≤ 63 bar (≤ 926.1 psi) measure the input pressure compared to atmospheric, those with spans ≥ 160 bar (≥ 2352 psi) compared to a vacuum.
Measuring cell for absolute pressure, flush-mounted diaphragm
Measuring cell for absolute pressure, flush-mounted diaphragm, function diagram
The input pressure (pe) is transferred to the absolute pressure sensor (5) via the seal diaphragm (3) and the filling liquid (4), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure.
Parameterization of SITRANS P300
Depending on the version, there are a range of options for parameterizing the pressure transmitter and for setting or scanning the parameters.
Parameterization using the input buttons (local operation)
With the input buttons you can easily set the most important parameters without any additional equipment.
Parameterization using HART communication
Parameterization using HART communication is performed with a HART communicator or a PC.
Communication between a HART communicator and a pressure transmitter
When parameterizing with the HART communicator, the connection is made directly to the 2-wire cable.
HART communication between a PC communicator and a pressure transmitter
When parameterizing with a PC, the connection is made through a HART modem.
The signals needed for communication in conformity with the HART 5.x or 6.x protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method.
Adjustable parameters on SITRANS P300 with HART communication
Parameters | Input buttons | HART communication |
---|---|---|
Start of scale | x | x |
Full-scale value | x | x |
Electrical damping | x | x |
Start-of-scale value without application of a pressure ("Blind setting") | x | x |
Full-scale value without application of a pressure ("Blind setting") | x | x |
Zero adjustment | x | x |
current transmitter | x | x |
Fault current | x | x |
Disabling of buttons, write protection | x | x 1) |
Type of dimension and actual dimension | x | x |
Input of characteristic | x | |
Freely-programmable LCD | x | |
Diagnostic functions | x |
1) Cancel apart from write protection
Diagnostic functions for SITRANS P300 with HART communication
- Zero correction display
- Event counter
- Limit transmitter
- Saturation alarm
- Slave pointer
- Simulation functions
- Maintenance timer
Available physical units of display for SITRANS P300 with HART communication
Table style: Technical specifications 2
Physical variable | Physical dimensions |
Pressure (setting can also be made in the factory) | Pa, MPa, kPa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, inH2O, inH2O (4 °C), mmH2O, ftH2O (20 °C), inHg, mmHg |
Level (height data) | m, cm, mm, ft, in |
Volume | m3, dm3, hl, yd3, ft3, in3, US gallon, lmp. gallon, bushel, barrel, barrel liquid |
Mass | g, kg, t, lb, Ston, Lton, oz |
Temperature | K, °C, °F, °R |
Miscellaneous | %, mA |
Parameterization through PROFIBUS PA interface
Fully digital communication through PROFIBUS PA, profile 3.0, is particularly user-friendly. The P300 PA is connected to a process control system, e.g. SIMATIC PSC 7, over PROFIBUS. Communication is possible even in a potentially explosive environment.
For parameterization through PROFIBUS you need suitable software, e.g. SIMATIC PDM (Process Device Manager).
Parameterization through FOUNDATION fieldbus interface
Fully digital communication through FOUNDATION fieldbus is particularly user-friendly. Through the FOUNDATION fieldbus the P300 is connected to a process control system. Communication is possible even in a potentially explosive environment.
For parameterization through the FOUNDATION fieldbus you need suitable software, e.g. National Instruments Configurator.
Adjustable parameters for SITRANS P300 PA and FF
Adjustable parameters | Input buttons | PROFIBUS PA and FOUNDATION fieldbus interface |
---|---|---|
Electrical damping | x | x |
Zero adjustment (correction of position) | x | x |
Buttons and/or function disabling | x | x |
Source of measured-value display | x | x |
Physical dimension of display | x | x |
Position of decimal point | x | x |
Bus address | x | x |
Adjustment of characteristic | x | x |
Input of characteristic | x | |
Freely-programmable LCD | x | |
Diagnostic functions | x |
Diagnostic functions for SITRANS P300 PA and FF
- Event counter
- Slave pointer
- Maintenance timer
- Simulation functions
- Display of zero correction
- Limit transmitter
- Saturation alarm
Physical dimensions available for the display
Physical variable | Physical dimensions |
Pressure (setting can also be made in the factory) | MPa, kPa, Pa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, mmH2O, mmH2O (4 °C), inH2O, inH20 (4 °C), ftH2O (20 °C), mmHg, inHg |
Level (height data) | m, cm, mm, ft, in, yd |
Volume | m3, dm3, hl, yd3, ft3, in3, US gallon, lmp. gallon, bushel, barrel, barrel liquid |
volume flow | m3/s, m3/min, m3/h, m3/d, l/s, l/min, l/h, l/ d, Ml/d, ft3/s, ft3/min, ft3/h, ft3/d, US gallon/s, US gallon/min, US gallon/h, US gallon/d, bbl/s, bbl/min, bbl/h, bbl/d |
Mass flow | g/s, g/min, g/h, g/d, kg/s, kg/min, kg/h, kg/d, t/s, t/min, t/h, /t/d, lb/s, lb/min, lb/h, lb/d, STon/s, STon/min, STon/h, STon/d, LTon/s, LTon/min, LTon/h, LTon/d |
Total mass flow | t, kg, g, lb, oz, LTon, STon |
Temperature | K, °C, °F, °R |
Miscellaneous | % |
Hygiene version
In the case of the SITRANS P300 with 7MF812.-... flush-mounted diaphragm, selected connections comply with the requirements of the EHEDG or 3A. You will find further details in the order form. Please note in particular that the seal materials used must comply with the requirements of 3A. Similarly, the filling liquids used must be FDA-compliant.
Чертеж
SITRANS P300, with oval flange, dimensions in mm (inch)
SITRANS P300, process connection M20 x 1.5, with mounted mounting bracket, dimensions in mm (inch)
SITRANS P300, flush-mounted, dimensions in mm (inch)
The diagram shows a SITRANS P300 with an example of a flange. In this drawing the height is subdivided into H1 and H2.
H1 = Height of the SITRANS P300 up to a defined cross-section
H2 = Height of the flange up to this defined cross-section
Only the height H2 is indicated in the dimensions of the flanges.
Flanges as per EN and ASME
Flange to EN
EN 1092-1 | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
25 | 40 | 115 mm (4.5") | Approx. 52 mm (2") | |
25 | 100 | 140 mm (5.5") | ||
40 | 40 | 150 mm (5.9") | ||
40 | 100 | 170 mm (6.7") | ||
50 | 16 | 165 mm (6.5") | ||
50 | 40 | 165 mm (6.5") | ||
80 | 16 | 200 mm (7.9") | ||
80 | 40 | 200 mm (7.9") |
Flanges to ASME
ASME B16.5 | ||||
---|---|---|---|---|
DN | class | ∅D | H2 | |
1" | 150 | 110 mm (4.3") | Approx. 52 mm (2") | |
1" | 300 | 125 mm (4.9") | ||
1½" | 150 | 130 mm (5.1") | ||
1½" | 300 | 155 mm (6.1") | ||
2“ | 150 | 150 mm (5.9") | ||
2“ | 300 | 165 mm (6.5") | ||
3“ | 150 | 190 mm (7.5") | ||
3“ | 300 | 210 mm (8.1") | ||
4“ | 150 | 230 mm (9.1") | ||
4“ | 300 | 255 mm (10.0") |
NuG and pharmaceutical connections
Connections to DIN
DIN 11851 (milk pipe union) | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 25 | 92 mm (3.6") | Approx. 52 mm (2") | |
80 | 25 | 127 mm (5.0") |
TriClamp to DIN 32676 | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | 64 mm (2.5") | Approx. 52 mm (2") | |
65 | 16 | 91 mm (3.6") |
Other connections
Varivent connection | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
40 ... 125 | 40 | 84 mm (3.3") | Approx. 52 mm (2") |
Biocontrol connection | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | 90 mm (3.5") | Approx. 52 mm (2") | |
65 | 16 | 120 mm (4.7") |
Sanitary process connection to DRD | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 40 | 105 mm (4.1") | Approx. 52 mm (2") | |
Sanitary process screw connection to NEUMO Bio-Connect | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | 82 mm (3.2") | Approx. 52 mm (2") | |
65 | 16 | 105 mm (4.1") | ||
80 | 16 | 115 mm (4.5") | ||
100 | 16 | 145 mm (5.7") | ||
2” | 16 | 82 mm (3.2") | ||
2½” | 16 | 105 mm (4.1") | ||
3” | 16 | 105 mm (4.1") | ||
4” | 16 | 145 mm (5.7") |
Sanitary process connection to NEUMO Bio-Connect flange connection | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | 110 mm (4.3") | Approx. 52 mm (2") | |
65 | 16 | 140 mm (5.5") | ||
80 | 16 | 150 mm (5.9") | ||
100 | 16 | 175 mm (6.9") | ||
2” | 16 | 100 mm (3.9") | ||
2½” | 16 | 110 mm (4.3") | ||
3” | 16 | 140 mm (5.5") | ||
4” | 16 | 175 mm (6.9") |
Sanitary process connection to NEUMO Bio-Connect clamp connection | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | 77.4 mm (3.0") | Approx. 52 mm (2") | |
65 | 10 | 90.9 mm (3.6") | ||
80 | 10 | 106 mm (4.2") | ||
100 | 10 | 119 mm (4.7") | ||
2” | 16 | 64 mm (2.5") | ||
2½” | 16 | 77.4 mm (3.0") | ||
3” | 10 | 90.9 mm (3.6") | ||
4” | 10 | 779 mm (4.7") |
Sanitary process connection to NEUMO Bio-Connect S flange connection | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | 125 mm (4.9") | Approx. 52 mm (2") | |
65 | 10 | 145 mm (5.7") | ||
80 | 10 | 155 mm (6.1") | ||
100 | 10 | 180 mm (7.1") | ||
2” | 16 | 125 mm (4.9") | ||
2½” | 10 | 135 mm (5.3") | ||
3” | 10 | 145 mm (5.7") | ||
4” | 10 | 180 mm (7.1") |
Threaded connection G¾", G1" and G2" acc. to DIN 3852 | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
¾“ | 63 | 37 mm (1.5") | Approx. 45 mm (1.8") | |
1“ | 63 | 48 mm (1.9") | Approx. 47 mm (1.9") | |
2“ | 63 | 78 mm (3.1") | Approx. 52 mm (2") |
Tank connection TG 52/50 and TG52/150 | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
25 | 40 | 63 mm (2.5") | Approx. 63 mm (2.5") | |
25 | 40 | 63 mm (2.5") | Approx. 170 mm (6.7") |
SMS socket with union nut | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
2“ | 25 | 84 mm (3.3") | Approx. 52 mm (2.1") | |
2½“ | 25 | 100 mm (3.9") | ||
3“ | 25 | 114 mm (4.5") |
SMS threaded socket | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
2“ | 25 | 70 x 1/6 mm | Approx. 52 mm (2.1") | |
2½“ | 25 | 85 x 1/6 mm | ||
3“ | 25 | 98 x 1/6 mm |
IDF socket with union nut | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
2“ | 25 | 77 mm (3") | Approx. 52 mm (2.1") | |
2½“ | 25 | 91 mm (3.6") | ||
3“ | 25 | 106 mm (4.2") |
IDF threaded socket | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
2“ | 25 | 64 mm (2.5") | Approx. 52 mm (2.1") | |
2½“ | 25 | 77,5 mm (3.1") | ||
3“ | 25 | 91 mm (3.6") |
Aseptic threaded socket to DIN 11864-1 Form A | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 25 | Approx. 52 mm (2.1") | ||
65 | 25 | |||
80 | 25 | |||
100 | 25 |
Aseptic flange with notch to DIN 11864-2 Form A | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | Approx. 52 mm (2.1") | ||
65 | 16 | |||
80 | 16 | |||
100 | 16 |
Aseptic flange with groove to DIN 11864-2 Form A | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 16 | Approx. 52 mm (2.1") | ||
65 | 16 | |||
80 | 16 | |||
100 |
Aseptic clamp with groove to DIN 11864-3 Form A | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
50 | 25 | Approx. 52 mm (2.1") | ||
65 | 25 | |||
80 | 16 | |||
100 | 16 |
Особенности
- High quality and service life
- High reliability even under extreme chemical and mechanical loads
- Extensive diagnosis and simulation functions
- Minimum conformity error
- Small long-term drift
- Wetted parts made of high-grade materials (such as stainless steel, Hastelloy, tantalum)
- Measuring range 0.008 bar to 400 bar (0.1 psi to 5802 psi)
- High measuring accuracy
- Parameterization over control keys and HART communication or PROFIBUS PA communication
Технические данные
SITRANS P300 for gauge and absolute pressure | ||||||
---|---|---|---|---|---|---|
HART | PROFIBUS PA and FOUNDATION fieldbus | |||||
Gauge pressure input | ||||||
Запрос коммерческого предложения× Сообщение отправлено× В ближайшее время сообщение будет обработано. Письмо с номером обращения отправлено на Ваш почтовый ящик. Спасибо за то, что выбрали Первый ZIP! Что-то пошло не так...× К сожалению, наша система расценила Ваше сообщение как спам. Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте. Приносим извинения за возможные неудобства. |