SITRANS P DS III with PMC connection Siemens
Чертеж
SITRANS P DS III pressure transmitters for gauge pressure, with PMC connection, dimensions in mm (inch)
The diagram shows a SITRANS P DS III with an example of a flange. In this drawing the height is subdivided into H1 and H2.
H1 = Height of the SITRANS P DS III up to a defined cross-section
H2 = Height of the flange up to this defined cross-section
Only the height H2 is indicated in the dimensions of the flanges.
PMC Style standard weldable sockets | PMC Style minibolt weldable sockets |
---|---|
PMC Style Standard (left) and PMC Style Minibolt (right) weldable sockets, dimensions in mm (inch)
Material: Stainless steel, Mat. No. 1.4404/316L
PMC Style standard | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
40.9 mm (1.6") | approx. 36.8 mm (1.4") |
PMC Style minibolt | ||||
---|---|---|---|---|
DN | PN | ∅D | H2 | |
26.3 mm (1.0") | approx. 33.1 mm (1.3") |
Технические данные
SITRANS P, DS III series for gauge pressure with PMC connection for the paper industry | ||||
---|---|---|---|---|
Input | ||||
Measured variable | Gauge pressure | |||
Span (fully adjustable) or nominal measuring range, max. operating pressure and max. test pressure | HART | PROFIBUS PA and FOUNDATION Fieldbus | ||
Span | Nominal measuring range | Max. perm. operating pressure MAWP (PS) | Max. permissible test pressure | |
0.01 ... 1 bar | 1 bar | 4 bar | 6 bar | |
0.04 ... 4 bar | 4 bar | 7 bar | 10 bar | |
0.16 ... 16 bar | 16 bar | 21 bar | 32 bar | |
Lower measuring limit | 100 mbar a/10 kPa a/1.45 psia | |||
Upper measuring limit | 100 % of max. span | |||
Output | HART | PROFIBUS PA and FOUNDATION Fieldbus | ||
Output signal | 4 ... 20 mA | Digital PROFIBUS PA and FOUNDATION Fieldbus signal | ||
| 3.55 mA, factory preset to 3.84 mA | - | ||
| 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA | - | ||
Load | ||||
| RB ≤ (UH - 10.5 V)/0.023 A in Ω, | - | ||
| RB = 230 ... 500 Ω (SIMATIC PDM) or | - | ||
Physical bus | - | IEC 61158-2 | ||
Protection against polarity reversal | Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. | |||
Electrical damping (step width 0.1 s) | Set to 2 s (0 ... 100 s) | |||
Measuring accuracy | According to IEC 60770-1 | |||
Reference conditions |
| |||
Measuring span ratio r (spread, Turn-Down) | r = maximum measuring span/set measuring span or nominal measuring range | |||
Error in measurement at limit setting including hysteresis and reproducibility | ||||
| ||||
| ≤ 0.075 % | |||
| ≤ (0.005 · r + 0.05) % | |||
Ambient temperature influence | ≤ (0.08 · r + 0.16) % | |||
Long-term stability (temperature change ±30 °C (±54 °F)) | ≤ (0.25 · r) % in 5 years | |||
Influence of mounting position | ≤ 0.1 mbar/0.01 kPa/0.00145 psi per 10° incline (zero point correction is possible with position error compensation) | |||
Effect of auxiliary power (in percent per voltage change) | 0.005 % per 1 V | |||
Measured-value resolution for PROFIBUS PA and FOUNDATION Fieldbus | 3 · 10-5 of nominal measuring range | |||
Rated conditions | ||||
Degree of protection according to IEC 60529 | IP66 (optional IP66/IP68), NEMA 4X | |||
Temperature of medium | -40 ... +100 °C (-40 ... +212 °F) | |||
Ambient conditions | ||||
| ||||
| -40 ... +85 °C (-40 ... +185 °F) | |||
| -50 ... +85 °C (-58 ... +185 °F) | |||
| ||||
| Relative humidity 0 ... 100 % | |||
| ||||
| According to IEC 61326 and NAMUR NE 21 | |||
Design | ||||
Weight (without options) | ≈ 1.5 kg (≈ 3.3 lb) | |||
Enclosure material | Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408 | |||
Wetted parts materials | ||||
| PTFE flat gasket | |||
| FPM (Viton) or optionally: FFPM or NBR | |||
Measuring cell filling | Silicone oil or inert fill fluid | |||
Process connection (standard) | Flush-mounted, 1½", PMC Standard design | |||
Process connection (minibolt) | Flush-mounted, 1", minibolt design | |||
Power supply UH | HART | PROFIBUS PA and FOUNDATION Fieldbus | ||
Terminal voltage on transmitter | 10.5 ... 45 V DC | - | ||
Auxiliary power | - | Bus-powered | ||
Separate supply voltage | - | Not necessary | ||
Bus voltage | ||||
| - | 9 ... 32 V | ||
| - | 9 ... 24 V | ||
Current consumption | ||||
| - | 12.5 mA | ||
| - | Yes | ||
| - | 15.5 mA | ||
Fault disconnection electronics (FDE) available | - | Yes | ||
Certificates and approvals | ||||
Classification according to PED 97/23/EC | For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) |
1) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064 . r + 0.08) %/28 °C (50 °F).
HART communication | |
---|---|
HART | 230 ... 1100 Ω |
Protocol | HART Version 5.x |
Software for computer | SIMATIC PDM |
PROFIBUS PA communication | |
---|---|
Simultaneous communication with master class 2 (max.) | 4 |
The address can be set using | Configuration tool or local operation (standard setting address 126) |
Cyclic data usage | |
| 5 (one measured value) or |
| 0, 1, or 2 (register operating mode and reset function for metering) |
Internal preprocessing | |
Device profile | PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B |
Function blocks | 2 |
| |
| Yes, linearly rising or falling characteristic |
| 0 … 100 s |
| Input /Output |
| parameterizable (last good value, substitute value, incorrect value) |
| Yes, one upper and lower warning limit and one alarm limit respectively |
| Can be reset, preset, optional direction of counting, simulation function of register output |
| parameterizable (summation with last good value, continuous summation, summation with incorrect value) |
| One upper and lower warning limit and one alarm limit respectively |
| 1 |
Transducer blocks | 2 |
| |
| Yes |
| Yes |
| Max. 30 nodes |
| Yes |
| Parameterizable |
| Constant value or by means of parameterizable ramp function |
FOUNDATION Fieldbus communication | |
---|---|
Function blocks | 3 function blocks analog input, 1 function block PID |
| |
| Yes, linearly rising or falling characteristic |
| 0 … 100 s |
| Output/input (can be locked within the device with a bridge) |
| parameterizable (last good value, substitute value, incorrect value) |
| Yes, one upper and lower warning limit and one alarm limit respectively |
| Yes |
| Standard FOUNDATION Fieldbus function block |
| 1 resource block |
Transducer blocks | 1 transducer block Pressure with calibration, 1 transducer block LCD |
| |
| Yes |
| Yes |
| Constant value or by means of parameterizable ramp function |