ATEX II 2G control unit, leakage compensation Siemens
Обзор
BARTEC EEx p control unit "Leakage compensation"
The APEX 2003.SI/A2 control unit controls and monitors the prepurging and operating phases of gas analyzers with containment systems in hazardous zone 1.
The control unit redundantly monitors the set overpressure of the purging gas. When the overpressure decreases, it is corrected to the adjustable setpoint (max. purging gas pressure 165 hPa).
Чертеж
BARTEC control unit, dimensions in mm
Схема подключения
BARTEC control unit, leakage compensation, gas connection diagram
BARTEC control unit, leakage compensation, electric connection diagram
Технические данные
Control unit ATEX IIG, compensation of losses through leaks | |
Guidelines | EC EMC directive 89/336/EEC, EC low voltage, RL 73/23/EEC, Ex directive 94/9/EC |
Design | Explosion-protected enclosure (EEx e) with viewing window in the cover |
Enclosure material | Glass fiber-reinforced polyester |
Degree of protection | IP65 |
Terminals | 2.5 mm, finely stranded |
Pressure sensors | MIN A = 0 … 300 hPa, |
Prepurging time | 0 … 99 min; 5 sec dropout delayed |
Weight | 11 kg |
Electrical data | |
Supply voltage | 230 V AC (115 V AC) ± 10 %, 48 … 62 Hz |
Power consumption | 21 W /230 V |
NO contacts | K2/3; max. 250 V, 5 A with cos ϕ = 1, K4/K5; supply voltage or floating, max. 250 V, 5 A with cos ϕ = 1 |
Communication | RS 485 interface |
Temperature switching value (option) | 0 … +40 °C |
Explosion protection | |
Marking | EEx e d ib [ia p] IIC T4/T6 |
Test certification | DMT 99 ATEX E 082 |
Ambient temperature | -20 … +40 °C |