1- and 2-phase, 24 V DC Siemens
Обзор
The 1-phase and 2-phase SITOP modular are technology power supplies for sophisticated solutions and offer maximum functionality for use in complex plants and machines. The ultra-wide input range allows connections to almost any 1-phase power supply system or directly between the line conductors of three-phase networks (2-phase) and ensures a high degree of safety even if there are large voltage fluctuations. The power boost provides up to three times the rated current for brief periods. In case of overload, you can choose between constant current with automatic restart or latching shutdown. The high degree of efficiency keeps energy consumption and heating in the control cabinet low, and the compact metal housing also saves space.
To further increase 24 V availability, the SITOP modular power supplies can be combined with buffer, DC UPS, redundancy and selectivity modules.
Main product highlights
- 24 V/5 A and 10 A, also available as version with PCB with protective coating.
- 1-phase and 2-phase ultra-wide input range
- Extremely slim design – no lateral installation clearances required
- Power Boost with 3 times the rated current (for 25 ms) for tripping protective devices
- Extra power with 1.5 times the rated current (5 s/min) for brief functional overload
- Selectable short-circuit response between constant current and restart
- Optional symmetrical load distribution for parallel operation
- Operating status on 3 LEDs
- High degree of efficiency up to 91 %
- Wide temperature range from -25 to +70 °C
- Comprehensive certifications, such as cULus, ATEX and GL
Технические данные
Order number | 6EP1333-3BA10 | 6EP1333-3BA10-8AC0 | 6EP1334-3BA10 | 6EP1334-3BA10-8AB0 | |
---|---|---|---|---|---|
Product | SITOP PSU200M | SITOP PSU200M | SITOP PSU200M | SITOP PSU200M | |
Power supply, type | 24 V/5 A | 24 V/5 A | 24 V/10 A | 24 V/10 A | |
Input |
|
|
|
| |
Input | 1-phase and 2-phase AC | 1-phase and 2-phase AC | 1-phase and 2-phase AC | 1-phase and 2-phase AC | |
Supply voltage |
|
|
|
| |
| 120 ... 230 V | 120 ... 230 V | 120 ... 230 V | 120 ... 230 V | |
| 230 ... 500 V | 230 ... 500 V | 230 ... 500 V | 230 ... 500 V | |
| Set by means of selector switch on the device; starting from Vin > 90/180 V | Set by means of selector switch on the device; starting from Vin > 90/180 V | Set by means of selector switch on the device | Set by means of selector switch on the device | |
Input voltage |
|
|
|
| |
| 85 ... 264 V | 85 ... 264 V | 85 ... 264 V | 85 ... 264 V | |
| 176 ... 550 V | 176 ... 550 V | 176 ... 550 V | 176 ... 550 V | |
Wide-range input | Yes | Yes | Yes | Yes | |
Overvoltage resistance | 1300 Vpeak, 1.3 ms | 1300 Vpeak, 1.3 ms | 1300 Vpeak, 1.3 ms | 1300 Vpeak, 1.3 ms | |
Mains buffering at Iout rated, min. | 25 ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | 25 ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | 25 ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | 25 ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | |
Rated line frequency | 50 ... 60 Hz | 50 ... 60 Hz | 50 ... 60 Hz | 50 ... 60 Hz | |
Rated line range | 47 ... 63 Hz | 47 ... 63 Hz | 47 ... 63 Hz | 47 ... 63 Hz | |
Input current |
|
|
|
| |
| 2.2 A | 2.2 A | 4.4 A | 4.4 A | |
| 1.2 A | 1.2 A | 2.4 A | 2.4 A | |
| 0.61 A | 0.61 A | 1.1 A | 1.1 A | |
Switch-on current limiting (+25 °C), max. | 35 A | 35 A | 35 A | 35 A | |
I²t, max. | 1.7 A²·s | 1.7 A²·s | 4 A²·s | 4 A²·s | |
Built-in incoming fuse | T 3.15 A (not accessible) | T 3.15 A (not accessible) | T 6.3 A (not accessible) | T 6.3 A (not accessible) | |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | |
Output |
|
|
|
| |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | |
Rated voltage Vout DC | 24 V | 24 V | 24 V | 24 V | |
Total tolerance, static ± | 3 % | 3 % | 3 % | 3 % | |
Static mains compensation, approx. | 0.1 % | 0.1 % | 0.1 % | 0.1 % | |
Static load balancing, approx. | 0.1 % | 0.1 % | 0.1 % | 0.1 % | |
Residual ripple peak-peak, max. | 50 mV | 50 mV | 50 mV | 50 mV | |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 200 mV | 200 mV | 200 mV | 200 mV | |
Adjustment range | 24 ... 28.8 V | 24 ... 28.8 V | 24 ... 28.8 V | 24 ... 28.8 V | |
Product function Output voltage adjustable | Yes | Yes | Yes | Yes | |
Output voltage setting | via potentiometer | via potentiometer | via potentiometer | via potentiometer | |
Status display | Green LED for 24 V OK | Green LED for 24 V OK | Green LED for 24 V OK | Green LED for 24 V OK | |
Signaling | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" | |
On/off behavior | Overshoot of Vout approx. 3 % | Overshoot of Vout approx. 3 % | Overshoot of Vout approx. 3 % | Overshoot of Vout approx. 3 % | |
Startup delay, max. | 1 s | 1 s | 1 s | 1 s | |
Voltage rise, typ. | 50 ms | 50 ms | 50 ms | 50 ms | |
Rated current value Iout rated | 5 A | 5 A | 10 A | 10 A | |
Current range | 0 ... 5 A | 0 ... 5 A | 0 ... 10 A | 0 ... 10 A | |
| +60 ... +70 °C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V) | +60 ... +70 °C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V) | |||
Active power supplied typical | 120 W | 120 W | 240 W | 240 W | |
Short-term overload current |
|
|
|
| |
| 15 A | 15 A | 30 A | 30 A | |
Duration of overloading capability for excess current |
|
|
|
| |
| 25 ms | 25 ms | 25 ms | 25 ms | |
Constant overload current |
|
|
|
| |
| 6 A | 6 A | 12 A | 12 A | |
Parallel switching for enhanced performance | Yes; switchable characteristic | Yes; switchable characteristic | Yes; switchable characteristic | Yes; switchable characteristic | |
Numbers of parallel switchable units for enhanced performance | 2 | 2 | 2 | 2 | |
Efficiency |
|
|
|
| |
Efficiency at Vout rated, Iout rated, approx. | 88 % | 88 % | 91 % | 91 % | |
Power loss at Vout rated, Iout rated, approx. | 17 W | 17 W | 24 W | 24 W | |
Active power loss during no-load operation maximum | 4 W | 4 W | 6 W | 6 W | |
Closed-loop control |
|
|
|
| |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.1 % | 0.1 % | 0.1 % | 0.1 % | |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 3 % | 3 % | 3 % | 3 % | |
Load step setting time 50 to 100%, typ. | 2 ms | 2 ms | 2 ms | 2 ms | |
Load step setting time 100 to 50%, typ. | 2 ms | 2 ms | 2 ms | 2 ms | |
Setting time maximum | 5 ms | 5 ms | 5 ms | 5 ms | |
Protection and monitoring |
|
|
|
| |
Output overvoltage protection | < 35 V | < 35 V | < 35 V | < 35 V | |
Current limitation, typ. | 6 A | 6 A | 12 A | 12 A | |
Property of the output Short-circuit proof | Yes | Yes | Yes | Yes | |
Short-circuit protection | Alternatively, constant current characteristic approx. 5.5 A or latching shutdown | Alternatively, constant current characteristic approx. 5.5 A or latching shutdown | Alternatively, constant current characteristic approx. 12 A or latching shutdown | Alternatively, constant current characteristic approx. 12 A or latching shutdown | |
Enduring short circuit current RMS value |
|
|
|
| |
| 6 A | 6 A | 12 A | 12 A | |
Overload/short-circuit indicator | LED yellow for "overload", LED red for "latching shutdown" | LED yellow for "overload", LED red for "latching shutdown" | LED yellow for "overload", LED red for "latching shutdown" | LED yellow for "overload", LED red for "latching shutdown" | |
Safety |
|
|
|
| |
Primary/secondary isolation | Yes | Yes | Yes | Yes | |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | |
Protection class | Class I | Class I | Class I | Class I | |
Leakage current |
|
|
|
| |
| 3.5 mA | 3.5 mA | 3.5 mA | 3.5 mA | |
| 0.25 mA | 0.25 mA | 0.32 mA | 0.32 mA | |
CE mark | Yes | Yes | Yes | Yes | |
UL/CSA approval | Yes | Yes | Yes | Yes | |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | |
Explosion protection | ATEX (EX) II 3G Ex nA nC IIC T4 Gc (for AC 120-230/230-400 V); cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3 | - | ATEX (EX) II 3G Ex nA nC IIC T4 Gc (for AC 120-230/230-400 V); cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3 | - | |
Certificate of suitability IECEx | No | No | No | No | |
Certificate of suitability NEC Class 2 | No | No | No | No | |
CB approval | Yes | Yes | Yes | Yes | |
Marine approval | GL, ABS | GL | GL, ABS | GL | |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 | IP20 | |
EMC |
|
|
|
| |
Emitted interference | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B | Запрос коммерческого предложения× Сообщение отправлено× В ближайшее время сообщение будет обработано. Письмо с номером обращения отправлено на Ваш почтовый ящик. Спасибо за то, что выбрали Первый ZIP! Что-то пошло не так...× К сожалению, наша система расценила Ваше сообщение как спам. Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте. Приносим извинения за возможные неудобства. |