1-phase, 24 V DC (PSU100D) Siemens

Обзор
The single-phase PSU100Ds are switch mode power supplies for direct wall mounting using screws. The flat and rugged aluminum enclosure with IP20 degree of protection can be installed in various orientations and is therefore ideal for installation locations with limited space or for mounting in control cabinets and enclosures without a DIN rail. The low-cost devices meet all the basic requirements for a power supply, typical applications being apparatus, automated equipment and automation solutions.
Main product highlights
- 24 V DC/ 2.1 A and 3.1 A, 4.1 A, 6.2 A and 12.5 A
- Compact metal enclosure
- Wide-range input
- Green LED for "24 V OK"
- Certification in accordance with CE and UL
- Adjustable output voltage from 22 to 28 V or from 11 to 14 V for compensating voltage drops
- Temperature range from -10 °C to +70 °C
Технические данные
Order number | 6EP1331-1LD00 | 6EP1332-1LD00 | 6EP1332-1LD10 | 6EP1333-1LD00 | 6EP1334-1LD00 | |
---|---|---|---|---|---|---|
Product | PSU100D | PSU100D | PSU100D | PSU100D | PSU100D | |
Power supply, type | 24 V/2.1 A | 24 V/3.1 A | 24 V/4.1 A | 24 V/6.2 A | 24 V/12.5 A | |
Input |
|
|
|
|
| |
Input | 1-phase AC | 1-phase AC | 1-phase AC | 1-phase AC | 1-phase AC | |
Rated voltage value Vin rated | 100 ... 240 V | 100 ... 240 V | 100 ... 240 V | 100 ... 240 V | 100 ... 240 V | |
Voltage range AC | 85 ... 264 V | 85 ... 264 V | 85 ... 264 V | 85 ... 264 V | 85 ... 264 V | |
Wide-range input | Yes | Yes | Yes | Yes | Yes | |
Mains buffering at Iout rated, min. | 15 ms; at Vin = 115/230 V | 15 ms; at Vin = 115/230 V | 15 ms; at Vin = 115/230 V | 15 ms; at Vin = 115/230 V | 15 ms; at Vin = 115/230 V | |
Rated line frequency | 50 ... 60 Hz | 50 ... 60 Hz | 50 ... 60 Hz | 50 ... 60 Hz | 50 ... 60 Hz | |
Rated line range | 47 ... 63 Hz | 47 ... 63 Hz | 47 ... 63 Hz | 47 ... 63 Hz | 47 ... 63 Hz | |
Input current |
|
|
|
|
| |
| 1.1 A | 1.5 A | 2 A | 3.1 A | 4 A | |
| 0.7 A | 1 A | 1.1 A | 2 A | 2 A | |
Switch-on current limiting (+25 °C), max. | 60 A | 60 A | 75 A | 75 A | 60 A | |
I²t, max. | 1.2 A²·s | 1.2 A²·s | 4 A²·s | 6.5 A²·s | 1.1 A²·s | |
Built-in incoming fuse | internal | internal | internal | internal | internal | |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B | |
Output |
|
|
|
|
| |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | |
Rated voltage Vout DC | 24 V | 24 V | 24 V | 24 V | 24 V | |
Total tolerance, static ± | 2 % | 2 % | 2 % | 2 % | 2 % | |
Static mains compensation, approx. | 0.5 % | 0.5 % | 0.5 % | 0.5 % | 0.5 % | |
Static load balancing, approx. | 1 % | 1 % | 1 % | 1 % | 0.5 % | |
Residual ripple peak-peak, max. | 100 mV | 100 mV | 100 mV | 100 mV | 100 mV | |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 100 mV | 100 mV | 100 mV | 100 mV | 100 mV | |
Adjustment range | 22 ... 28 V | 22 ... 28 V | 22 ... 28 V | 22 ... 28 V | 22 ... 28 V | |
Product function Output voltage adjustable | Yes | Yes | Yes | Yes | Yes | |
Output voltage setting | via potentiometer | via potentiometer | via potentiometer | via potentiometer | via potentiometer | |
Status display | Green LED for 24 V OK | Green LED for 24 V OK | Green LED for 24 V OK | Green LED for 24 V OK | Green LED for 24 V OK | |
Signaling | - | |||||
On/off behavior | Overshoot of Vout < 2 % | Overshoot of Vout < 2 % | Overshoot of Vout < 2 % | Overshoot of Vout < 2 % | Overshoot of Vout < 2 % | |
Startup delay, max. | 1 s | 2.5 s | 1 s | 1 s | 1 s | |
Voltage increase time of the output voltage maximum | 30 ms | 30 ms | 30 ms | 30 ms | 30 ms | |
Rated current value Iout rated | 2.1 A | 3.1 A | 4.1 A | 6.2 A | 12.5 A | |
Current range | 0 ... 2.1 A | 0 ... 3.1 A | 0 ... 4.1 A | 0 ... 6.2 A | 0 ... 12.5 A | |
| +50 ... +70 °C: Derating 2.5%/K | +50 ... +70 °C: Derating 2.5%/K | +50 ... +70 °C: Derating 2.5%/K | +50 ... +70 °C: Derating 2.5%/K | +50 ... +70 °C: Derating 2.5%/K | |
Active power supplied typical | 50 W | 75 W | 100 W | 150 W | 300 W | |
Parallel switching for enhanced performance | Yes | Yes | Yes | Yes | Yes | |
Numbers of parallel switchable units for enhanced performance | 2 | 2 | 2 | 2 | 2 | |
Efficiency |
|
|
|
|
| |
Efficiency at Vout rated, Iout rated, approx. | 86 % | 86 % | 86 % | 86 % | 86 % | |
Power loss at Vout rated, Iout rated, approx. | 8 W | 12 W | 16 W | 24 W | 48 W | |
Closed-loop control |
|
|
|
|
| |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.5 % | 0.5 % | 0.5 % | 0.5 % | 0.5 % | |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 5 % | 5 % | 5 % | 5 % | 5 % | |
Protection and monitoring |
|
|
|
|
| |
Output overvoltage protection | < 35 V | < 35 V | < 35 V | < 35 V | < 35 V | |
Current limitation, typ. | 2.5 A | 3.7 A | 4.9 A | 7.4 A | 15 A | |
Property of the output Short-circuit proof | Yes | Yes | Yes | Yes | Yes | |
Short-circuit protection | Electronic shutdown, automatic restart | Electronic shutdown, automatic restart | Electronic shutdown, automatic restart | Electronic shutdown, automatic restart | Electronic shutdown, automatic restart | |
Enduring short circuit current RMS value |
|
|
|
|
| |
| 6 A | 6 A | 10 A | 16 A | 15 A | |
Overload/short-circuit indicator | - | - | - | - | - | |
Safety |
|
|
|
|
| |
Primary/secondary isolation | Yes | Yes | Yes | Yes | Yes | |
Galvanic isolation | Safety extra low output voltage Vout according to EN 60950-1 | Safety extra low output voltage Vout according to EN 60950-1 | Safety extra low output voltage Vout according to EN 60950-1 | Safety extra low output voltage Vout according to EN 60950-1 | Safety extra low output voltage Vout according to EN 60950-1 | |
Protection class | Class I | Class I | Class I | Class I | Class I | |
Leakage current |
|
|
|
|
| |
| 3.5 mA | 3.5 mA | 3.5 mA | 3.5 mA | 3.5 mA | |
| 1 mA | 1 mA | 1 mA | 1 mA | 1 mA | |
CE mark | Yes | Yes | Yes | Yes | Yes | |
UL/CSA approval | Yes | Yes | Yes | Yes | Yes | |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 60950-1, CSA C22.2 No. 60950-1), File E151273 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 60950-1, CSA C22.2 No. 60950-1), File E151273 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 60950-1, CSA C22.2 No. 60950-1), File E151273 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 60950-1, CSA C22.2 No. 60950-1), File E151273 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 60950-1, CSA C22.2 No. 60950-1), File E151273 | |
Explosion protection | - | - | - | - | - | |
Certificate of suitability IECEx | No | No | No | No | No | |
Certificate of suitability NEC Class 2 | No | No | No | No | No | |
FM approval | - | - | - | - | - | |
CB approval | Yes | Yes | Yes | Yes | Yes | |
Marine approval | - | - | - | - | - | |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 | IP20 | IP20 | |
EMC |
|
|
|
|
| |
Emitted interference | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B | |
Supply harmonics limitation | not applicable | EN 61000-3-2 | EN 61000-3-2 | - | EN 61000-3-2 | |
Noise immunity | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 | |
Operating data |
|
|
|
|
| |
Ambient temperature |
|
|
| Запрос коммерческого предложения× Сообщение отправлено× В ближайшее время сообщение будет обработано. Письмо с номером обращения отправлено на Ваш почтовый ящик. Спасибо за то, что выбрали Первый ZIP! Что-то пошло не так...× К сожалению, наша система расценила Ваше сообщение как спам. Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте. Приносим извинения за возможные неудобства. |