SITOP DC-UPS Siemens
Область применения
These battery modules that can be connected in parallel bridge power failures for a few hours. This enables processes or parts of them to be continued, measured values to be recorded without interruption and communication to be maintained. High-performance industrial PCs that have to be shut down also have somewhat higher energy demands. Especially if a large panel continues to be operated during the shutdown. The DC UPS is used, for example, in machine tool production, in the textile industry, in all types of production lines, bottling plants or also for the obstacle lights of wind power plants.
The serial or USB interface and a free software tool enable easy communication with a PC.
Configuration with SITOP DC UPS and battery module: 24 V buffering to maintain communication, signaling and sensor measured values. To relieve the load on the UPS, the actuators are supplied directly from the power supply unit.
Обзор
By combining a DC UPS module with at least one 24 V battery module and a SITOP power supply unit, longer power failures can be bridged without any interruption. Even if a greater buffering current is required, the DC UPS with maintenance-free lead battery provides optimum safety. It spans power failures up to several hours long and delivers up to 40 A.
Дизайн
- DC UPS modules 24 V/6 A, 15 A, 40 A
- Digital inputs/outputs, optionally with serial or USB interface
- Battery modules 1.2 Ah, 3.2 Ah, 7 Ah, 12 Ah with lead rechargeable batteries of corrosion-resistant lead-calcium high-performance grid plates and glass fiber
- Battery module 2.5 Ah with "high-temperature battery" of pure lead
Функции
SITOP DC UPS software tool
Via the USB interface, all relevant messages about the status of the uninterruptible DC power supply can be transmitted to a PC (e.g. SIMATIC IPC). The DC UPS can also be configured via the USB interface.
The SITOP DC UPS software provides the user with a free tool that is extremely easy to use for the purpose of monitoring and configuring the DC UPS. Signals sent from the uninterruptible DC power supply can be processed on the PC. In monitoring mode, the statuses of the uninterruptible DC power supply are visualized on the PC.
Safe shutdown in the event of a power failure and automatic PC restart are supported. It is also possible to freely define responses to the different operating states of the uninterruptible DC power supply, so that extremely flexible integration into a wide variety of applications is possible.
Overview of configuration possibilities:
- Times for shutting down the PC
- UPS switch-off
- Further processing of all signals, e.g. linking to proprietary software or WinCC flexible
- Monitoring and display of UPS operating status
- OPC server for linking signals to proprietary applications
- Automatic restarting of IPCs when power is restored during shutdown
The software runs under the operating systems Windows 2000, Windows XP, Windows Vista and Windows 7. Free download from:
http://support.automation.siemens.com/WW/view/en/48946053
Monitoring and configuration window of software V3 for SITOP DC UPS
Особенности
- 24 V buffering for a few hours for the purpose of continuing processes
- Maintenance-free battery modules from 1.2 to 12 Ah
- High reliability and availability due to monitoring of the operational readiness, battery feeder, aging and charging status
- Long operating life of loads and batteries due to integrated battery management
- Settings by means of DIP switches: Battery connection threshold, end-of-charge voltage, charging current, bridging time
- SW tool, free of charge, for easy configuring and integrating in PC-based systems
Технические данные
The table shows the maximum buffering times for the battery modules for different load currents.
The SITOP Selection Tool offers detailed selection guidance according to criteria such as the required backup time, nominal current, peak current and battery connection threshold:
http://www.siemens.com/sitop-selection-tool
Load current | Battery module 1.2 Ah | Battery module 3.2 Ah | Battery module 7 Ah | Battery module 12 Ah (6EP1935-6MF01) | Battery module 2.5 Ah |
---|---|---|---|---|---|
1 A | 34.5 min | 2.6 h | 5.4 h | 9 h | 2 h |
2 A | 15 min | 1 h | 2.6 h | 4.6 h | 1 h |
3 A | 9 min | 39.3 min | 1.6 h | 2.9 h | 37.5 min |
4 A | 6.5 min | 27.1 min | 1.2 h | 2.2 h | 27 min |
6 A | 3.5 min | 17.5 min | 41 min | 1.2 h | 17.6 min |
8 A | 2 min | 12.1 min | 28.6 min | 53.3 min | 12.5 min |
10 A | 1 min | 9 min | 21.8 min | 43.5 min | 8.8 min |
12 A | - | 7 min | 17.3 min | 33.3 min | 6.8 min |
14 A | - | 5 min | 15.1 min | 27.5 min | 5.1 min |
16 A | - | 4 min | 12.5 min | 23.8 min | 4.3 min |
20 A | - | 1 min | 9.1 min | 20.1 min | - |
25 A | - | - | - | 12.6 min | - |
30 A | - | - | - | 9.1 min | - |
35 A | - | - | - | 17.1 min (2 x 12 Ah) | - |
40 A | - | - | - | 13.5 min (2 x 12 Ah) | - |
Important information for selecting the battery capacity:
Determination of the mains buffering times is based on the discharge period of new or non-aged, completely charged battery modules at a battery temperature not below +25 °C to the shutdown of the DC UPS.
Battery aging reduces the still available battery capacity up until the end of the service life to typically around 50% of the original capacity value when new (1.2 Ah/3.2 Ah/7 Ah, etc.) and the internal resistance increases. When the message "Battery charge > 85%" appears, only around 50% x 85% = approx. 43% of the originally available capacity can be assumed at the end of the battery service life.
At battery temperatures below +25 °C, the available capacity drops approximately by another 30% at +5 °C battery temperature, to approximately 70% of the approximately remaining 43%. There is then only around 30% of the original capacity available.
A significantly larger battery capacity must therefore be selected when configuring the plant: A drop to approx. 50% is compensated for by selecting 1 / approx. 0.5 = approx. double the battery capacity (required as per the table for the relevant load current and the relevant buffering time). Available capacity of approx. 43% is compensated for by selecting 1 / approx. 0.43 = approx. 2.33 times the battery capacity. Available capacity of approx. 30% is compensated for by selecting 1 / approx. 0.3 = approx. 3.33 times the battery capacity.
Recommendation:
Instead of installing double the battery capacity, regular battery replacement halfway through the expected service life (reduction of capacity to approx. 50%) can be more advisable for the following reasons: Capacity does not drop below 100% until the halfway point of the expected battery life (or slightly beyond). With regular replacement after this point, only the single battery capacity (instead of double capacity) must be installed due to aging (-> neutral in price with regard to battery module costs, but only requires half the space).
Replacing the battery after half its service life dispenses above all with the large scatter range of the residual capacity at the end of the service life, which is not accurately defined by battery manufacturers (after the full time, many batteries are above, but many are also below the average 50% residual capacity, that is to say, even if double the capacity is installed, the influence of aging at the end of service life is not reliably compensated for, rather only typically) -> When replacing after half the expected service life, the configured buffering time is maintained with considerably greater reliability.
In the case of batteries stored in cool conditions (not above +25 °C) and for not longer than approximately 4 months, the following service life can be assumed, strongly dependent on battery temperature:
Battery temperature | Drop to approx. 50% of residual capacity | Recommendation: Replace (at 100% of residual capacity) | Alternative recommendation |
+20 °C | 4 years | 2 years | |
+30 °C | 2 years | 1 year | |
+40 °C | 1 year | 0.5 years | Install double capacity and replace 1 x per year |
In normal cases (installation in the coolest location in the control cabinet at approx. +30 °C), the battery should be replaced with single installed battery capacity in accordance with the selection table after 1 year of operation!
- On the DC UPS module 40 A, at least 2 battery modules of 7 Ah or higher must be connected in parallel for output currents > 30 A. When connecting battery modules in parallel, you must ensure identical capacity and aging.
- After a power failure, the battery module is disconnected from the loads at the end of the selected buffering time either automatically or electronically by opening the On/Off control circuit, and as soon as the 24 V input voltage is available again, it is quickly re-charged with the charge current of the relevant DC UPS module (with I-U charge characteristic: First constant current I for fast charging, and changeover to constant voltage U to maintain the charge when the battery is almost full).
Product | DC UPS module | DC UPS module | DC UPS module |
Power supply, type | 6 A | 15 A | 40 A |
Article number | 6EP1931-2DC21 | 6EP1931-2EC211) | 6EP1931-2FC211) |
Input L+/M in normal operation | |||
Controlled DC voltage | Controlled DC voltage | Controlled DC voltage | |
Rated voltage Uinrated2) | 24 V DC | 24 V DC | 24 V DC |
Voltage range | 22 ... 29 V DC | 22 ... 29 V DC | 22 ... 29 V DC |
Connection threshold for battery | 22.5 V DC ± 0.1 V (factory setting), adjustable in the range 22 ... 25.5 V DC (in 0.5 V increments) | 22.5 V DC ± 0.1 V (factory setting), adjustable in the range 22 ... 25.5 V DC (in 0.5 V increments) | 22.5 V DC ± 0.1 V (factory setting), adjustable in the range 22 ... 25.5 V DC (in 0.5 V increments) |
Rated current Iin rated | 6 A + approx. 0.6 A with empty battery | 15 A + approx. 1 A with empty battery | 40 A + approx. 2.6 A with empty battery |
Mains buffering | |||
Line buffering or buffer time | Dependent on connected battery and load current, see selection table battery module and mains buffering times as well as the relevant important information notes! | Dependent on connected battery and load current, see selection table battery module and mains buffering times as well as the relevant important information notes! | Dependent on connected battery and load current, see selection table battery module and mains buffering times as well as the relevant important information notes! |
On/off control circuit | External isolated NO contact required (load max. 15 V DC/max. 10 mA). With an open control circuit, the accumulator is isolated from output L+, thus canceling line buffering. If there is no input voltage, a quiescent current of approximately 0.3 mA is drawn from the battery disconnected from the output. | External isolated NO contact required (load max. 15 V DC/max. 10 mA). With an open control circuit, the accumulator is isolated from output L+, thus canceling line buffering. If there is no input voltage, a quiescent current of approximately 0.3 mA is drawn from the battery disconnected from the output. | External isolated NO contact required (load max. 15 V DC/max. 10 mA). With an open control circuit, the accumulator is isolated from output L+, thus canceling line buffering. If there is no input voltage, a quiescent current of approximately 0.3 mA is drawn from the battery disconnected from the output. |
Methods of setting the buffering time | Adjustableusing DIP switches to a maximum buffering time up to forced shutdown through exhaustive discharge protection (at approx. 19 V) or to a limited buffering time of 5 ... 635 s (in 10 s increments) | Adjustableusing DIP switches to a maximum buffering time up to forced shutdown through exhaustive discharge protection (at approx. 19 V) or to a limited buffering time of 5 ... 635 s (in 10 s increments) | Adjustableusing DIP switches to a maximum buffering time up to forced shutdown through exhaustive discharge protection (at approx. 19 V) or to a limited buffering time of 5 ... 635 s (in 10 s increments) |
Interruption | Adjustableusing DIP switch, either:
| Adjustableusing DIP switch, either:
No forced interruption on expiry of the set buffer time | Adjustableusing DIP switch, either:
No forced interruption on expiry of the set buffer time |
Output L+/M in normal operation | |||
Rated voltage value Uout rated | 24 V DC (output voltage of SITOP power supply) | 24 V DC (output voltage of SITOP power supply) | 24 V DC (output voltage of SITOP power supply) |
Voltage range | Input voltage Vin less approx. 0.5 V DC | Input voltage Vin less approx. 0.5 V DC | Input voltage Vin less approx. 0.5 V DC |
Startup delay | Approx. 1 s | Approx. 1 s | Approx. 1 s |
Voltage rise | Typ. 60 ms | Typ. 60 ms | Typ. 360 ms |
Output current Iout | 0 ... 6 A | 0 ... 15 A | 0 ... 40 A |
Dynamic current with overload | Electronic current limitation to 1.05 ... 1.4 x Ioutrated for approx. 80 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts) | Electronic current limitation to 1.05 ... 1.4 x Ioutrated for approx. 80 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts) | Electronic current limitation to 1.05 ... 1.4 x Ioutrated for approx. 80 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts) |
Dynamic current with short-circuit | Electronic current limitation to 1.5 ... 3 x Ioutrated for approx. 20 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts) | Electronic current limitation to 1.5 ... 3 x Ioutrated for approx. 20 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts) | Electronic current limitation to 1.5 ... 3 x Ioutrated for approx. 20 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts) |
Output L+/M with battery operation | |||
Rated voltage value Uout rated | 24 V DC (from battery module) | 24 V DC (from battery module) | 24 V DC (from battery module) |
Approximate voltage range | 27 V to 19 V DC at Iout = 0.05 x C x 1/h or 24 V at Iout = 1 x C x 1/h or 23 V at Iout = 2 x C x 1/h (C = total connected battery capacity in Ah), 19 V disconnection threshold for exhaustive discharge protection | 27 V to 19 V DC at Iout = 0.05 x C x 1/h or 24 V at Iout = 1 x C x 1/h or 23 V at Iout = 2 x C x 1/h (C = total connected battery capacity in Ah), 19 V disconnection threshold for exhaustive discharge protection | 27 V to 19 V DC at Iout = 0.05 x C x 1/h or 24 V at Iout = 1 x C x 1/h or 23 V at Iout = 2 x C x 1/h (C = total connected battery capacity in Ah), 19 V disconnection threshold for exhaustive discharge protection |
Output current Iout3) | 0 ... 6 A (permanently permissible) | 0 ... 15 A (permanently permissible) | 0 ... 40 A (permanently permissible) |
Dynamic current with overload | Electronic current limitation to 1.05 to 1.4 x Ioutrated for approx. 80 ms, then latching switch-off of output (restart following return to normal operation) | Electronic current limitation to 1.05 to 1.4 x Ioutrated for approx. 80 ms, then latching switch-off of output (restart following return to normal operation) | Electronic current limitation to 1.05 to 1.4 x Ioutrated for approx. 80 ms, then latching switch-off of output (restart following return to normal operation) |
Dynamic current with short-circuit | Electronic current limitation to 1.5 to 3 x Ioutrated for approx. 20 ms, then latching switch-off of output (restart following return to normal operation) | Electronic current limitation to 1.5 to 3 x Ioutrated for approx. 20 ms, then latching switch-off of output (restart following return to normal operation) | Electronic current limitation to 1.5 to 3 x Ioutrated for approx. 20 ms, then latching switch-off of output (restart following return to normal operation) |
Output +Bat/-Bat in normal operation | |||
Output +Bat/-Bat in normal operation | I-U charging characteristic (first constant current I, then constant voltage U) | I-U charging characteristic (first constant current I, then constant voltage U) | I-U charging characteristic (first constant current I, then constant voltage U) |
End-of-charge voltage V | 26.6 V DC ± 0.1 V (factory setting for +40 °C battery temperature), adjustable in the range 26.3 ... 29.3 V (in 0.1 V increments) | 26.6 V DC ± 0.1 V (factory setting for +40 °C battery temperature), adjustable in the range 26.3 ... 29.3 V (in 0.1 V increments) | 26.6 V DC ± 0.1 V (factory setting for +40 °C battery temperature), adjustable in the range 26.3 ... 29.3 V (in 0.1 V increments) |
Charging current I | Approx. 0.4 A (factory setting), adjustable to 0.2 A or 0.4 A (charging is carried out with closed and open on/off circuit); at a battery voltage of < 6 V (batteries defective), charging is not carried out as a protective measure. | Approx. 0.7 A (factory setting), adjustable to 0.35 A or 0.7 A (charging is carried out with closed and open on/off circuit); at a battery voltage of < 6 V (batteries defective), charging is not carried out as a protective measure. | Approx. 2 A (factory setting), adjustable to 1 A or 2 A (charging is carried out with closed and open on/off circuit); at a battery voltage of < 6 V (batteries defective), charging is not carried out as a protective measure. |
Efficiency/heat loss | |||
at Uoutrated, Ioutrated approx. | 95% / 7 W | 96.2% / 14 W | 97.2% / 28.6 W |
With battery operation, approx. | 94.5% / 8 W | 96% / 15 W | 96.9% / 33.6 W |
Protection and monitoring | |||
Reverse polarity protection | Against polarity reversal on input voltage and batteries | Against polarity reversal on input voltage and batteries | Against polarity reversal on input voltage and batteries |
Overload protection | In accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in battery mode (restart following return to normal operation) | In accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in battery mode (restart following return to normal operation) | In accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in battery mode (restart following return to normal operation) |
Short-circuit protection | In accordance with "dynamic current with short-circuit" in normal operation (automatic restart attempts) or in battery mode (restart following return to normal operation). Built-in (not accessible) 16 A fuse (6 A and 15 A on DC UPS module) or 64 A fuse (40 A on DC UPS module). | In accordance with "dynamic current with short-circuit" in normal operation (automatic restart attempts) or in battery mode (restart following return to normal operation). Built-in (not accessible) 16 A fuse (6 A and 15 A on DC UPS module) or 64 A fuse (40 A on DC UPS module). | In accordance with "dynamic current with short-circuit" in normal operation (automatic restart attempts) or in battery mode (restart following return to normal operation). Built-in (not accessible) 16 A fuse (6 A and 15 A on DC UPS module) or 64 A fuse (40 A on DC UPS module). |
Exhaustive discharge protection | Automatic shutdown when battery voltage falls below approx. 19 V. At a battery voltage of < 6 V (batteries defective), charging is not carried out as a protective measure. | Automatic shutdown when battery voltage falls below approx. 19 V. At a battery voltage of < 6 V (batteries defective), charging is not carried out as a protective measure. | Automatic shutdown when battery voltage falls below approx. 19 V. At a battery voltage of < 6 V (batteries defective), charging is not carried out as a protective measure. |
Monitoring "Wire break in battery circuit" | Alarm signal if battery circuit not closed or if it opens during operation (cyclic check approximately every 20 s) | Alarm signal if battery circuit not closed or if it opens during operation (cyclic check approximately every 20 s) | Alarm signal if battery circuit not closed or if it opens during operation (cyclic check approximately every 20 s) |
Monitoring "Battery replacement required" | Alarm signal flashing at approx. 0.25 Hz repetition frequency (approx. 2 s alarm, approx. 2 s no alarm, approx. 2 s alarm, etc.). Check every 4 hours with 6 ohm load for 1 s if no buffer mode or switch-off has taken place within 4 hours. | Alarm signal flashing at approx. 0.25 Hz repetition frequency (approx. 2 s alarm, approx. 2 no alarm, approx. 2 s alarm, etc.). Check every 4 hours with 3 ohm load for 1 s if no buffer mode or switch-off has taken place within 4 hours. | Alarm signal flashing at approx. 0.25 Hz repetition frequency (approx. 2 s alarm, approx. 2 no alarm, approx. 2 s alarm, etc.). Check every 4 hours with 1 ohm load for 1 s if no buffer mode or switch-off has taken place within 4 hours. No monitoring is performed when the compatibility switch is in the "On" position! |
Monitoring "Battery charge status > 85%" | Indication whether batteries are charged to at least 85% of residual capacity still available depending on aging | Indication whether batteries are charged to at least 85% of residual capacity still available depending on aging | Indication whether batteries are charged to at least 85% of residual capacity still available depending on aging |
Signaling4) | |||
Normal operation | Green LED (O K) and isolated changeover contact "24 V DC OK/Bat" at setting "24 V DC OK" 5) | Green LED (O K) and isolated changeover contact "24 V DC OK/Bat" at setting "24 V DC OK" 5) | Green LED (O K) and isolated changeover contact "24 V DC OK/Bat" at setting "24 V DC OK" 5) |
Buffering or battery operation (battery supplies load alone or in addition to PS in the case of overload) | Yellow LED (Bat) and isolated changeover contact "24 V DC OK/Bat" at setting "Bat" (de-energized position) | Yellow LED (Bat) and isolated changeover contact "24 V DC OK/Bat" at setting "Bat" (de-energized position) | Yellow LED (Bat) and isolated changeover contact "24 V DC OK/Bat" at setting "Bat" (de-energized position) |
Alarm (buffer not ready, or prewarning at and above < 20.4 V battery voltage) | Red LED (alarm) and isolated changeover contact at setting "Alarm" (= off position). | Red LED (alarm) and isolated changeover contact at setting "Alarm" (= off position). | Red LED (alarm) and isolated changeover contact at setting "Alarm" (= off position). |
"Battery replacement required" | Red LED (alarm) flashing at 0.25 Hz and isolated changeover contact (alarm) switching at approx. 0.25 Hz | Red LED (alarm) flashing at 0.25 Hz and isolated changeover contact (alarm) switching at approx. 0.25 Hz | Red LED (alarm) flashing at 0.25 Hz and isolated changeover contact (alarm) switching at approx. 0.25 Hz |
"Battery charge status > 85%" | Second green LED (Bat > 85%) and isolated NO contact closed (off position = open) | Second green LED (Bat > 85%) and isolated NO contact closed (off position = open) | Second green LED (Bat > 85%) and isolated NO contact closed (off position = open) |
Compatibility switch | Only on 6EP1931-2FC21 | Only on 6EP1931-2FC21 | Only on 6EP1931-2FC21 |
Optional interface and software | |||
Serial interface | Only for 6EP1931-2.C31 | Only for 6EP1931-2.C31 | Only for 6EP1931-2.C31 |
USB interface | Only for 6EP1931-2.C42 | Only for 6EP1931-2.C42 | Only for 6EP1931-2.C42 |
Software | DC UPS software tool (runs under Windows 2000, Windows XP, Windows Vista and Windows 7) for reading and processing signals | DC UPS software tool (runs under Windows 2000, Windows XP, Windows Vista and Windows 7) for reading and processing signals | DC UPS software tool (runs under Windows 2000, Windows XP, Windows Vista and Windows 7) for reading and processing signals |
Control signals | |||
On/off control signal | Buffering is terminated or the battery is disconnected from the output by opening the control circuit or by means of DIP switches on the device (DIP switch must be in "Off" position). All other functions are retained. | Buffering is terminated or the battery is disconnected from the output by opening the control circuit or by means of DIP switches on the device (DIP switch must be in "Off" position). All other functions are retained. | Buffering is terminated or the battery is disconnected from the output by opening the control circuit or by means of DIP switches on the device (DIP switch must be in "Off" position). All other functions are retained. |
"Remote Timerstart" via serial interface or USB | Starts mains buffering for the set buffering time | Starts mains buffering for the set buffering time | Starts mains buffering for the set buffering time |
Safety | |||
Primary/secondary isolation | No | No | No |
Safety class | Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required) | Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required) | Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required) |
EMC | |||
Emitted interference | Radio interference suppression according to EN 55022, Class B | Radio interference suppression according to EN 55022, Class B | Radio interference suppression according to EN 55022, Class B |
Interference immunity | Interference immunity according to EN 61000-6-2 | Interference immunity according to EN 61000-6-2 | Interference immunity according to EN 61000-6-2 |
Environmental conditions | |||
Ambient temperature during operation | -25 ... + 60 °C with natural convection | -25 ... + 60 °C with natural convection | -25 ... + 60 °C with natural convection |
Transport/storage temperature | – 40 ... + 85 °C | – 40 ... + 85 °C | – 40 ... + 85 °C |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 |
Humidity class | Rated conditions in accordance with EN 60721, climate class 3K3 (relative humidity 5% ... 85% and absolute humidity 1 g/m3 ... 25 g/m3; no condensation) | Rated conditions in accordance with EN 60721, climate class 3K3 (relative humidity 5% ... 85% and absolute humidity 1 g/m3 ... 25 g/m3; no condensation) | Rated conditions in accordance with EN 60721, climate class 3K3 (relative humidity 5% ... 85% and absolute humidity 1 g/m3 ... 25 g/m3; no condensation) |
Approvals | |||
CE mark | Yes | Yes | Yes |
UL/cUL (CSA) approval | cULus-listed (UL 508, CSA C22.2 No.107.1), File E197259 | cULus-listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
Mechanics | |||
Input connections 24 V DC | 2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG | 2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG | 2 screw terminals for 0.33 ... 10 mm2/22 ... 7 AWG |
Output connections 24 V DC | 4 screw terminals for 1 ... 4 mm2/17 ... 11 AWG | 4 screw terminals for 1 ... 4 mm2/17 ... 11 AWG | 4 screw terminals for 0.33 ... 10 mm2/22 ... 7 AWG |
Battery module connections 24 V DC | 2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG | 2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG | 2 screw terminals for 0.33 ... 10 mm2/22 ... 7 AWG |
Connections for control circuit and alarm signals | 10 screw terminals for 0.5 ... 2.5 mm2/20 ... 13 AWG | 10 screw terminals for 0.5 ... 2.5 mm2/20 ... 13 AWG | 10 screw terminals for 0.5 ... 2.5 mm2/20 ... 13 AWG |
Dimensions (W x H x D) in mm | 50 x 125 x approx. 125 | 50 x 125 x approx. 125 | 102 x 125 x 125 |
Weight, approx. | 0.4 kg (with serial or USB interface: 0.45 kg). | 0.4 kg (with serial or USB interface: 0.45 kg). | 1.1 kg (with serial or USB interface: 1.1 kg). |
Installation | Snaps onto DIN rail EN 60715 35 x 7.5/15 | Snaps onto DIN rail EN 60715 35 x 7.5/15 | Snaps onto DIN rail EN 60715 35 x 7.5/15 |
1) SIPLUS module, see SIPLUS range
2) All SITOP 24 V DC power supplies are permissible without restriction.
3) In order to implement more than 30 A up to max. 40 A output current for the DC-UPS module 40 A, two 7 Ah or 12 Ah battery modules connected in parallel are required.
4) Permissible contact rating: 60 V DC/1 A or 30 V AC/1 A.
5) "24 V DC OK" means: voltage of the power supply unit is greater than the battery connection threshold set on the DC UPS module.