Battery modules Siemens

Обзор
Maintenance-free battery modules with 1.2 Ah up to 12 Ah (lead-gel accumulator) for ambient temperatures from 0 to +40 °C as well as high-temperature battery module with 2.5 Ah (pure-lead accumulator) for ambient temperatures of –40 °C to +60 °C. The battery modules are completely prewired with battery retainer and terminals. For longer buffer times, the battery modules can be connected in parallel. Mounting onto standard mounting rail or directly to the wall.
Технические данные
Order number | 6EP1935-6MC01 | 6EP1935-6MD31 | 6EP1935-6MD11 | 6EP1935-6ME21 | 6EP1935-6MF01 | |
---|---|---|---|---|---|---|
Product | SITOP Battery module | SITOP Battery module | SITOP Battery module | SITOP Battery module | SITOP Battery module | |
Product type | Battery module 1.2 Ah | Battery module 2.5 Ah | Battery module 3.2 Ah | Battery module 7 Ah | Battery module 12 Ah | |
Charging current charging voltage |
|
|
|
|
| |
End-of-charge voltage for DC |
|
|
|
|
| |
| 29 V | |||||
| 28.6 V | |||||
| 27.8 V | 28.3 V | 27.8 V | 27.8 V | 27.8 V | |
| 27.3 V | 27.9 V | 27.3 V | 27.3 V | 27.3 V | |
| 26.8 V | 27.5 V | 26.8 V | 26.8 V | 26.8 V | |
| 26.6 V | 27.2 V | 26.6 V | 26.6 V | 26.6 V | |
| 26.3 V | 26.8 V | 26.3 V | 26.3 V | 26.3 V | |
| 26.4 V | |||||
Permissible charging current, max. | 0.3 A | 5 A | 0.8 A | 1.75 A | 3 A | |
Safety |
|
|
|
|
| |
Short-circuit protection | Battery fuse 7.5 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 15 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 15 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 20 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 20 A/32 V (solid-state circuitry blade-type fuse + support) | |
Design of the overload protection | Valve control | Valve control | Valve control | Valve control | Valve control | |
Safety |
|
|
|
|
| |
Protection class | Class III | Class III | Class III | Class III | Class III | |
CE mark | Yes | Yes | Yes | Yes | Yes | |
UL/cUL (CSA) approval | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | |
Degree of protection (EN 60529) | IP00 | IP00 | IP00 | IP00 | IP00 | |
Operating data note |
|
|
|
|
| |
Operating data note | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | |
Ambient temperature |
|
|
|
|
| |
| -15 ... +50 °C | -40 ... +60 °C | -15 ... +50 °C | -15 ... +50 °C | -15 ... +50 °C | |
| -20 ... +50 °C | -40 ... +60 °C | -20 ... +50 °C | -20 ... +50 °C | -20 ... +50 °C | |
| -20 ... +50 °C | -40 ... +60 °C | -20 ... +50 °C | -20 ... +50 °C | -20 ... +50 °C | |
Relative temporary capacity loss at 20 °C in a month typical | 3 % | 3 % | 3 % | 3 % | 3 % | |
Service life |
|
|
|
|
| |
Service life of lead-acid battery |
|
|
|
|
| |
| capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | |
| 4 y | 10 y | 4 y | 4 y | 4 y | |
| 2 y | 7 y | 2 y | 2 y | 2 y | |
| 1 y | 3 y | 1 y | 1 y | 1 y | |
| 0.5 y | 1.5 y | 0.5 y | 0.5 y | 0.5 y | |
| 1 y | |||||
Ambient temperature during storage Note | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | |
Mechanics |
|
|
|
|
| |
Connection technology | spring-loaded terminals | spring-loaded terminals | spring-loaded terminals | spring-loaded terminals | spring-loaded terminals | |
Connection for power supply unit | 1 screw terminal each for 0.08 ... 2.5 mm² for + BATT and - BATT | 1 screw terminal each for 0.08 ... 2.5 mm² for + BATT and - BATT | 1 screw terminal each for 0.08 ... 2.5 mm² for + BATT and - BATT | 1 screw terminal each for 0.08 ... 4 mm² for + BATT and - BATT | 1 screw terminal each for 0.08 ... 4 mm² for + BATT and - BATT | |
Product component belonging to | Accessories pack with solid-state circuitry fuse 7.5 A | Accessories pack with solid-state circuitry fuse 15 A | Accessories pack with solid-state circuitry fuse 15 A | Accessories pack with solid-state circuitry fuse 20 A and 30 A | Accessories pack with solid-state circuitry fuse 20 A and 30 A | |
Width of the enclosure | 96 mm | 265 mm | 190 mm | 186 mm | 253 mm | |
Height of the enclosure | 106 mm | 151 mm | 151 mm | 168 mm | 168 mm | |
Depth of the enclosure | 108 mm | 91 mm | 82 mm | 121 mm | 121 mm | |
Installation width | 116 mm | 285 mm | 210 mm | 206 mm | 273 mm | |
Installation height | 126 mm | 171 mm | 171 mm | 188 mm | 188 mm | |
Weight, approx. | 1.8 kg | 3.8 kg | 3.2 kg | 6 kg | 9 kg | |
Installation | snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws | snaps onto DIN rail EN 60715 35x15 or keyhole mounting for hooking in to M4 screws | snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws | can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws) | can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws) | |
Number of cells | 12 | 12 | 12 | 12 | 12 | |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |