Технические данные



Article No.

6EP1 935-6MC01

Product

SITOP Battery module

Product type

Battery module 1.2 Ah

Charging currentcharging voltage

 

End of charging voltage for DC

 

  • at -10 °C recommended

 

  • at 0 °C recommended

 

  • at 10 °C recommended

27,8 V

  • at 20 °C recommended

27,3 V

  • at 30 °C recommended

26,8 V

  • at 40 °C recommended

26,6 V

  • at 50 °C recommended

26,3 V

  • at 60 °C recommended

 

Charging current maximum

0,3 A

Safety

 

Short-circuit protection

Battery fuse 7.5 A/32 V (solid-state circuitry blade-type fuse + support)

Design of the overload protection

Valve control

Safety

 

Protection class

Class III

CE mark

Yes

UL/cUL (CSA) approval

cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627

Degree of protection (EN 60529)

IP00

Operating data

 

  • note

For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.

Ambient temperature

 

  • in operation

-15 … +50 °C

Ambient temperature

 

  • on transport

-20 … +50 °C

  • in storage

-20 … +50 °C

Relative, temporary capacity loss at 20 °C in a month typical

3 %

Service life

 

Service life of lead-acid battery

 

  • typical note

capacity falls to 50 % of original capacity

  • at 20 °C typical

4 a

  • at 30 °C typical

2 a

  • at 40 °C typical

1 a

  • at 50 °C typical

0,5 a

  • at 60 °C typical

 

Ambient temperature during storage note

Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

Mechanics

 

Connection technology

spring-loaded terminals

Design of the electrical connection for power supply unit

1 screw terminal each for 0.08 ... 2.5 mm² for + BATT and - BATT

Product component belonging to

Accessories pack with solid-state circuitry fuse 7.5 A

Width of the housing

96 mm

Height of the housing

106 mm

Depth of the housing

108 mm

Installation width

116 mm

Installation height

126 mm

Weight, approx.

1,8 kg

Installation

snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws

Number of cells

12

Other information

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)