Power output modules Siemens

Дизайн
- Modules enclosed in metal housing
- Connection of the phases via conductor rails
- Connection of the heat emitters by means of mating connectors (the heat emitter and mating connector must be ordered separately.)
- Channel fuses at the front
- Cooling is possible with the optional fan module for LA724I and LA724I HP power output modules, see "Fan module"
- Internal parallel bus interface
- 4 diagnostic LEDs for indicating channel/module faults
Функции
Power switching elements
LA724I and LA724I HP power output modules
- Power triacs with zero crossover switching
- Protection of triacs and opto-triacs against overvoltages by Transil diodes
LA724I SSR power output module
There are no power triacs here. The load is activated via external Solid State Relays (SSR).
Output power
LA724I power output module
- 24 power channels of 230 V each (8 outputs per phase)
- Max. 1 150 W switching capacity per output
- Max. 7 360 W switching capacity per phase
LA724I HP power output module
- 12 power output channels for 230 V/400 V (4 outputs per phase)
- Max. 2 300 W/4 000 W switching capacity per output
- Max. 9 200 W switching capacity per phase for star connection and max. 16 000 W switching capacity for delta connection
LA724I SSR power output module
24 channels with one digital control signal of 24 V (8 outputs per phase)
Forced ventilation
LA724I and LA724I HP power output modules
Depending on the switching capacity and ambient temperature, the power output modules may have to be forced ventilated. A fan module is available as an option for this purpose, see "Fan module".
For detailed information, refer to the "SIPLUS HCS724I Heater Control System" Operating Instructions, http://support.automation.siemens.com/WW/view/en/55336534.
Temperature monitoring
LA724I and LA724I HP power output modules
There is an NTC thermistor on the heat sink for monitoring its temperature. This temperature-dependent resistor outputs a signal to the SIMATIC S7‑300 at 92 °C ± 3 °C. A second switching threshold at 100 °C ± 3 °C switches off the power outputs of the module.
Supply voltage monitoring
LA724I SSR power output module
- The connected 24 V DC supply is monitored for failure. In the event of a failure, the outputs to the Solid State Relay (SSR) are deactivated.
- The drivers for the control outputs are monitored for correct functioning.
Fuses
LA724I power output module
- Each power output has a 5 A fuse in a fuse holder that is accessible from the front to protect the power triac, and one 32 A fuse per phase to limit the phase current.
LA724I HP power output module
- Each power output has a 10 A fuse in a fuse holder that is accessible from the front to protect the power triac, and one 40 A fuse per phase to limit the phase current.
LA716I SSR power output module
Protection for each channel is to be provided externally.
Diagnostics facilities
LA724I and LA724I HP power output modules
Diagnostics functions are provided as standard to detect the following faults:
- Internal fuse defective or triac at high-resistance
- Triac failed
- External fault such as blown fuse, heat emitter or cable breakage
If several heat emitters are connected to one output in parallel, failure of an individual heat emitter is detected by means of extended diagnostics.
LA724I SSR power output module
Two different diagnostics methods are possible:
- Diagnostics of voltages from the load circuit allows the following faults to be detected:
- Solid State Relay (SSR) cannot be closed, supply line to the SSR is interrupted, or external channel fuse has ruptured
- Solid State Relay (SSR) cannot be opened, break in emitter or wiring
- Diagnostics using the external current measuring module (see "Current measuring module") allow the following faults to be detected in addition (these diagnostics are recommended for fault detection in emitters connected in parallel):
- Rated voltage for channel has been exceeded
- Rated voltage for channel has been undershot
Технические данные
Order number |
| 6BK1700-2BA00-0AA0 | 6BK1700-2BA10-0AA0 | 6BK1700-4BA70-0AA0 | |
---|---|---|---|---|---|
Product designation |
| Power module LA724I | - | Power module LA724I HP | |
General technical data: |
|
|
|
| |
Control version / of heat emitters |
| Half-wave control | - | Half-wave control | |
Type of load |
| Ohmic load | Solid State Relay | Ohmic load | |
Supply voltage: |
|
|
|
| |
Type of voltage / of the supply voltage |
| AC | |||
Supply voltage / with AC / Rated value | V | 230 | 400 | ||
| % | 18 | |||
| % | 15 | |||
Supply voltage frequency |
|
|
|
| |
| Hz | 50 | - | 50 | |
| Hz | 60 | - | 60 | |
Relative symmetrical tolerance / of the supply voltage frequency | % | 5 | - | 5 | |
Switching capacity current |
|
|
|
| |
| A | 120 | |||
| A | 32 | - | 40 | |
Design of the electrical isolation |
| Optocoupler between main circuit and SELV/PELV | |||
Power capacity / of the module |
|
|
|
| |
|
|
|
|
| |
| kW | NO_DATA | - | 36.5 | |
| kW | NO_DATA | - | 22.6 | |
|
|
|
|
| |
| kW | 22 | - | 21 | |
| kW | 14.4 | - | 13 | |
Power capacity / maximum permissible | kW | 22 | - | 48 | |
Type of electrical connection / for supply voltage |
| Bus bar or ring cable lug | |||
Power Electronics: |
|
|
|
| |
Number of outputs / for heating power |
| 24 | - | 12 | |
Number of heat emitters / per output / maximum |
| 5 | - | 5 | |
Output voltage |
|
|
|
| |
| V | 230 | - | 230 | |
| V | NO_DATA | - | 400 | |
Design of the overvoltage protection |
| Transil diodes | - | Transil diodes | |
Power capacity / per output |
|
|
|
| |
| W | 1 150 | - | 4 000 | |
| W | 75 | - | 75 | |
Output current / at output / for heating power / Rated value | A | 5 | - | 10 | |
Design of short-circuit protection / for heating power / per output |
| Fuse 5 A | - | Fuse 16 A | |
Galvanic isolation / between the outputs |
| No | - | No | |
Type of electrical connection / at output / for heating and fan |
| Socket strip, 8-pole | - | Socket strip, 8-pole | |
Type of connectable conductor cross-section |
|
|
|
| |
|
|
|
|
| |
|
| 1x (0.2 ... 1.5 mm²) | |||
|
| 1x (0.2 ... 1.5 mm²) | - | 1x (0.2 ... 1.5 mm²) | |
|
| 28 ... 16 | - | 28 ... 16 | |
Inputs/ Outputs: |
|
|
|
| |
Control supply voltage / for DC / Rated value / minimum | V | - | 20.4 | - | |
Type of electrical connection / for control supply voltage |
| - | 2-pin connector | - | |
Type of connectable conductor cross-section |
|
|
|
| |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
|
| - | 28 ... 14 | - | |
Number of semiconductor outputs |
| - | 24 | - | |
Type of switching output |
| - | semiconductor output (high side switch) | - | |
Type of voltage / of output voltages |
| - | DC | - | |
Output voltage / for DC / Rated value | V | - | 24 | - | |
Output voltage |
|
|
|
| |
| V | - | 28.8 | - | |
| V | - | 18.4 | - | |
Output current / at digital output / for signal <1> / maximum | A | - | 0.05 | - | |
Galvanic isolation / between the outputs and system interface |
| - | No | - | |
Switching behavior |
| - | monostable | - | |
Property of the output / Short-circuit proof |
| - | Yes | - | |
Type of electrical connection / at the digital outputs |
| - | 8-pin connector | - | |
Type of connectable conductor cross-section |
|
|
|
| |
|
|
|
|
| |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
|
| - | 28 ... 16 | - | |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
Type of electrical connection / at the measurement inputs for current |
| Internal | externally via 6-pin connector for SM724I | Internal | |
Type of connectable conductor cross-section / at the measurement inputs for current |
|
|
|
| |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
|
| - | 28 ... 14 | - | |
Diagnostics voltage |
|
|
|
| |
| V | - | 230 | - | |
| V | - | 400 | - | |
Type of electrical connection / at the measurement inputs for voltage |
| - | Socket strip, 8-pole | - | |
Type of connectable conductor cross-section / at the measurement inputs for voltage |
|
|
|
| |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
|
| - | 1x (0.2 ... 1.5 mm²) | - | |
|
| - | 28 ... 16 | - | |
Installation/ mounting/ dimensions: |
|
|
|
| |
Width | mm | 50 | |||
Height | mm | 480 | |||
Depth | mm | 210 | |||
Further information: |
|
|
|
| |
Number of status displays |
| 4 | |||
Display version / as status display by LED |
| 1 LED green = LA status indicator, 3 LEDs red = fault indicator LA per phase | |||
Design of the power supply |
| Power supply via central connection | |||
Product function / Temperature monitoring |
| Yes | - | Yes | |
Type of the temperature monitoring |
| NTC thermistor | - | NTC thermistor | |
Diagnostics function |
|
|
|
| |
|
| Yes | |||
|
| Yes | |||
|
| Yes |
Дополнительно
Design | for power output module | Type |
---|---|---|
Mating connectors | ||
| LA724I, LA724I HP | 40018384 |
| LA724I SSR | A5E00210675 |
| LA724I SSR | A5E00043661 |
| LA724I SSR | A5E00210670 |
| LA724I SSR | 41818384 |
Data link | ||
| LA724I | 200021116 |
| LA724I HP | A5E01204540 |
Recommended Solid State Relay (SSR)
SIRIUS SC semiconductor relay/contactor,
e.g. 3RF2350‑1AA02:
semiconductor contactor 50 A,
40 °C,
control voltage 24 V,
screw connection