Output reactors Siemens

Обзор
Output reactor for PM230 Power Modules, frame size FSA
Output reactors reduce the rate of voltage rise (dv/dt) and the height of the current peaks, and enable longer motor cables to be connected.
Owing to the high rates of voltage rise of the fast-switching IGBTs, the capacitance of long motor cables reverses polarity very quickly with every switching operation in the inverter. As a result, the inverter is loaded with additional current peaks of substantial magnitude.
Output reactors reduce the magnitude of these additional peaks because the cable capacitance reverses polarity more slowly across the reactor inductance, thereby attenuating the amplitudes of the current peaks.
When using output reactors, the following should be observed:
- Max. permissible output frequency 200 Hz
- Max. permissible pulse frequency 4 kHz
- The output reactor must be installed as close as possible to the Power Module
Интеграция
Output reactors that are optionally available depending on the Power Module used
The following load-side power components are optionally available in the appropriate frames sizes for the Power Modules:
| Frame size | |||||
---|---|---|---|---|---|---|
| FSA | FSB | FSC | FSD | FSE | FSF |
PM230 Power Module degree of protection IP20 or IP55/UL Type 12 | ||||||
Available frame sizes | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Load-side power components | ||||||
Output reactor | S | S | S | S | S | S |
S = Lateral mounting
– = Not possible
Технические данные
Line voltage 380 ... 480 V 3 AC | Output reactor | ||||
---|---|---|---|---|---|
| 6SL3202-0AE16-1CA0 | 6SL3202-0AE18-8CA0 | 6SL3202-0AE21-8CA0 | 6SL3202-0AE23-8CA0 | |
Rated current | A | 6.1 | 9 | 18.5 | 39 |
Power loss | kW | 0.09 | 0.08 | 0.08 | 0.11 |
Connection to the Power Module/motor connection |
| Screw terminals | Screw terminals | Screw terminals | Screw terminals |
| mm2 | 4 | 4 | 10 | 16 |
PE connection |
| M4 screw stud | M4 screw stud | M5 screw stud | M5 screw stud |
Cable length, max. between output reactor and motor |
|
|
|
|
|
|
|
|
|
|
|
| m (ft) | 150 (492.15) | 150 (492.15) | 150 (492.15) | 150 (492.15) |
| m (ft) | 225 (738.23) | 225 (738.23) | 225 (738.23) | 225 (738.23) |
|
|
|
|
|
|
| m (ft) | 100 (328.10) | 100 (328.10) | 100 (328.10) | 100 (328.10) |
| m (ft) | 150 (492.15) | 150 (492.15) | 150 (492.15) | 150 (492.15) |
Dimensions |
|
|
|
|
|
| mm (in) | 207 (8.15) | 207 (8.15) | 247 (9.72) | 257 (10.12) |
| mm (in) | 175 (6.89) | 180 (7.09) | 215 (8.46) | 235 (9.25) |
| mm (in) | 72.5 (2.85) | 72.5 (2.85) | 100 (3.94) | 114.7 (4.52) |
Possible as base component |
| No | No | No | No |
Degree of protection |
| Control cabinet built-in unit IP20 | Control cabinet built-in unit IP20 | Control cabinet built-in unit IP20 | Control cabinet built-in unit IP20 |
Weight, approx. | kg (lb) | 3.4 (7.50) | 3.9 (8.60) | 10.1 (22.3) | 11.2 (24.7) |
Suitable for | Type | 6SL3210-1NE11-3 . L1 6SL3210-1NE11-7 . L1 6SL3210-1NE12-2 . L1 6SL3210-1NE13-1 . L1 6SL3210-1NE14-1 . L1 6SL3210-1NE15-8 . L1 | 6SL3210-1NE17-7 . L1 | 6SL3210-1NE21-0 . L1 6SL3210-1NE21-3 . L1 6SL3210-1NE21-8 . L1 | 6SL3210-1NE22-6 . L1 6SL3210-1NE23-2 . L1 6SL3210-1NE23-8 . L1 |
Suitable for | Type | - | 6SL3211-1NE17-7 . L1 | 6SL3211-1NE21-8 . L1 | 6SL3211-1NE23-8 . L1 |
Suitable for | Type | 6SL3223-0DE13-7 . A1 6SL3223-0DE15-5 . A1 6SL3223-0DE17-5 . A1 6SL3223-0DE21-1 . A1 6SL3223-0DE21-5 . A1 6SL3223-0DE22-2 . A1 | 6SL3223-0DE23-0 . A1 | 6SL3223-0DE24-0 . A1 6SL3223-0DE25-5 . A1 6SL3223-0DE27-5 . A1 | 6SL3223-0DE31-1 . A1 6SL3223-0DE31-5 . A1 6SL3223-0DE31-8AA1 FSC
6SL3223-0DE31-8BA0 FSD |
|
| FSA | FSA | FSB | FSC/FSD |
Line voltage 380 ... 480 V 3 AC | Output reactor | ||||
---|---|---|---|---|---|
| 6SE6400-3TC03-8DD0 | 6SE6400-3TC05-4DD0 | 6SE6400-3TC08-0ED0 | 6SE6400-3TC07-5ED0 | |
Rated current | A | 45 1) | 68 1) | 104 1) | 90 1) |
Power loss | kW | 0.2 | 0.2 | 0.17 | 0.27 |
Connection to the Power Module |
| Flat connector for M6 cable lug | Flat connector for M6 cable lug | Flat connector for M6 cable lug | Flat connector for M6 cable lug |
Motor connection |
| Flat connector for M6 cable lug | Flat connector for M6 cable lug | Flat connector for M6 cable lug | Flat connector for M6 cable lug |
PE connection |
| M6 screw | M6 screw | M6 screw | M6 screw |
Cable length, max. between output reactor and motor |
|
|
|
|
|
|
|
|
|
|
|
| m (ft) | 200 (656.20) | 200 (656.20) | 200 (656.20) | 200 (656.20) |
| m (ft) | 300 (984.30) | 300 (984.30) | 300 (984.30) | 300 (984.30) |
Dimensions |
|
|
|
|
|
| mm (in) | 225 (8.86) | 225 (8.86) | 225 (8.86) | 270 (10.63) |
| mm (in) | 210 (8.27) | 210 (8.27) | 210 (8.27) | 248 (9.76) |
| mm (in) | 179 (7.05) | 150 (492.15) | 150 (492.15) | 209 (8.23) |
Possible as base component |
| No | No | No | No |
Degree of protection |
| IP00 | IP00 | IP00 | IP00 |
Weight, approx. | kg (lb) | 16.1 (35.5) | 10.7 (23.6) | 10.4 (22.9) | 24.9 (54.9) |
Suitable for | Type | 6SL3210-1NE24-5UL0 6SL3210-1NE24-5AL0 | 6SL3210-1NE26-0UL0 6SL3210-1NE26-0AL0 | 6SL3210-1NE27-5UL0 6SL3210-1NE27-5AL0 | 6SL3210-1NE28-8UL0 6SL3210-1NE28-8AL0 |
Suitable for | Type | 6SL3223-0DE32-2UA0 6SL3223-0DE32-2AA0 | 6SL3223-0DE33-0UA0 6SL3223-0DE33-0AA0 | 6SL3223-0DE33-7UA0 6SL3223-0DE33-7AA0 | 6SL3223-0DE34-5UA0 6SL3223-0DE34-5AA0 |
| kW (hp) | 22 (29.5) | 30 (40.2) | 37 (49.6) | 45 (60.3) |
| A | 45 | 60 | 75 | 90 |
|
| FSD | FSD | FSE | FSE |
1) On the rating plate of the reactor the current is specified according to the duty cycle for high overload (HO). This is lower than the current specified according to the duty cycle for low overload (LO) of the Power Module.
Line voltage 380 ... 480 V 3 AC | Output reactor | |||
---|---|---|---|---|
| 6SE6400-3TC14-5FD0 | 6SE6400-3TC15-4FD0 | 6SE6400-3TC14-5FD0 | |
Rated current | A | 178 1) | 178 1) | 178 1) |
Power loss | kW | 0.47 | 0.25 | 0.47 |
Connection to the Power Module |
| Flat connector for M8 cable lug | Flat connector for M8 cable lug | Flat connector for M8 cable lug |
Motor connection |
| Flat connector for M8 cable lug | Flat connector for M8 cable lug | Flat connector for M8 cable lug |
PE connection |
| M8 screw | M6 screw | M8 screw |
Cable length, max. between output reactor and motor |
|
|
|
|
|
|
|
|
|
| m (ft) | 200 (656.20) | 200 (656.20) | 200 (656.20) |
| m (ft) | 300 (984.30) | 300 (984.30) | 300 (984.30) |
Dimensions |
|
|
|
|
| mm (in) | 350 (13.78) | 270 (10.63) | 350 (13.78) |
| mm (in) | 321 (12.64) | 248 (9.76) | 321 (12.64) |
| mm (in) | 288 (11.34) | 209 (8.23) | 288 (11.34) |
Possible as base component |
| No | No | No |
Degree of protection |
| IP00 | IP00 | IP00 |
Weight, approx. | kg (lb) | 51.5 (114) | 24 (52.9) | 51.5 (114) |
Suitable for | Type | 6SL3210-1NE31-1UL0 6SL3210-1NE31-1AL0 | 6SL3210-1NE31-5UL0 6SL3210-1NE31-5AL0 | – |
Suitable for | Type | 6SL3223-0DE35-5UA0 6SL3223-0DE35-5AA0 | 6SL3223-0DE37-5UA0 6SL3223-0DE37-5AA0 | 6SL3223-0DE38-8UA0 6SL3223-0DE38-8AA0 |
| kW (hp) | 55 (73.8) | 75 (101) | 90 (121) |
| A | 110 | 145 | 178 |
|
| FSF | FSF | FSF |
1) On the rating plate of the reactor the current is specified according to the duty cycle for high overload (HO). This is lower than the current specified according to the duty cycle for low overload (LO) of the Power Module.