Braking resistors Siemens

Обзор
Braking resistor
Excess energy in the DC link is dissipated in the braking resistor. The braking resistors are intended for use with PM240 Power Modules which feature an integrated braking chopper, but cannot regenerate energy to the supply system. For regenerative operation, e.g. the braking of a rotating mass with high moment of inertia, a braking resistor must be connected to convert the resulting energy into heat.
The braking resistors can be installed at the side next to the PM240 Power Modules.
The braking resistors for the Power Modules of frame size FSF should be placed outside the control cabinet or outside the switchgear room so that the heat loss is removed from the area of the Power Modules. The level of air conditioning required is therefore reduced.
Every braking resistor has a temperature switch (UL-listed). The temperature switch must be evaluated to prevent consequential damage if the braking resistor overheats.
Интеграция
Available optional braking resistors
| Frame size |
---|---|
| FSF |
PM240 Power Module with integrated braking chopper | |
DC link components | |
Braking resistor | S |
S = Lateral mounting
Технические данные
Line voltage 380 V ... 480 V 3 AC | Braking resistor | ||
---|---|---|---|
| 6SE6400-4BD24-0FA0 | 6SE6400-4BD26-0FA0 | |
Resistance | Ω | 8.2 | 5.5 |
Rated power PDB (continuous breaking power) | kW (hp) | 4 | 5.6 |
Peak power Pmax (load duration ta = 12 s for cycle time t 12 s) | kW (hp) | 80 | 120 |
Power connections |
| M6 screw studs | M6 screw studs |
Thermostatic switch |
| NC contact | NC contact |
|
| 250 V AC/2.5 A | 250 V AC/2.5 A |
Degree of protection |
| IP20 | IP20 |
Frame size |
| FSF | FSF |
Dimensions |
|
|
|
| mm (in) | 395 | 526 |
| mm (in) | 650 | 301 |
| mm (in) | 315 | 484 |
Weight, approx. | kg (lb) | 16.7 | 17.5 |
Suitable for | Type | 6SL3224-0BE37-5UA0 | 6SL3224-0BE38-8UA0 |
|
| FSF | FSF |