Sine-wave filters Siemens

Обзор



Sine-wave filter

Sine-wave filters limit the the rate of voltage rise (dv/dt) and the peak voltages on the motor winding. Similar to an output reactor, they enable the connection of longer motor cables.

Bearing currents are also reduced significantly. Using these filters therefore allows standard motors with standard insulation and without insulated bearings to be operated on SINAMICS. As a result, the voltage load on the motor winding is virtually identical to the load on windings of directly mains-fed motors.

Owing to the very low rates of voltage rise on the motor cable, the sine-wave filter also has a positive impact in terms of electromagnetic compatibility which means that it is not absolutely essential to use shielded cables for short motor cables to achieve the required standard of EMC.

Since the voltage applied to the motor is not pulsed, the inverter-related stray losses and additional noise in the motor are also reduced considerably and the noise level of the motor is similar to the level produced by directly mains-fed motors.

When using sine-wave filters, the following should be observed:

  • Pulse frequencies of between 4 kHz and 8 kHz are permissible for rated outputs up to and including 90 kW
  • Only a pulse frequency of 4 kHz is permissible for rated outputs of 110 kW and higher. Note additional current derating as compared with rated pulse frequency of 2 kHz (see derating data)
  • The output frequency is limited to 150 Hz.
  • Operation and commissioning may only be performed with the motor connected as the sine-wave filter is not no-load proof
  • It must be ensured that the automatic pulse frequency reduction functions are also deactivated
  • A derating of 5 % must be observed when the appropriate PM240 Power Module is selected 

Интеграция



Available optional sine-wave filters

 

Frame size

 

FSF

PM240 Power Module with integrated braking chopper

Load-side power components

Sine-wave filter

S



S = Lateral mounting

Технические данные



Line voltage 380 ... 480 V 3 AC

Sine-wave filter (for pulse frequencies 4 ... 8 kHz, only 4 kHz permissible at 110 kW and above – note additional current derating as compared with rated pulse frequency of 2 kHz, see derating data)

 

6SL3202-0AE31-8SA0

6SL3000-2CE32-3AA0

Rated current

A

182

225

225

Power loss

kW (hp)

0.47

0.221

0.221

Connection to the Power Module

 

Screw terminals

1 x hole for M10

1 x hole for M10

  • Conductor cross-section

mm2

150

  

Motor connection

 

Screw terminals

1 x hole for M10

1 x hole for M10

  • Conductor cross-section

mm2

150

  

PE connection

 

M8 screw

1 x hole for M10

1 x hole for M10

Cable length, max.

between sine-wave filter and motor

 

 

 

 

  • 380 ... 480 V ±10 % 3 AC

 

 

 

 

  • Shielded

m (ft)

200

300

300

  • Unshielded

m (ft)

300

450

450

Dimensions

 

 

 

 

  • Width

mm (in)

350

620

620

  • Height

mm (in)

468

300

300

  • Depth

mm (in)

305

320

320

Degree of protection

 

IP00

IP00

IP00

Weight, approx.

kg (lb)

80.0

124

124

Suitable for
PM240 Power Module

Type

6SL3224-0BE37-5UA0

6SL3224-0BE37-5AA0

6SL3224-0BE38-8UA0

6SL3224-0BE41-1UA0

  • Rated power of the Power Module

kW (hp)

90

110

132

  • Rated current Irated of the Power Module

A

178

205

250

  • Frame size

 

FSF

FSF

FSF