Стандартный шинный держатель для горизонтальной установки Siemens

Обзор
- Installation and arrangement on the rear panel, minimum cabinet depth 600 mm
- Rated current of busbars at +35 °C ambient temperature, observe reduction factor, acc. to DIN 43671
- Cross-arms must be ordered separately
Технические данные
Rated current | Rated short-time current Icw (1 s) kA/ rated peak withstand current Ipk kA | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
max. clearance between two busbar holders (in mm) | |||||||||||||
A | 10/20 | 15/30 | 20/40 | 30/63 | 40/84 | 50/105 | 55/121 | 60/132 | 65/143 | 70/154 | 80/176 | 100/220 | |
3-pole | |||||||||||||
800 | 1200 | 800 | 600 | 375 | 275 | – | – | – | – | – | – | – | |
1250 | – | – | – | 500 | 375 | 300 | 260 | 235 | 225 | – | – | – | |
1600 | – | – | – | 460 | 340 | 260 | 240 | 220 | 200 | – | – | – | |
4-pole | |||||||||||||
800 | 1200 | 800 | 600 | 375 | 275 | – | – | – | – | – | – | – | |
1250 | – | – | – | 500 | 375 | 300 | 260 | 235 | 225 | – | – | – | |
1600 | – | – | – | 460 | 340 | 260 | 240 | 220 | 200 | – | – | – |
Дополнительно
Cross-arms for standard busbar holders incl. fixing material (1 set= 2 items)
Note:
The standard busbar support is designed for increased busbar temperatures up to +85 °C. This means that the cross-section may be reduced at the same rated current level. Please observe Cu dimensions and rated current.