Line filters Siemens

Обзор



In plants with strict EMC requirements, line filters work together with line reactors to restrict the conducted interference emanating from the Power Modules to the limit values of Class A1 as defined in EN 55011 and Category C2 as defined in EN 61800‑3. Line filters are suited only for direct connection to TN-systems.

Технические данные



Line voltage 380 ... 480 V 3 AC

Line filter

 

6SL3000-0HE15-0AA0

6SL3000-0HE21-0AA0

6SL3000-0BE21-6DA0

6SL3000-0BE23-6DA1

6SL3000-0BE25-5DA0

Rated current

A

12

25

36

74

105

Power loss

kW

0.02

0.02

0.016

0.026

0.043

Line/load connection

L1, L2, L3 / U, V, W

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

10

10

10

35

50

PE connection

 

M6 screw studs according to DIN 46234

M6 screw studs according to DIN 46234

M6 screw studs according to DIN 46234

M6 screw studs according to DIN 46234

M6 screw studs according to DIN 46234

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

60 (2.36)

60 (2.36)

50 (1.97)

75 (2.95)

100 (3.94)

  • Height

mm (in)

285 (11.22)

285 (11.22)

420 (16.54)

433 (17.05)

466 (18.35)

  • Depth

mm (in)

122 (4.80)

122 (4.80)

226 (8.90)

226 (8.90)

226 (8.90)

Weight, approx.

kg (lb)

2.1 (4.63)

2.3 (5.07)

5 (11.0)

7.5 (16.5)

11.5 (25.4)

Approvals, according to

 

cURus

cURus

cURus

cURus

cURus

Suitable for Smart Line Module in booksize or booksize compact format

Type

6SL3130-6AE15-0AB1

6SL3131-6AE15-0AA1

6SL3136-6AE15-0AA1

6SL3130-6AE21-0AB1

6SL3131-6AE21-0AA1

6SL3136-6AE21-0AA1

6SL3130-6TE21-6AA4

6SL3131-6TE21-6AA3

6SL3430-6TE21-6AA1

6SL3130-6TE23-6AA3

6SL3131-6TE23-6AA3

6SL3130-6TE25-5AA3

6SL3131-6TE25-5AA3

  • Rated power of the Smart Line Module

kW

5

10

16

36

55