Line filters Siemens
Обзор
In plants with strict EMC requirements, line filters work together with line reactors to restrict the conducted interference emanating from the Power Modules to the limit values of Class A1 as defined in EN 55011 and Category C2 as defined in EN 61800‑3. Line filters are suited only for direct connection to TN-systems.
Технические данные
Line voltage 380 ... 480 V 3 AC | Line filter | |||||
---|---|---|---|---|---|---|
| 6SL3000-0HE15-0AA0 | 6SL3000-0HE21-0AA0 | 6SL3000-0BE21-6DA0 | 6SL3000-0BE23-6DA1 | 6SL3000-0BE25-5DA0 | |
Rated current | A | 12 | 25 | 36 | 74 | 105 |
Power loss | kW | 0.02 | 0.02 | 0.016 | 0.026 | 0.043 |
Line/load connection L1, L2, L3 / U, V, W |
| Screw-type terminals | Screw-type terminals | Screw-type terminals | Screw-type terminals | Screw-type terminals |
| mm2 | 10 | 10 | 10 | 35 | 50 |
PE connection |
| M6 screw studs according to DIN 46234 | M6 screw studs according to DIN 46234 | M6 screw studs according to DIN 46234 | M6 screw studs according to DIN 46234 | M6 screw studs according to DIN 46234 |
Degree of protection |
| IP20 | IP20 | IP20 | IP20 | IP20 |
Dimensions |
|
|
|
|
|
|
| mm (in) | 60 (2.36) | 60 (2.36) | 50 (1.97) | 75 (2.95) | 100 (3.94) |
| mm (in) | 285 (11.22) | 285 (11.22) | 420 (16.54) | 433 (17.05) | 466 (18.35) |
| mm (in) | 122 (4.80) | 122 (4.80) | 226 (8.90) | 226 (8.90) | 226 (8.90) |
Weight, approx. | kg (lb) | 2.1 (4.63) | 2.3 (5.07) | 5 (11.0) | 7.5 (16.5) | 11.5 (25.4) |
Approvals, according to |
| cURus | cURus | cURus | cURus | cURus |
Suitable for Smart Line Module in booksize or booksize compact format | Type | 6SL3130-6AE15-0AB1 6SL3131-6AE15-0AA1 6SL3136-6AE15-0AA1 | 6SL3130-6AE21-0AB1 6SL3131-6AE21-0AA1 6SL3136-6AE21-0AA1 | 6SL3130-6TE21-6AA4 6SL3131-6TE21-6AA3 6SL3430-6TE21-6AA1 | 6SL3130-6TE23-6AA3 6SL3131-6TE23-6AA3 | 6SL3130-6TE25-5AA3 6SL3131-6TE25-5AA3 |
| kW | 5 | 10 | 16 | 36 | 55 |