Технические данные



Line voltage 380 ... 480 V 3 AC

Basic Line Filter

 

6SL3000-0BE21-6DA0

6SL3000-0BE23-6DA1

6SL3000-0BE25-5DA0

6SL3000-0BE28-0DA0

6SL3000-0BE31-2DA0

Rated current

A

36

74

105

132

192

Power loss

kW

0.016

0.02

0.041

0.048

0.086

Line supply/load connection

L1, L2, L3 / U, V, W

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

10

35

50

95

95

PE connection

 

M6 screw studs according to DIN 46234

M6 screw studs according to DIN 46234

M8 screw studs according to DIN 46234

M10 screw studs according to DIN 46234

M10 screw studs according to DIN 46234

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

50 (1.97)

75 (2.95)

100 (3.94)

150 (5.91)

150 (5.91)

  • Height

mm (in)

429 (16.89)

433 (17.05)

466 (18.35)

479 (18.86)

479 (18.86)

  • Depth

mm (in)

226 (8.90)

226 (8.90)

226 (8.90)

226 (8.90)

226 (8.90)

Weight, approx.

kg (lb)

5 (11.0)

7.5 (16.5)

11.5 (25.4)

18.2 (40.1)

18.8 (41.5)

Approvals, according to

 

cURus

cURus

cURus

cURus

cURus

Suitable for Active Line Module in booksize format

Type

6SL3130-7TE21-6AA4

6SL3131-7TE21-6AA3

6SL3136-7TE21-6AA3

6SL3130-7TE23-6AA3

6SL3131-7TE23-6AA3

6SL3136-7TE23-6AA3

6SL3130-7TE25-5AA3

6SL3131-7TE25-5AA3

6SL3136-7TE25-5AA3

6SL3130-7TE28-0AA3

6SL3131-7TE28-0AA3

6SL3136-7TE28-0AA3

6SL3130-7TE31-2AA3

6SL3131-7TE31-2AA3

6SL3136-7TE31-2AA3

6SL3135-7TE31-2AA3

  • Rated power of the Active Line Module

kW

16

36

55

80

120