Recommended line-side components Siemens
Обзор
Suitable line-side power components are assigned depending on the power rating of the Basic Line Module.
The tables below list recommended components.
Further information about the line contactors, switch disconnectors, fuses and circuit breakers specified in the tables can be found in Catalogs LV 10.1 and IC 10.
Assignment of line-side power components to Basic Line Modules in booksize format
Rated power | Assignment to Basic Line Module in booksize format | Line contactor | Output coupling device for line contactor | Main switch |
---|---|---|---|---|
kW (HP) | Types 6SL3130- and 6SL3136- | Type | Order No. | Order No. |
Line voltage 380 ... 480 V 3 AC | ||||
20 (25) | 1TE22‑0AA0 | 3RT1035-… | 3TX7004-1LB00 | 3LD2504-0TK51 |
40 (50) | 1TE24‑0AA0 | 3RT1045-… | 3TX7004-1LB00 | 3LD2704-0TK51 |
100 (125) | 1TE31‑0AA0 | 3RT1056-… | 3TX7004-1LB00 | 3KA5530-1GE01 |
Rated power | Assignment to Basic Line Module in booksize format | Circuit breaker IEC 60947 | Circuit breaker UL489/CSA C22.2 No. 5-02 | Fuse switch disconnector |
---|---|---|---|---|
kW (HP) | Types 6SL3130- and 6SL3136- | Order No. | Order No. | Order No. |
Line voltage 380 ... 480 V 3 AC | ||||
20 (25) | 1TE22-0AA0 | 3RV1041-4JA10 | 3VL2106-2KN30-... | 3NP1123-1CA20 |
40 (50) | 1TE24-0AA0 | 3VL2710-1DC33-... | 3VL2110-2KN30-... | 3NP1123-1CA20 |
100 (125) | 1TE31-0AA0 | 3VL3725-1DC36-... | 3VL3125-2KN30-... | 3NP1143-1DA20 |
Rated power | Assignment to Basic Line Module in booksize format | Switch disconnector with fuse holders | LV HRC fuse | UL/CSA fuse, Class J 1) Available from: Mersen | ||||
---|---|---|---|---|---|---|---|---|
kW (HP) | Types 6SL3130- and 6SL3136- | Order No. | Rated current | Size | Order No. | Rated current | Size mm | Reference No. |
Line voltage 380 ... 480 V 3 AC | ||||||||
20 (25) | 1TE22-0AA0 | 3KL5230-1GB01 | 63 A | 000 | 3NA3822 | 60 A | 27 × 60 | AJT60 |
40 (50) | 1TE24-0AA0 | 3KL5230-1GB01 | 100 A | 000 | 3NA3830 | 100 A | 29 × 117 | AJT100 |
100 (125) | 1TE31-0AA0 | 3KL5730-1GB01 | 250 A | 1 | 3NA3144 | 250 A | 54 × 181 | AJT250 |
1) Not suitable for 3NP and 3KL switch disconnectors.