Active Line Modules Siemens
Обзор
A wide range of single-axis Line Modules and Motor Modules with graded current/power ratings can be supplied:
- Active Line Modules: Single-axis version
In chassis format with rated power from 132 kW to 300 kW - Single Motor Modules: Single-axis version
In chassis format with rated output currents of 210 A to 490 A
In principle, all Single Motor Modules can operate on Active Line Modules for the corresponding voltage range.
The self-commutated rectifier/regenerative units (with IGBTs in rectifier and regenerative directions) generate a regulated DC link voltage. This means that the connected Motor Modules are decoupled from the line voltage. Line voltage fluctuations within the permissible supply tolerances have no effect on the motor voltage.
If required, the Active Line Modules can also provide reactive power compensation.
Active Line Modules are designed for connection to grounded, star (TN, TT) and non-grounded, symmetrical IT supply systems.
In order to operate an Active Line Module, it is absolutely essential to use the appropriate Active Interface Module.
Дизайн
The Active Line Modules in chassis format feature the following interfaces as standard:
- 1 line connection
- 1 connection for the 24 V DC electronic power supply
- 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
- 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
- 3 DRIVE‑CLiQ sockets
- 2 PE/protective conductor connections
The status of the Active Line Modules is indicated via two multi-color LEDs.
The scope of supply of the Active Line Modules includes:
- Frame sizes FX and GX:
- 0.60 m (1.97 ft) DRIVE‑CLiQ cable for connection to the CU320 Control Unit or SINUMERIK NCU
Характеристика
Overload capability
High overload
Derating characteristics
Current derating as a function of the ambient temperature
Note: A derating factor kT > 1.0 is applicable only in conjunction with "current derating as a function of installation altitude". The rated current data may not be exceeded. For further information see System description.
Current derating as a function of the installation altitude
Voltage derating as a function of installation altitude
Интеграция
The Active Line Module receives its control information via DRIVE-CLiQ from:
- CU320 Control Unit
- SINUMERIK 840D sl with
- NCU 710.3 PN
- NCU 720.3 PN
- NCU 730.3 PN
- Numeric Control Extensions NX10.3/NX15.3
Технические данные
Product name | Active Line Modules in chassis format |
---|---|
6SL3330-7TE3... | |
Line supply voltage Up to 2000 m (6562 ft) above sea level | 380 ... 480 V 3 AC ±10% (-15% < 1 min) |
Line frequency | 47 … 63 Hz |
Line power factor |
|
| 1.0 (factory setting) |
| 1.0 (factory setting) |
Overvoltage category According to EN 60664‑1 | Class III |
DC link voltage Vd | The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage. Factory setting for DC link voltage: 1.5 × line voltage |
Electronic power supply | 24 V DC, -15 %/+20 % |
Radio interference suppression |
|
| Category C3 according to EN 61800‑3 |
Cooling method | Increased air cooling by means of built-in fan |
Permissible ambient or coolant temperature (air) In operation for line-side components, Line Modules and Motor Modules | 0 … 40 °C (32 … 104 °F) without derating, |
Installation altitude | Up to 2000 m (6562 ft) above sea level without derating, |
Declarations of conformity | CE (Low Voltage and EMC Directives) |
Approvals, according to | cULus |
Line supply voltage 380 … 480 V 3 AC | Active Line Module in chassis format | ||||
---|---|---|---|---|---|
6SL3330‑... | 7TE32-1AA3 | 7TE32-6AA3 | 7TE33-8AA3 | 7TE35-0AA3 | |
Infeed/regenerative feedback power |
|
|
|
|
|
| |||||
| kW | 132 | 160 | 235 | 300 |
| (HP) | (200) | (225) | (350) | (450) |
| kW | 198 | 240 | 352,5 | 450 |
DC link current |
|
|
|
|
|
| A | 235 | 291 | 425 | 549 |
| A | 209 | 259 | 378 | 489 |
| A | 352 | 436 | 637 | 823 |
Input current |
|
|
|
|
|
| A | 210 | 260 | 380 | 490 |
| A | 315 | 390 | 570 | 735 |
Current requirement |
|
|
|
|
|
| A | 1.1 | 1.1 | 1.35 | 1.35 |
| A | 0.63/0.95 | 1.13/1.7 | 1.8/2.7 | 1.8/2.7 |
DC link capacitance | µF | 4200 | 5200 | 7800 | 9600 |
Power loss, max. | kW | 2.3 | 2.9 | 4.2 | 5.1 |
Cooling air requirement | m3/s (ft3/s) | 0.17 (6.0) | 0.23 (8.1) | 0.36 (12.7) | 0.36 (12.7) |
Sound pressure level LpA (1 m) 1) | dB | 74/76 | 75/77 | 76/78 | 76/78 |
Line connection U1, V1, W1 |
| Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw |
| mm2 | 2 × 185 | 2 × 185 | 2 × 185 | 2 × 185 |
DC link connection DCP, DCN |
| Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw |
| mm2 | 2 × 185 | 2 × 185 | 2 × 185 | 2 × 185 |
PE connection |
| M10 screw | M10 screw | M10 screw | M10 screw |
|
|
|
|
|
|
| mm2 | 1 × 185 | 1 × 185 | 1 × 185 | 1 × 185 |
| mm2 | 2 × 185 | 2 × 185 | 2 × 185 | 2 × 185 |
Cable length, max. Total of all motor cables and DC link |
|
|
|
|
|
| m (ft) | 2700 (8859) | 2700 (8859) | 2700 (8859) | 2700 (8859) |
| m (ft) | 4050 (13288) | 4050 (13288) | 4050 (13288) | 4050 (13288) |
Degree of protection |
| IP20 | IP20 | IP20 | IP20 |
Dimensions |
|
|
|
|
|
| mm (in) | 326 (12.83) | 326 (12.83) | 326 (12.83) | 326 (12.83) |
| mm (in) | 1400 (55.12) | 1400 (55.12) | 1533 (60.35) | 1533 (60.35) |
| mm (in) | 356 (14.02) | 356 (14.02) | 543 (21.38) | 543 (21.38) |
Frame size |
| FX | FX | GX | GX |
Weight, approx. | kg (lb) | 88 (194) | 88 (194) | 152 (335) | 152 (335) |
1) Total sound pressure level of Active Interface Module and Active Line Module.
2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be dimensioned accordingly.