Active Line Modules Siemens

Обзор



A wide range of single-axis Line Modules and Motor Modules with graded current/power ratings can be supplied:

  • Active Line Modules: Single-axis version
    In chassis format with rated power from 132 kW to 300 kW
  • Single Motor Modules: Single-axis version
    In chassis format with rated output currents of 210 A to 490 A

In principle, all Single Motor Modules can operate on Active Line Modules for the corresponding voltage range.

The self-commutated rectifier/regenerative units (with IGBTs in rectifier and regenerative directions) generate a regulated DC link voltage. This means that the connected Motor Modules are decoupled from the line voltage. Line voltage fluctuations within the permissible supply tolerances have no effect on the motor voltage.

If required, the Active Line Modules can also provide reactive power compensation.

Active Line Modules are designed for connection to grounded, star (TN, TT) and non-grounded, symmetrical IT supply systems.

In order to operate an Active Line Module, it is absolutely essential to use the appropriate Active Interface Module.

Дизайн



The Active Line Modules in chassis format feature the following interfaces as standard:

  • 1 line connection
  • 1 connection for the 24 V DC electronic power supply
  • 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
  • 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
  • 3 DRIVE‑CLiQ sockets
  • 2 PE/protective conductor connections

The status of the Active Line Modules is indicated via two multi-color LEDs.

The scope of supply of the Active Line Modules includes:

  • Frame sizes FX and GX:
    • 0.60 m (1.97 ft) DRIVE‑CLiQ cable for connection to the CU320 Control Unit or SINUMERIK NCU

Характеристика



Overload capability

High overload

Derating characteristics

Current derating as a function of the ambient temperature

Note: A derating factor kT > 1.0 is applicable only in conjunction with "current derating as a function of installation altitude". The rated current data may not be exceeded. For further information see System description.

Current derating as a function of the installation altitude

Voltage derating as a function of installation altitude

Интеграция



The Active Line Module receives its control information via DRIVE-CLiQ from:

  • CU320 Control Unit
  • SINUMERIK 840D sl with
    • NCU 710.3 PN
    • NCU 720.3 PN
    • NCU 730.3 PN
    • Numeric Control Extensions NX10.3/NX15.3

Технические данные



Product name

Active Line Modules in chassis format

 

6SL3330-7TE3...

Line supply voltage

Up to 2000 m (6562 ft) above sea level

380 ... 480 V 3 AC ±10% (-15% < 1 min)

Line frequency

47 … 63 Hz

Line power factor

 

  • Fundamental component (cos φ1)

1.0 (factory setting)
can be altered by input of a reactive current setpoint

  • Total (λ)

1.0 (factory setting)

Overvoltage category

According to EN 60664‑1

Class III

DC link voltage Vd

The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.

Factory setting for DC link voltage: 1.5 × line voltage

Electronic power supply

24 V DC, -15 %/+20 %

Radio interference suppression

 

  • Standard
    With Active Interface Module

Category C3 according to EN 61800‑3

Cooling method

Increased air cooling by means of built-in fan

Permissible ambient or coolant temperature (air)

In operation for line-side components, Line Modules and Motor Modules

0 … 40 °C (32  … 104 °F) without derating,
> 40 … 55 °C (104  … 131 °F), see derating characteristics

Installation altitude

Up to 2000 m (6562 ft) above sea level without derating,
> 2000 ... 4000 m (6562 ... 13124 ft) above sea level, see derating characteristics

Declarations of conformity

CE (Low Voltage and EMC Directives)

Approvals, according to

cULus



Line supply voltage 380 … 480 V 3 AC

Active Line Module in chassis format

 

6SL3330‑...

7TE32-1AA3

7TE32-6AA3

7TE33-8AA3

7TE35-0AA3

Infeed/regenerative feedback power

 

 

 

 

 

  • Rated power Prated
     
  • At 400 V 3 AC

kW

132

160

235

300

  • At 460 V 3 AC 2)

(HP)

(200)

(225)

(350)

(450)

  • Pmax

kW

198

240

352,5

450

DC link current

 

 

 

 

 

  • Rated current Irated_DC

A

235

291

425

549

  • IH_DC

A

209

259

378

489

  • Imax_DC

A

352

436

637

823

Input current

 

 

 

 

 

  • Rated current at 400 V 3 AC 

A

210

260

380

490

  • Maximum

A

315

390

570

735

Current requirement

 

 

 

 

 

  • 24 V DC electronic power supply, max.

A

1.1

1.1

1.35

1.35

  • Fan supply at 400 V 2 AC, 50/60 Hz, max.

A

0.63/0.95

1.13/1.7

1.8/2.7

1.8/2.7

DC link capacitance

µF

4200

5200

7800

9600

Power loss, max.

kW

2.3

2.9

4.2

5.1

Cooling air requirement

m3/s (ft3/s)

0.17 (6.0)

0.23 (8.1)

0.36 (12.7)

0.36 (12.7)

Sound pressure level

LpA (1 m) 1)
at 50/60 Hz

dB

74/76

75/77

76/78

76/78

Line connection

U1, V1, W1

 

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

  • Conductor cross-section, max.

mm2

2 × 185

2 × 185

2 × 185

2 × 185

DC link connection

DCP, DCN

 

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

  • Conductor cross-section, max.

mm2

2 × 185

2 × 185

2 × 185

2 × 185

PE connection

 

M10 screw

M10 screw

M10 screw

M10 screw

  • Conductor cross-section, max.

 

 

 

 

 

  • PE1/GND

mm2

1 × 185

1 × 185

1 × 185

1 × 185

  • PE2/GND

mm2

2 × 185

2 × 185

2 × 185

2 × 185

Cable length, max.

Total of all motor cables and DC link

 

 

 

 

 

  • Shielded

m (ft)

2700 (8859)

2700 (8859)

2700 (8859)

2700 (8859)

  • Unshielded

m (ft)

4050 (13288)

4050 (13288)

4050 (13288)

4050 (13288)

Degree of protection

 

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

  • Width

mm (in)

326 (12.83)

326 (12.83)

326 (12.83)

326 (12.83)

  • Height

mm (in)

1400 (55.12)

1400 (55.12)

1533 (60.35)

1533 (60.35)

  • Depth

mm (in)

356 (14.02)

356 (14.02)

543 (21.38)

543 (21.38)

Frame size

 

FX

FX

GX

GX

Weight, approx.

kg (lb)

88 (194)

88 (194)

152 (335)

152 (335)



1) Total sound pressure level of Active Interface Module and Active Line Module.

2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be dimensioned accordingly.