Line filters Siemens

Обзор



In plants with strict EMC requirements, the line filter for frame size FSA restricts the conducted interference emanating from the PM340 Power Module to the limit values of Class C2 as defined in EN 61800‑3. The line filter is suited only for direct connection to TN (grounded) systems.

Note:

The line filter is designed only for PM340 Power Modules of frame size FSA and a line voltage of 380 V to 480 V 3 AC. All other PM340 Power Modules are available with integrated line filter.

Интеграция



Line filter, line reactor and Power Module can be mounted in front of one another.

Технические данные



Line voltage 380 ... 480 V 3 AC

Line filter

6SE6400-2FA00-6AD0

Rated current

6 A

Power loss

< 5 W

Line connection

L1, L2, L3

Screw-type terminals

  • Conductor cross-section

1 ... 2.5 mm2

PE connection

M4 screw stud

Load connection

U, V, W

Shielded cable

  • Conductor cross-section

4 × 1.5 mm2

  • Length, approx.

0.24 m (0.79 ft)

Degree of protection

IP20 (with correctly connected load connection cable)

Dimensions

 

  • Width

73.5 mm (2.89 in)

  • Height

200 mm (7.87 in)

  • Depth

44 mm (1.73 in)

Weight, approx.

0.5 kg (1 lb)

Approvals, according to

cURus

Suitable for Power Module, blocksize format

Type (rated output current)

6SL3210-1SE11-... (1.3 A and 1.7 A)

6SL3210-1SE12-... (2.2 A)

6SL3210-1SE13-... (3.1 A)

6SL3210-1SE14-... (4.1 A)