Line filters Siemens
Обзор
In plants with strict EMC requirements, the line filter for frame size FSA restricts the conducted interference emanating from the PM340 Power Module to the limit values of Class C2 as defined in EN 61800‑3. The line filter is suited only for direct connection to TN (grounded) systems.
Note:
The line filter is designed only for PM340 Power Modules of frame size FSA and a line voltage of 380 V to 480 V 3 AC. All other PM340 Power Modules are available with integrated line filter.
Интеграция
Line filter, line reactor and Power Module can be mounted in front of one another.
Технические данные
Line voltage 380 ... 480 V 3 AC | Line filter 6SE6400-2FA00-6AD0 |
---|---|
Rated current | 6 A |
Power loss | < 5 W |
Line connection L1, L2, L3 | Screw-type terminals |
| 1 ... 2.5 mm2 |
PE connection | M4 screw stud |
Load connection U, V, W | Shielded cable |
| 4 × 1.5 mm2 |
| 0.24 m (0.79 ft) |
Degree of protection | IP20 (with correctly connected load connection cable) |
Dimensions |
|
| 73.5 mm (2.89 in) |
| 200 mm (7.87 in) |
| 44 mm (1.73 in) |
Weight, approx. | 0.5 kg (1 lb) |
Approvals, according to | cURus |
Suitable for Power Module, blocksize format Type (rated output current) | 6SL3210-1SE11-... (1.3 A and 1.7 A) 6SL3210-1SE12-... (2.2 A) 6SL3210-1SE13-... (3.1 A) 6SL3210-1SE14-... (4.1 A) |