Single Motor Modules in booksize compact format Siemens
Дизайн
Single Motor Modules in booksize compact format
The Single Motor Modules in booksize compact format feature the following connections and interfaces as standard:
- 2 DC link connections via integrated DC link busbars
- 1 electronics power supply connection via integrated 24 V DC busbars
- 3 DRIVE‑CLiQ sockets
- 1 motor connection via connector
- 1 safe standstill input (enable pulses)
- 1 safe motor brake control
- 1 temperature sensor input (KTY84‑130 or PTC)
- 2 PE (protective earth) connections
The status of the Motor Modules is indicated via two multi-color LEDs.
The shield of the motor cable is routed over the connector to the motor connection.
The signal cable shield can be connected to the Motor Module by means of a shield connection terminal, e.g. Weidmüller type KLBÜ 3-8 SC.
The scope of supply of the Motor Modules includes:
- DRIVE‑CLiQ cable (length depends on module width) to connect Motor Module to adjacent Motor Module
length 0.11 m (4.33 in) for 50 mm (1.97 in) wide Motor Modules or
length 0.16 m (6.3 in) for 75 mm (2.95 in) wide Motor Modules. - 2 blanking plugs for sealing unused DRIVE‑CLiQ sockets
- Jumper for connecting the 24 V DC busbar to the adjacent Motor Module
- Connector X21
- Connector X11 for motor brake connection
- Connector X1 for motor connection
- 1 set of warning signs in 30 languages
- 1 heat conducting foil
Характеристика
Overload capability
Peak current duty cycle with full load (300% overload)
Note:
Imax stands for 2 x Irated in the following overload characteristics.
Load cycle with previous load
Load cycle without previous load
S6 load cycle with previous load with a load cycle period of 600 s
S6 load cycle with previous load with a load cycle period of 60 s
Load cycle with 60 s overload with a load cycle period of 300 s
Load cycle with 30 s overload with a load cycle period of 300 s
Derating characteristics
3 A and 5 A Single Motor Modules in booksize compact format
Output current dependent on pulse frequency
9 A and 18 A Single Motor Modules in booksize compact format
Output current dependent on pulse frequency
Output current dependent on ambient temperature
Output current dependent on installation altitude
Voltage derating dependent on installation altitude
Output current dependent on output frequency
Интеграция
Single Motor Modules communicate with the Control Unit via DRIVE‑CLiQ.
Connection example of Single Motor Module in booksize compact format
Технические данные
Single Motor Module in booksize compact format 6SL3420-1TE... |
|
---|---|
DC link voltage (up to 2000 m (6562 ft) above sea level) | 510 ... 720 V DC |
Output frequency |
|
| 0 ... 650 Hz 1) 2) |
| 0 ... 300 Hz 1) |
| 0 ... 600 Hz 1) 2) |
Electronics power supply | 24 V DC -15 %/+20 % |
Type of cooling | Internal air cooling (power units with increased air cooling by built-in fan) Cold plate cooling |
Permissible ambient and coolant temperature (air) during operation for line-side components, Line Modules and Motor Modules | 0 ... 40 °C (32 ... 104 °F) without derating, |
Installation altitude | Up to 1000 m (3281 ft) above sea level without derating, |
Declarations of conformity | CE (Low-Voltage and EMC Directives) |
Approvals, according to | UL-recognized |
Safety Integrated | Safety Integrity Level 2 (SIL 2) acc. to IEC 61508, Performance Level d (PL d) acc. to ISO 13849‑1 and Control Category 3 acc. to ISO 13849‑1 or EN 954‑1 For further information, see section Safety Integrated.. |
1) Note the correlation between max. output frequency, pulse frequency and current derating.For more information, see section System description - Dimensioning.
2) The output frequency is currently limited to 550 Hz. The specified values apply to systems with license for high output frequency. For further information, refer to section Control Units and http://support.automation.siemens.com/WW/view/en/104020669
DC link voltage 510 ... 720 V DC | Single Motor Module in booksize compact format | ||||
---|---|---|---|---|---|
| 6SL3420-1TE13-0AA1 | 6SL3420-1TE15-0AA1 | 6SL3420-1TE21-0AA1 | 6SL3420-1TE21-8AA1 | |
Output current |
|
|
|
|
|
| A | 3 | 5 | 9 | 18 |
| A | 2.6 | 4.3 | 7.7 | 15.3 |
| A | 3.5 | 6 | 10 | 24 |
| A | 9 | 15 | 27 | 54 |
Type rating 1) |
|
|
|
|
|
| kW (HP) | 1.6 (1.5) | 2.7 (3) | 4.8 (5) | 9.7 (10) |
| kW (HP) | 1.4 (1) | 2.3 (2.5) | 4.1 (5) | 8.2 (10) |
Rated pulse frequency | kHz | 8 | 8 | 4 | 4 |
DC link current Id2) | A | 3.6 | 6 | 11 | 22 |
Current carrying capacity |
|
|
|
|
|
| A | 100 | 100 | 100 | 100 |
| A | 20 | 20 | 20 | 20 |
DC link capacitance | μF | 110 | 110 | 110 | 235 |
Power requirement At 24 V DC, max. | A | 0.85 | 0.85 | 0.85 | 0.85 |
Power loss |
|
|
|
|
|
| kW | 0.07 | 0.1 | 0.1 | 0.18 |
| kW | 0.026/0.04 | 0.031/0.065 | 0.031/0.065 | 0.051/0.095 |
Cooling air requirement | m3/s (ft3/s) | 0.008 (0.3) | 0.008 (0.3) | 0.008 (0.3) | 0.008 (0.3) |
Thermal resistance Rth | K/W | 0.25 | 0.25 | 0.25 | 0.16 |
Sound pressure level LpA (1 m) | dB | <60 | <60 | <60 | <60 |
Motor connection U2, V2, W2 |
| Connector (X1) with screw-type terminals | Connector (X1) with screw-type terminals | Connector (X1) with screw-type terminals | Connector (X1) with screw-type terminals |
| mm2 | 0.2 ... 6 | 0.2 ... 6 | 0.2 ... 6 | 0.2 ... 6 |
Shield connection |
| Integrated in connector (X1) | Integrated in connector (X1) | Integrated in connector (X1) | Integrated in connector (X1) |
PE connection |
| M5 screw | M5 screw | M5 screw | M5 screw |
Motor brake connection |
| Connector (X11), | Connector (X11), | Connector (X11), | Connector (X11), |
Motor cable length, max. |
|
|
|
|
|
| m (ft) | 50 (164) | 50 (164) | 50 (164) | 70 (230) |
| m (ft) | 75 (246) | 75 (246) | 75 (246) | 100 (328) |
Degree of protection |
| IP20 | IP20 | IP20 | IP20 |
Dimensions |
|
|
|
|
|
| mm (in) | 50 (1.97) | 50 (1.97) | 50 (1.97) | 75 (2.95) |
| mm (in) | 270 (10.63) | 270 (10.63) | 270 (10.63) | 270 (10.63) |
| mm (in) | 226 (8.90) | 226 (8.90) | 226 (8.90) | 226 (8.90) |
Weight, approx. | kg (lb) | 2.7 (5.95) | 2.7 (5.95) | 2.7 (5.95) | 3.4 (7.50) |
1) Rated power of a typical standard asynchronous (induction) motor at 600 V DC link voltage.
2) Rated DC link current for dimensioning an external DC connection.For DC link current calculation for dimensioning the Line Module, see chapter System description – Dimensioning.
3) If, due to a number of Line Modules and Motor Modules being mounted side-by-side, the current carrying capacity exceeds 20 A, an additional 24 V DC connection using a 24 V terminal adapter is required (max. cross-section 6 mm2, max. fuse protection 20 A).