TM15 Terminal Module Siemens

Обзор



The number of available digital inputs and outputs within a drive system can be expanded with the TM15 Terminal Module.

Дизайн



The following are located on the TM15 Terminal Module:

  • 24 bidirectional digital inputs/outputs (isolation in 3 groups with 8 channels each)
  • 24 green status LEDs for indicating the logical signal status of the relevant terminal
  • 2 DRIVE‑CLiQ sockets
  • 1 connection for the electronics power supply via the 24 V DC power supply connector
  • 1 PE (protective earth) connection

The TM15 Terminal Module can be snapped onto a TH 35 standard mounting rail in accordance with EN 60715 (IEC 60715).

The signal cable shield can be connected to the TM15 Terminal Module via a shield connection terminal, e.g. Phoenix Contact type SK8 or Weidmüller type KLBÜ CO 1. The shield connection terminal must not be used for strain relief.

The status of the TM15 Terminal Module is indicated via a multi-color LED.

Интеграция



The TM15 Terminal Module communicates with a CU310‑2, CU320‑2 or SIMOTION D Control Unit via DRIVE‑CLiQ.

Connection example of a TM15 Terminal Module

Технические данные



TM15 Terminal Module

6SL3055-0AA00-3FA0

 

Power requirement

With 24 V DC without load, max.

0.15 A

  • Conductor cross-section, max.

2.5 mm2

  • Fuse protection, max.

20 A

Number of DRIVE‑CLiQ sockets

2

I/O

 

  • Digital inputs/outputs

Can be parameterized channel-by-channel as DI or DO

  • Number of digital inputs/outputs

24

  • Isolation

Yes, in groups of 8

  • Cables and connections

Plug-in screw-type terminals

  • Conductor cross-section, max.

1.5 mm2

Digital inputs

 

  • Voltage

-3 … +30 V

  • Low level (an open digital input is interpreted as "low")

-3 … +5 V

  • High level

15 … 30 V

  • Current consumption at 24 V DC

5 … 11 mA

  • Delay times of digital inputs, typ.1)

 

  • L → H

50 μs

  • H → L

100 μs

Digital outputs

Sustained short-circuit strength

 

  • Voltage

24 V DC

  • Load current per digital output, max.

0.5 A

  • Delay times (resistive load) 1)

 

  • L → H, typ.
    L → H, max.

50 μs
100 μs

  • H → L, typ.
    H → L, max.

150 μs
225 μs

  • Aggregate current of outputs (per group), max.

 

  • Up to 60 °C (140 °F)

2 A

  • Up to 50 °C (122 °F)

3 A

  • Up to 40 °C (104 °F)

4 A

Power loss

< 3 W

PE connection

M4 screw

Dimensions

 

  • Width

50 mm (1.97 in)

  • Height

150 mm (5.90 in)

  • Depth

111 mm (4.37 in)

Weight, approx.

0.86 kg (2 lb)

Approvals, according to

cULus



1) The specified delay times refer to the hardware. The actual reaction time depends on the time slot in which the digital input/output is processed.