1-phase, 24 V DC (for S7-1500 and ET200MP) Siemens
Обзор
The design and functionality of the SIMATIC PM 1507 single-phase load power supply (PM = power module) with automatic range selection of the input voltage makes it an optimal match to the SIMATIC S7-1500 PLC. It supplies the S7-1500 system components such as CPU, system power supply (PS), I/O circuits of the input and output modules and, if necessary, the sensors and actuators with 24 V DC.
Дизайн
- The load current supplies are directly fastened to the S7-1500 mounting rail (without connection to the backplane bus) and can be mounted directly to the left of the CPU (no installation clearance required)
- Diagnostics LEDs to indicate status and faults: Operation, Fault, Stand-by
- ON/OFF switches (operation/stand-by) in case of swapping modules
- Mains connection plug with touch protection and strain relief for connection of input voltage (enables permanent wiring)
- Plug-in 24 V DC output terminal with reverse polarity protection for connection of 24 V loads (enables permanent wiring)
Функции
- Connection to all 1-phase 50/60 Hz networks (120 / 230 V AC) through automatic range switching
- Short-term mains buffering
- Output voltage of 24 V DC that is limited to maximum 28 V DC (prevents any damages in 24 V loads if input voltage is too high)
- 50% "Extra Power" for 5 seconds per minute for short-term overloads, for example, when switching on 24V consumers
- Parallel connection of two load current supplies for enhanced performance
Технические данные
Order number | 6EP1332-4BA00 | 6EP1333-4BA00 | |
---|---|---|---|
Product | S7-1500 PM1507 | S7-1500 PM1507 | |
Power supply, type | 24 V/3 A | 24 V/8 A | |
Input |
|
| |
Input | 1-phase AC | 1-phase AC | |
Supply voltage |
|
| |
| 120 V | 120 V | |
| 230 V | 230 V | |
| Automatic range selection | Automatic range selection | |
Input voltage |
|
| |
| 85 ... 132 V | 85 ... 132 V | |
| 170 ... 264 V | 170 ... 264 V | |
Wide-range input | No | No | |
Overvoltage resistance | 2.3 × Vin rated, 1.3 ms | 2.3 × Vin rated, 1.3 ms | |
Mains buffering at Iout rated, min. | 20 ms; at Vin = 93/187 V | 20 ms; at Vin = 93/187 V | |
Rated line frequency | 50 ... 60 Hz | 50 ... 60 Hz | |
Rated line range | 45 ... 65 Hz | 45 ... 65 Hz | |
Input current |
|
| |
| 1.4 A | 3.7 A | |
| 0.8 A | 1.7 A | |
Switch-on current limiting (+25 °C), max. | 23 A | 62 A | |
Duration of inrush current limiting at 25 °C |
|
| |
| 3 ms | 3 ms | |
I²t, max. | 1.3 A²·s | 12 A²·s | |
Built-in incoming fuse | T 3,15 A/250 V (not accessible) | T 6.3 A/250 V (not accessible) | |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C | Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C | |
Output |
|
| |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | |
Rated voltage Vout DC | 24 V | 24 V | |
Total tolerance, static ± | 1 % | 1 % | |
Static mains compensation, approx. | 0.1 % | 0.1 % | |
Static load balancing, approx. | 0.1 % | 0.1 % | |
Residual ripple peak-peak, max. | 50 mV | 50 mV | |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 150 mV | 150 mV | |
Product function Output voltage adjustable | No | No | |
Status display | LED green for 24 V OK; LED red for error; LED yellow for stand-by | LED green for 24 V OK; LED red for error; LED yellow for stand-by | |
On/off behavior | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) | |
Startup delay, max. | 1.5 s | 1.5 s | |
Voltage rise, typ. | 10 ms | 10 ms | |
Rated current value Iout rated | 3 A | 8 A | |
Current range | 0 ... 3 A | 0 ... 8 A | |
Active power supplied typical | 72 W | 192 W | |
Short-term overload current |
|
| |
| 12 A | 35 A | |
| 12 A | 35 A | |
Duration of overloading capability for excess current |
|
| |
| 70 ms | 70 ms | |
| 70 ms | 70 ms | |
Parallel switching for enhanced performance | Yes; Parallel switching of 3 A and 8 A possible, devices must be switched on at the same time, max. 75% per device with I-load | Yes; Parallel switching of 3 A and 8 A possible, devices must be switched on at the same time, max. 75% per device with I-load | |
Numbers of parallel switchable units for enhanced performance | 2 | 2 | |
Efficiency |
|
| |
Efficiency at Vout rated, Iout rated, approx. | 87 % | 90 % | |
Power loss at Vout rated, Iout rated, approx. | 11 W | 21 W | |
Closed-loop control |
|
| |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.1 % | 0.1 % | |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 1 % | 2 % | |
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ. | 3 % | 3 % | |
Load step setting time 10 to 90%, typ. | 5 ms | 5 ms | |
Load step setting time 90 to 10%, typ. | 5 ms | 5 ms | |
Setting time maximum | 5 ms | 5 ms | |
Protection and monitoring |
|
| |
Output overvoltage protection | Additional control loop, limitation (closed loop control) at < 28.8 V | Additional control loop, limitation (closed loop control) at < 28.8 V | |
Current limitation | 3.15 ... 3.6 A | 8.4 ... 9.6 A | |
Current limitation, typ. | 3.4 A | 9 A | |
Property of the output Short-circuit proof | Yes | Yes | |
Short-circuit protection | Electronic shutdown, automatic restart | Electronic shutdown, automatic restart | |
Overload/short-circuit indicator | - | - | |
Safety |
|
| |
Primary/secondary isolation | Yes | Yes | |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 | |
Protection class | Class I | Class I | |
Leakage current |
|
| |
| 3.5 mA | 3.5 mA | |
| 0.4 mA | 1.3 mA | |
CE mark | Yes | Yes | |
UL/CSA approval | Yes | Yes | |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 | cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 | |
Explosion protection | ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 | ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T3, File E330455 | |
Certificate of suitability IECEx | No | No | |
Certificate of suitability NEC Class 2 | No | No | |
FM approval | Class I, Div. 2, Group ABCD, T4 | Class I, Div. 2, Group ABCD, T4 | |
CB approval | Yes | Yes | |
Marine approval | GL, DNV | GL, DNV | |
Degree of protection (EN 60529) | IP20 | IP20 | |
EMC |
|
| |
Emitted interference | EN 55022 Class B | EN 55022 Class B | |
Supply harmonics limitation | EN 61000-3-2 | EN 61000-3-2 | |
Noise immunity | EN 61000-6-2 | EN 61000-6-2 | |
Operating data |
|
| |
Ambient temperature |
|
| |
| 0 ... 60 °C | 0 ... 60 °C | |
| with natural convection | with natural convection | |
| -40 ... +85 °C | -40 ... +85 °C | |
| -40 ... +85 °C | -40 ... +85 °C | |
Humidity class according to EN 60721 | Climate class 3K3, no condensation | Climate class 3K3, no condensation | |
Mechanics |
|
| |
Connection technology | Screw-/spring clamp connection | Screw-/spring clamp connection | |
Connections |
|
| |
| L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² | L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² | |
| L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² | L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² | |
Product function |
|
| |
| Yes | Yes | |
| Yes | Yes | |
Width of the enclosure | 50 mm | 75 mm | |
Height of the enclosure | 147 mm | 147 mm | |
Depth of the enclosure | 129 mm | 129 mm | |
Weight, approx. | 0.45 kg | 0.74 kg | |
Product property of the enclosure housing for side-by-side mounting | Yes | Yes | |
Installation | Can be mounted onto S7-1500 rail | Can be mounted onto S7-1500 rail | |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Дополнительно
Power connector | 6ES7590-8AA00-0AA0 |
With coding element for power supply module; spare part, |