CPU 416F Siemens

Область применения
The CPU 416F-2 and the CPU 416F-3 PN/DP are high-performance CPUs of the SIMATIC S7-400. They allow a fail-safe automation system to be constructed for plants with increased safety requirements.
The integrated PROFIBUS DP interfaces of CPU 416F-2 support direct connection to the PROFIBUS DP fieldbus as a master or as a slave.
Another DP master system can be connected in the case of the CPU 416F-3 PN/DP through the IF 964-DP interface module.
The integrated PROFINET interface of the CPU 416F-3 PN/DP implements switch functionality by using the ERTEC 400 ASIC. This forms the basis for provision of 2 externally accessible PROFINET ports. This means that apart from hierarchic network topologies, line structures can also be implemented with the new S7-400 controllers.
Note:
Only interface module 6ES7964-2AA04-0AB0 can be used.
Fail-safe I/O modules can be connected to all integrated interfaces, to IF 964-DP and/or through communication modules (CP443-5 Ext. and CP443-1 Advanced). Safety-related communication is performed over PROFIBUS DP with the PROFIsafe profile.
Обзор
- For constructing a fail-safe automation system for plants with increased safety requirements
- High-performance CPU in the top-end performance range
- Complies with safety requirements to SIL 3 acc. to IEC 61508 and PL e acc. to ISO 13849.1
- Standard and safety-related tasks can be performed with a single CPU
- Multi-processor mode is possible
- Safety-related communication with distributed I/O devices over PROFIBUS DP with the PROFIsafe profile
- Fail-safe I/O modules can be connected decentralized over the integrated interfaces (DP and PN with CPU416F-3 PN/DP) and/or through communication modules (CP443-5 Ext. and CP443-1 Adv.)
- Standard modules for non-safety-related applications can be operated centrally and decentralized
Дизайн
Both CPUs feature:
- High-performance processor:
The CPUs achieve command runtimes down to 0.03 µs per binary instruction. - CPU 416F-2: 5.6 MB working memory (of which 2.8 MB each for program or data);
CPU 416F-3 PN/DP: 11.2 MB working memory (of which 5.6 MB each for program or data);
fast working memory for sections of the user program that are significant for execution. - Flexible expansion possibilities:
Max. 262144 digital, 16384 analog inputs/outputs. - MPI multi-point interface:
The MPI allows a simple network to be established with up to 32 stations and a data transmission rate of up to 12 Mbit/s. The CPUs can establish up to 44 connections to stations of the communications bus (C bus) and MPI. - Mode selector:
Implemented as a toggle switch. - Diagnostics buffer:
The last 120 error and interrupt events are stored in a ring buffer for diagnostic purposes. The number of entries can be parameterized. - Real-time clock:
Diagnostic alarms of the CPU are tagged with the date and time. - Memory card:
To expand the integrated load memory. RAM and FEPROM cards (FEPROM for saving even at zero voltage). - Combined MPI/DP interface and integrated PROFIBUS DP interface (with CPU 416F-2):
The PROFIBUS DP master interface allows a distributed automation configuration offering high speed and ease of use. The distributed I/O is treated like a central I/O from the point of view of the user (same configuring, addressing and programming).
Mixed installation: SIMATIC S5 and SIMATIC S7 as PROFIBUS master acc. to EN 50170.
CPU 416F-3 PN/DP also features:
- Submodule socket:
Using the IF 964-DP interface module, an additional PROFIBUS DP master system can be connected. - PROFINET interface with 2 ports (switch)
- PROFINET I/O, 256 IO devices can be connected
- PROFINET CBA
Fail-safe I/O modules can be connected to all integrated interfaces, to IF 964-DP and/or through communication modules (CP443-5 Ext. and CP443-1 Advanced). Safety-related communication is performed over PROFIBUS DP with the PROFIsafe profile.
Функции
- Block protection:
A password concept protects the user program from unauthorized access. - Integrated HMI services:
For HMI devices, the user only has to specify the source and destination for the data. They are then cyclically transported by the system automatically. - Integrated communication functions:
- PG/OP communication
- Global data communication
- S7 basic communication
- S7 communication
- Firmware update over the network
CPU 416F-3 PN/DP additionally:
- Open communication over TCP/IP, UDP and ISO-on-TCP (RFC1006)
- Distributed intelligence in Component Based Automation (CBA) on PROFINET
- Additional diagnostic option with integrated web server
Parameterizable properties
Using the STEP 7 hardware configuration tool, properties and responses of the S7-400 including the CPUs can be parameterized, e.g.:
- MPI multi-point interface:
- Determining station addresses.
- Start-up/cyclic response.
- Determining the maximum cycle time and communication load.
- Address assignment:
Addressing the I/O modules. - Retentive areas:
Determining the number of retentive bit memories, counters, timers, data blocks and clock bit memories - Size of the process image, local data.
- Length of the diagnostic buffer.
- Protection level:
Specifying the access rights to program and data. - System diagnostics:
Determining handling and scope of the diagnostic alarms. - Cyclic interrupts:
Setting of periodicity
CPU 416F-3 PN/DP additionally:
- PROFINET interface
- Parameterization of time synchronization with NTP procedure
Information and display functions
- Status and error LEDs:
LEDs indicate, for example, internal and external errors and operating states such as RUN, STOP, start-up and test functions. - Test functions:
The PG is used to indicate signal states during program execution, to modify process variables independently of the user program, to output the contents of stack memories, to execute individual program steps, and to block program sections. - Information functions:
The PG can be used to obtain information about the memory capacity and operating mode of the CPU and the current loading of the work and load memory.
Communication
The safety related and standard communication between the central controller and the fail-safe ET 200 modules takes place over PROFIBUS DP and/or PROFINET. The specially developed PROFIBUS profile PROFIsafe supports the transfer of user data for the safety functions within the standard data message frame. Additional hardware components, e.g. special safety buses are not required. The necessary software is either integrated in the hardware components as an expansion of the operating system or loaded into the CPU later as a certified software block.
Mode of operation
The safety functions of the F-CPU are included in the F program of the CPU and in the fail-safe signal modules.
The signal modules monitor the output and input signals by means of discrepancy analysis and the injection of test signals.
The CPU checks the proper operation of the controller by means of periodic self-tests, command tests and logic-based and time-based program execution checks. Furthermore, the I/O is checked using requests for signs of life.
If an error is diagnosed in the system, the system will be placed in a safe state.
An F runtime license is not required to operate the CPU 416F-2 and CPU 416F-3 PN/DP.
Programming
The CPU 416F-2 and the CPU 416F-3 PN/DP are programmed in the same manner as the other SIMATIC S7 systems. The user program for non-fail-safe plant sections is created using familiar programming tools, e.g. STEP 7.
Option packages SIMATIC S7 Distributed Safety (Classic) and SIMATIC Safety Advanced V12 (TIA Portal V12)
The STEP 7 option packages "SIMATIC S7 Distributed Safety" (Classic) or SIMATIC Safety Advanced V12 (TIA Portal V12) are required for programming the safety-related program sections. The packages contain all the functions and blocks required to create an F program.
The F program with the safety functions is connected in F FBD or F LAD or using special functions from the F library. Use of F FBD or F LAD simplifies configuration and programming of the plant and also acceptance testing thanks to the non-plant-specific uniform presentation form. The programmer can concentrate on configuring the safety-related application without having to use additional tools. The STEP 7 option package "SIMATIC S7 Distributed Safety" is required for programming the safety-related program sections. The package contains all the functions and blocks required to create an F program.
Технические данные
Order number | 6ES7416-2FN05-0AB0 | 6ES7416-3FS07-0AB0 | |
---|---|---|---|
CPU 416F-2, MPI, PROFIBUS, 5.6 MB | |||
General information |
|
| |
Product type designation | CPU 416F-2 | CPU416F-3 PN/DP | |
Engineering with |
|
| |
| STEP 7 V5.3 SP2 or higher with hardware update, Distributed Safety V5.2 SP2 or higher | STEP 7 V5.5 or higher with HSP 262 | |
Supply voltage |
|
| |
Rated value (DC) | |||
| No; Power supply via system power supply | No; Power supply via system power supply | |
Power loss |
|
| |
Power loss, typ. | 4.5 W | 6.5 W | |
Memory |
|
| |
Work memory |
|
| |
| 5.6 Mbyte | 16 Mbyte | |
| 2.8 Mbyte | 8 Mbyte | |
| 2.8 Mbyte | 8 Mbyte | |
Load memory |
|
| |
| 64 Mbyte | 64 Mbyte | |
| 1 Mbyte | 1 Mbyte | |
| 64 Mbyte | 64 Mbyte | |
CPU processing times |
|
| |
for bit operations, typ. | 30 ns | 12.5 ns | |
for word operations, typ. | 30 ns | 12.5 ns | |
for fixed point arithmetic, typ. | 30 ns | 12.5 ns | |
for floating point arithmetic, typ. | 90 ns | 25 ns | |
Counters, timers and their retentivity |
|
| |
S7 counter |
|
| |
| 2 048 | 2 048 | |
IEC counter |
|
| |
| Yes | Yes | |
S7 times |
|
| |
| 2 048 | 2 048 | |
IEC timer |
|
| |
| Yes | Yes | |
Data areas and their retentivity |
|
| |
Flag |
|
| |
| 16 kbyte; Size of bit memory address area | 16 kbyte; Size of bit memory address area | |
Address area |
|
| |
I/O address area |
|
| |
| 16 kbyte | 16 kbyte | |
| 16 kbyte | 16 kbyte | |
Process image |
|
| |
| 16 kbyte | 16 kbyte | |
| 16 kbyte | 16 kbyte | |
Hardware configuration |
|
| |
Slots |
|
| |
| 1 | 2 | |
Time of day |
|
| |
Clock |
|
| |
| Yes | Yes | |
Operating hours counter |
|
| |
| 16 | 16 | |
Interfaces |
|
| |
Interfaces/bus type | 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) | ||
Number of RS 485 interfaces | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 1; Combined MPI / PROFIBUS DP | |
Number of other interfaces | 1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) | ||
1. Interface |
|
| |
Interface type | Integrated | Integrated | |
Physics | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI | |
Functionality |
|
| |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
DP master |
|
| |
| 32 | 32 | |
2. Interface |
|
| |
Interface type | Integrated | PROFINET | |
Physics | RS 485 / PROFIBUS | Ethernet RJ45 | |
Number of ports | 2 | ||
Functionality |
|
| |
| Yes | No | |
| Yes | No | |
| Yes | ||
| Yes | ||
| Yes | ||
DP master |
|
| |
| 125 | ||
PROFINET IO Controller |
|
| |
| 256 | ||
| 256 | ||
| 64 | ||
3. Interface |
|
| |
Interface type | Pluggable interface module (IF) | ||
Plug-in interface modules | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) | ||
Physics | RS 485 / PROFIBUS | ||
Functionality |
|
| |
| No | ||
| Yes | ||
| Yes | ||
DP master |
|
| |
| 125 | ||
Isochronous mode |
|
| |
Isochronous operation (application synchronized up to terminal) | Yes; For PROFIBUS only | Yes; Via PROFIBUS DP or PROFINET interface | |
Communication functions |
|
| |
PG/OP communication | Yes | Yes | |
Data record routing | Yes | Yes | |
Global data communication |
|
| |
| Yes | Yes | |
S7 basic communication |
|
| |
| Yes | Yes | |
S7 communication |
|
| |
| Yes | Yes | |
S5 compatible communication |
|
| |
| Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | |
Standard communication (FMS) |
|
| |
| Yes; Via CP and loadable FB | Yes; Via CP and loadable FB | |
Open IE communication |
|
| |
| Yes; via integrated PROFINET interface and loadable FBs | ||
| 94 | ||
| Via CP 443-1 and loadable FB | Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs | |
| 94 | ||
| Yes; via integrated PROFINET interface and loadable FBs | ||
| 94 | ||
Web server |
|
| |
| No | Yes | |
Number of connections |
|
| |
| 64 | 96 | |
Standards, approvals, certificates |
|
| |
Use in hazardous areas |
|
| |
| ATEX II 3 G Ex nA IIC T4 Gc | ATEX II 3 G Ex nA IIC T4 Gc | |
Ambient conditions | Запрос коммерческого предложения× Сообщение отправлено× В ближайшее время сообщение будет обработано. Письмо с номером обращения отправлено на Ваш почтовый ящик. Спасибо за то, что выбрали Первый ZIP! Что-то пошло не так...× К сожалению, наша система расценила Ваше сообщение как спам. Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте. Приносим извинения за возможные неудобства. |