SM 421 digital input module Siemens

Область применения
Digital input modules can be used to connect the control to digital process signals. They are suitable for connecting standard switches and two-wire proximity switches (BERO).
Обзор
- Digital inputs for the SIMATIC S7-400
- For connecting standard switches and two-wire proximity switches (BERO)
Дизайн
The digital input modules have the following mechanical features:
- Compact configuration:
The rugged plastic housing contains:- Green LEDs to indicate signal states at the inputs
- One red LED each to indicate internal and external faults or errors in modules with diagnostic and process interrupts
- Labeling strips
- Simple assembly
- User-friendly wiring:
The modules are wired by means of a plug-in front connector.
Функции
Digital input modules convert the levels of the external digital signals from the process into the internal signal level of the S7-400.
Технические данные
Order number | 6ES7421-7BH01-0AB0 | 6ES7421-1BL01-0AA0 | 6ES7421-1EL00-0AA0 | 6ES7421-1FH20-0AA0 | 6ES7421-7DH00-0AB0 | |
---|---|---|---|---|---|---|
SM421, 16DI, DC24V, 0.05MS INPUT DELAY | SM421, 32DI, DC24V | SM421, 32DI, DC/AC 120V | SIMATIC S7-400, DIG.INPUT MOD. | SIMATIC S7-400, SM 421 | ||
Supply voltage |
|
|
|
|
| |
Load voltage L+ |
|
|
|
|
| |
| 24 V | |||||
| 20.4 V | |||||
| 28.8 V | |||||
Input current |
|
|
|
|
| |
from supply voltage L+, max. | 120 mA | |||||
from backplane bus 5 V DC, max. | 130 mA | 20 mA | 200 mA | 80 mA | 150 mA | |
Power loss |
|
|
|
|
| |
Power loss, typ. | 5 W | 6 W | 6.5 W | 12 W | 8 W; 3.5 W (24 V DC); 6.5 W (48 V DC); 8.0 W (60 V DC) | |
Digital inputs |
|
|
|
|
| |
Number of digital inputs | 16 | 32 | 32 | 16 | 16 | |
Number of simultaneously controllable inputs |
|
|
|
|
| |
| 16 | 32 | 32 | 16 | 16 | |
Input voltage |
|
|
|
|
| |
| DC | DC | AC/DC | AC/DC | AC/DC | |
| 24 V | 24 V | ||||
| 120 V | 230 V; 120/230 V UC | 24 V; 24 to 60 V UC | |||
| -30V DC to +5V DC | -30V DC to +5V DC | 0 to 20 V UC | 0 to 40 V AC/ -40 to +40 V DC | -6 to +6 V DC/ 0 to 5 V AC | |
| 11V DC to 30V DC | 13 V DC to 30 V DC | 79 to 132 V AC; 80 to 132 V DC | 74 to 264 V AC; 80 to 264 V DC, -80 to -264 V | 15 to 72 V DC; -15 to -72 V DC; 15 to 60 V AC | |
| 47 ... 63 Hz | 47 ... 63 Hz | 47 to 63 Hz AC / DC | |||
Input current |
|
|
|
|
| |
| 1.3 mA | 1 mA | 6 mA; AC: 6 mA; DC: 2 mA | |||
| 6 mA; 6 to 8 mA | 7 mA | 2 mA; 2 to 5 mA | 10 mA; at 120 V: 10 mA AC, 1.8 mA DC; at 230 V: 14 mA AC, 2 mA DC | 4 mA; 4 to 10 mA | |
Input delay (for rated value of input voltage) |
|
|
|
|
| |
for standard inputs |
|
|
|
|
| |
| Yes | Yes | ||||
| 0.5 ms; 0.5 / 3 / 10 / 20 ms | |||||
Cable length |
|
|
|
|
| |
| 1 000 m; 1000 m: 3 ms, 70 m: 0.5 ms, 30 m: 0.1 ms, 30 m: 0.05 ms | 1 000 m | 1 000 m | 1 000 m | 1 000 m | |
| 600 m; 600 m: 3 ms; 50 m: 0,5 ms; 20 m: 0,1 ms; 20 m: 0,05 ms | 600 m | 600 m | 600 m | 600 m; 600 m: 3, 10, 20 ms; 100 m: 0,5 ms | |
Encoder |
|
|
|
|
| |
Connectable encoders |
|
|
|
|
| |
| Yes | Yes | Yes | Yes | Yes | |
| 3 mA | 1.5 mA | 1 mA | 5 mA; AC: 5 mA | 0.5 mA; 0.5 to 2 mA | |
Interrupts/diagnostics/status information |
|
|
|
|
| |
Alarms |
|
|
|
|
| |
| Yes; Parameterizable | Yes; Parameterizable | ||||
| Yes; Parameterizable | Yes; Parameterizable | ||||
Diagnostic messages |
|
|
|
|
| |
| Yes; internal/ external fault | Yes; internal/ external fault | ||||
Potential separation |
|
|
|
|
| |
Potential separation digital inputs |
|
|
|
|
| |
| 8 | 32 | 8 | 4 | 1 | |
| Yes | Yes | Yes | Yes | Yes | |
Isolation |
|
|
|
|
| |
Isolation tested with | 500 V DC | 500 V DC | 1500 V AC | 1500 V AC | 1500 V AC | |
Dimensions |
|
|
|
|
| |
Width | 25 mm | 25 mm | 25 mm | 25 mm | 25 mm | |
Height | 290 mm | 290 mm | 290 mm | 290 mm | 290 mm | |
Depth | 210 mm | 210 mm | 210 mm | 210 mm | 210 mm | |
Weights |
|
|
|
|
| |
Weight, approx. | 600 g | 500 g | 600 g | 650 g | 600 g |