SM 422 digital output module Siemens

Область применения
Digital output modules can be used to output digital signals from the control to the process. They are suitable, for example, for connecting solenoid valves, contactors, low-power motors, lamps and motor starters.
Обзор
- Digital outputs for the SIMATIC S7-400
- For connecting solenoid valves, contactors, low-power motors, lamps and motor starters
Дизайн
Digital output modules are characterized by the following mechanical features:
- Compact configuration:
The rugged plastic housing contains:- Green LEDs for indicating the signal statuses at the outputs
- One red LED each to indicate internal and external faults or errors, and to display blown fuses and the absence of the load voltage
- Labeling strips
- Simple assembly
- User-friendly wiring:
The modules are wired by means of a plug-in front connector.
Функции
Digital output modules convert the internal signal levels of the S7-400 in the external signal levels required for the process.
Технические данные
Order number | 6ES7422-1FH00-0AA0 | 6ES7422-1HH00-0AA0 | 6ES7422-1BH11-0AA0 | 6ES7422-1BL00-0AA0 | 6ES7422-7BL00-0AB0 | |
---|---|---|---|---|---|---|
SM422, 16DO, AC120/230V, 2A | SM422, 16DO, AC5-230V, 5A RELAY | SM422, 16DO, DC24V, 2A, | SIMATIC S7-400, SM 422 | SIMATIC S7-400, DIG.OUTPUT MOD. | ||
Supply voltage |
|
|
|
|
| |
Load voltage L+ |
|
|
|
|
| |
| 60 V | 24 V | 24 V | 24 V | ||
| 1 V | 20.4 V | 20.4 V | 20.4 V | ||
| 60 V | 28.8 V | 28.8 V | 28.8 V | ||
Load voltage L1 |
|
|
|
|
| |
| 230 V; 120/230V AC | 230 V | ||||
| 79 V | 2 V | ||||
| 264 V | 264 V | ||||
Input current |
|
|
|
|
| |
from load voltage L+ (without load), max. | 1.5 mA | 30 mA | 30 mA | 120 mA | ||
from backplane bus 5 V DC, max. | 400 mA | 1 A | 160 mA | 200 mA | 200 mA | |
Power loss |
|
|
|
|
| |
Power loss, typ. | 16 W | 4.5 W | 5 W | 4 W | 8 W | |
Digital outputs |
|
|
|
|
| |
Number of digital outputs | 16 | 16; Relays | 16 | 32 | 32 | |
Limitation of inductive shutdown voltage to | -30 V | -27 V | L+ (-45 V) | |||
Switching capacity of the outputs |
|
|
|
|
| |
| 50 W | 60 W | 10 W | 5 W | 5 W | |
Output voltage |
|
|
|
|
| |
| L1 (-18.1 V) | L+ (-0.5 V) | L+ (-0.3 V) | L+ (-0.8 V) | ||
Output current |
|
|
|
|
| |
| 2 A | 5 A | 2 A | 0.5 A | 0.5 A | |
| 10 mA | 5 mA | 5 mA | 5 mA | ||
| 2 A | 2.4 A | 0.6 A | 600 A | ||
| 2.6 mA | 0.5 mA | 0.3 mA | 0.5 mA | ||
Switching frequency |
|
|
|
|
| |
| 10 Hz | 10 Hz | 100 Hz | 100 Hz | 100 Hz | |
| 0.5 Hz | 0.1 Hz | 0.5 Hz | 2 Hz | ||
Total current of the outputs (per group) |
|
|
|
|
| |
all mounting positions |
|
|
|
|
| |
| 2 A; 5 A with fan subassembly; per 4 adjacent outputs | 5 A; 10 A with fan subassembly | 2 A; 2 adjacent outputs each | 2 A; 8 adjacent outputs each | 2 A | |
Relay outputs |
|
|
|
|
| |
| 100 000; 100,000 (AC 15 / DC 13); 3,000,000 mechanical | |||||
Switching capacity of contacts |
|
|
|
|
| |
| 5 A; 5 A (30 V DC); 5 A (230 V AC) | |||||
| 5 A; 5 A (30 V DC); 5 A (230 V AC); 1.2 A (60 V DC); 0.2 A (125 V DC) | |||||
Cable length |
|
|
|
|
| |
| 1 000 m | 1 000 m | 1 000 m | 1 000 m | 1 000 m | |
| 600 m | 600 m | 600 m | 600 m | 600 m | |
Interrupts/diagnostics/status information |
|
|
|
|
| |
Alarms |
|
|
|
|
| |
| Yes; Parameterizable | |||||
Diagnostic messages |
|
|
|
|
| |
| Yes; internal/ external fault | |||||
Potential separation |
|
|
|
|
| |
Potential separation digital outputs |
|
|
|
|
| |
| 4 | 2 | 8 | 32 | 8 | |
| Yes | Yes | Yes | Yes | Yes | |
Isolation |
|
|
|
|
| |
Isolation tested with | 1500 V AC | 1500 V AC | 500 V DC | 500 V DC | 500 V DC | |
Dimensions |
|
|
|
|
| |
Width | 25 mm | 25 mm | 25 mm | 25 mm | 25 mm | |
Height | 290 mm | 290 mm | 290 mm | 290 mm | 290 mm | |
Depth | 210 mm | 210 mm | 210 mm | 210 mm | 210 mm | |
Weights |
|
|
|
|
| |
Weight, approx. | 800 g | 700 g | 600 g | 600 g | 600 g |
Дальнейшая информация
Brochures
Information material for downloading can be found in the Internet: