SIPLUS S7-400 SM 432 analog output modules Siemens

Область применения
Analog output modules permit the output of analog signals from the controller to the process.
Обзор
- Analog outputs for SIMATIC S7-400
- For connection of analog actuators
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme
Дизайн
The analog output module features the following mechanical characteristics:
- Compact design:
The rugged plastic enclosure contains:- Labeling strips
- Easy installation.
- User-friendly wiring:
The modules are wired via a plug-in front connector. - Different measurement ranges.
Функции
The analog output modules convert digital values from the S7-400 into analog signals for the process.
Технические данные
Order number | 6AG1432-1HF00-4AB0 | |
---|---|---|
SIPLUS_SM432_8AA | ||
Supply voltage |
| |
Load voltage L+ |
| |
| 24 V | |
Input current |
| |
from supply voltage L+, max. | 400 mA | |
from backplane bus 5 V DC, max. | 150 mA | |
Power loss |
| |
Power loss, typ. | 9 W | |
Hardware configuration |
| |
Slots |
| |
| 1 | |
Analog outputs |
| |
Number of analog outputs | 8 | |
Voltage output, short-circuit protection | Yes | |
Voltage output, short-circuit current, max. | 30 mA | |
Current output, no-load voltage, max. | 19 V | |
Output ranges, voltage |
| |
| Yes | |
| Yes | |
| Yes | |
Output ranges, current |
| |
| Yes | |
| Yes | |
| Yes | |
Load impedance (in rated range of output) |
| |
| 1 kΩ | |
| 1 µF | |
| 500 Ω; 600 ohms if common-mode-voltage reduced to <1 V | |
Cable length |
| |
| 200 m | |
Analog value generation |
| |
Integration and conversion time/resolution per channel |
| |
| 13 bit | |
| 420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 mA; 300 µs in all ranges | |
Settling time |
| |
| 0.1 ms | |
| 3.5 ms | |
| 0.5 ms | |
Errors/accuracies |
| |
Operational error limit in overall temperature range |
| |
| 0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V | |
| 1 %; +/-20 mA, 4 to 20 mV | |
Basic error limit (operational limit at 25 °C) |
| |
| 0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V | |
| 0.5 %; +/-20 mA, 0 to 20 mA | |
Potential separation |
| |
Potential separation analog outputs |
| |
| Yes | |
Isolation |
| |
Isolation tested with | 2120 V DC between bus and L+/M; 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground | |
Ambient conditions |
| |
Ambient temperature during operation |
| |
| 0 °C; = Tmin | |
| 60 °C; = Tmax | |
Extended ambient conditions |
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) Запрос коммерческого предложения× Сообщение отправлено× В ближайшее время сообщение будет обработано. Письмо с номером обращения отправлено на Ваш почтовый ящик. Спасибо за то, что выбрали Первый ZIP! Что-то пошло не так...× К сожалению, наша система расценила Ваше сообщение как спам. Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте. Приносим извинения за возможные неудобства. |