Drivers are available for downloading for the CP 341 and CP 441-2:
- Modbus:
For communication according to the Modbus protocol with RTU format.
Communication as master or slave
The two serial interfaces of the CP 441-2 can be operated independently with different standard protocols or downloadable drivers together with the V.24/TTY/X.27 interface modules.
Обзор
- Drivers for Modbus protocol with RTU message format; communication as master or slave
- Downloadable onto CP 341 and CP 441-2 (6ES7 441-2AA04-0AE0)
Функции
Modbus
- Modbus master:
Master/slave coupling with SIMATIC S7 as master. - Modbus slave:
Master/slave coupling with SIMATIC S7 as slave, message frame traffic from slave to slave not possible.
Configuration
The configuration package for CP 441-2 and CP 341 (V4.0 and higher) and STEP 7 V4.0 are required for downloading and configuration of the drivers. The drivers are copy protected by a dongle.
Технические данные
Parameterization software | Loadable drivers for CP 441-2 and CP 341 |
Type of license | Simple license, copy license |
Target system | SIMATIC CP 341, SIMATIC CP 441-2 |
Technical specifications | Modbus Master |
| - Modbus protocol with RTU format
|
| - Master/slave coupling: SIMATIC S7 is master
|
| - Function codes implemented: 01, 02, 03, 04, 05, 06, 07, 08, 11,12,15,16
|
| - No V.24 control and signal lines
|
| - CRC polynomial: x16 + x15 + x2 +1
|
| - Interfaces: TTY (20 mA); V.24 (RS 232 C); X.27 (RS 422/485) 2-wire or 4-wire
|
| - Receive mailbox specified on BRCV
|
| - Character delay time 3.5 characters or multiple thereof
|
| - Broadcast message possible
|
Adjustable parameters | - Transmission rate 300 bit/s up to 76800 bit/s (TTY up to 19200 bit/s)
|
| |
| - With/without RS 485 operation for 2-wire connections
|
| - With/without modem operation (ignore smudge characters)
|
| - Response monitoring time 100 ms to 25.5 s in steps of 100 ms
|
| - Factor for the character delay time 1-10
|
| - Default setting of receive line when using the X.27 interface module
|
| Modbus slave |
| - Modbus protocol with RTU format
|
| - Master/slave coupling: SIMATIC S7 is slave
|
| - Function codes implemented: 01, 02, 03, 04, 05, 06, 08, 15, 16
|
| - No V.24 control and signal line
|
| - CRC polynomial: x16 + x15 + x2 +1
|
| - Interfaces: TTY (20 mA), V.24 (RS 232C), X.27 (RS 422/485) 2-wire or 4-wire
|
| - Communications FB 180, instance DB 180 (use of a multi-instance)
|
| - Conversion of the Modbus data address to S7 data areas. Data areas which can be processed: DB, bit memories, outputs, inputs, timers, counters
|
| - Character delay time 3.5 characters or multiple thereof
|
Adjustable parameters | - Transmission rate 300 bit/s up to 76800 bit/s (TTY up to 19200 bit/s)
|
| |
| - Slave address of CP (1 to 255)
|
| - With/without RS 485 operation for 2-wire connection
|
| - With/without modem operation (ignore smudge characters)
|
| - Factor for the character delay time 1-10
|
| - Number of work DB (for FB processing)
|
| - Enabling of memory areas for writing by the master
|
| - Default setting of receive line when using the X.27 interface module
|
| - Conversion of Modbus addresses to S7 data areas
|