CP 443-1 Siemens

Область применения
- The CP 443-1 is used to connect the SIMATIC S7-400 to Industrial Ethernet networks. With its own processor, it relieves the CPU of communications tasks and facilitates additional connections.
The CP 443-1 offers communication options with
- PGs/PCs
- Host computers
- HMI systems
- SIMATIC S5/S7/C7 systems
- PROFINET IO devices
Обзор
Communications processor for connecting a SIMATIC S7-400 to Industrial Ethernet networks, also as PROFINET IO controller or in SIMATIC H systems.
The CP supports:
- PG/OP communication
- S7 communication
- Open communication (SEND/RECEIVE)
- PROFINET communication
- IT communication
The communications processor can also be used for redundant S7 communication in SIMATIC H systems and for fail-safe applications (PROFIsafe) in connection with an S7-400 F-CPU.
Дизайн
The CP 443-1 features all the advantages of the SIMATIC S7-400 design:
- Compact design:
- Two RJ45 sockets for connecting to Industrial Ethernet; automatic data rate detection by means of the autosensing/autocrossover function; the connection is made via the IE FC RJ45 Plug 180 with 180° cable outlet or via a standard patch cable
- Diagnostics LEDs for indicating the operational and communication status
- Easy installation:
The CP 443-1 is mounted on the S7-400 rack and connected to the other modules via the backplane bus. No slot rules apply. - The CP 443-1 can be operated without a fan
- The CP 443-1 can also be operated in the expansion rack (ER) in conjunction with the IM 460/461
- The module can be replaced without the need for a programming device
Функции
- Two RJ45 ports with 10/100 Mbps full/half duplex with autosensing and autocrossover functionality via integrated 2-port switch
- Communication services of the interface:
- Open communication (TCP/IP and UDP): Multicast with UDP, including routing between both interfaces
- PG/OP communication: Inter-network with S7 routing
- S7 communication (client, server, multiplexing) including routing between both interfaces
- S7 H communication for S7-400 H systems, now also across network boundaries (ISO-on-TCP)
- Certified PROFINET IO controller with real-time properties (RT and IRT)
- IP address assignment via DHCP, simple PC tool or via program block (e.g. for HMI)
- Media redundancy (MRP):
- Within an Ethernet network with ring topology, the CP supports the media redundancy procedure MRPMRP as an MRP Manager and as an MRP Client
- Diagnostics and network management:
- Comprehensive diagnostics functions for all modules in the rack (including graphical diagnostics, e.g. topology)
- Integration in network management systems due to support of SNMP V1/V3
- Security mechanisms:
- Access protection by means of configurable IP access list
- Secure firmware update
- Plagiarism detection
- Certification as per the Achilles Level II Standard
http://www.wurldtech.com/product_services/certifications/certified_products/
- Configuration of all functions with STEP 7 V5.5 SP2;
configuration with STEP 7 Professional V11 only with a limited range of functions of the predecessor CP 443-1 (6GK7 443-1EX20-0XE0) possible - When using the blocks AG_SSEND (FC53), AG_SRECV (FC63), TSEND (FB63), TRCV (FB64), TCON (FB65) and TDISCON (FB66), please note the following information: http://support.automation.siemens.com/WW/view/en/60037071
- Module replacement without programming device: All information can be stored on the CPU
Интеграция
Interfacing to higher-level network with CP 443-1 as PROFINET IO controller
Line structure as PROFINET IO controller with integrated real-time switch
Line structure at the superordinated control level through integrated 2-port switch
Особенности
- High plant availability through the support of media redundancy (MRP) and use in the SIMATIC S7-400 H system
- Optimum support of maintenance through
- Web-based diagnostics
- Remote programming via WAN or a telephone network (ISDN)
- Monitoring by means of IT network management tools (SNMP)
- Module exchange without programming device using the C-PLUG swap medium
- Securing the system against unauthorized access by means of
- Central access protection for any devices within an automation cell, e.g. by means of authentication of the network stations
- The capability of later connecting existing SIMATIC S7 systems to Industrial Ethernet using the CP 443-1 ensures investment protection
Технические данные
Order number | 6GK7443-1EX30-0XE0 | |
---|---|---|
Product type designation | CP 443-1 | |
Transmission rate |
| |
Transfer rate |
| |
| 10 ... 100 Mbit/s | |
Interfaces |
| |
Number of interfaces acc. to Industrial Ethernet | 2 | |
Number of electrical connections |
| |
| 2 | |
Type of electrical connection |
| |
| RJ45 port | |
design of the removable storage C-PLUG | No | |
Supply voltage, current consumption, power loss |
| |
Type of voltage of the supply voltage | DC | |
Supply voltage 1 from backplane bus | 5 V | |
Relative symmetrical tolerance at DC |
| |
| 5 % | |
Consumed current |
| |
| 1.4 A | |
Active power loss | 7.25 W | |
Permitted ambient conditions |
| |
Ambient temperature |
| |
| 0 ... 60 °C | |
| -40 ... +70 °C | |
| -40 ... +70 °C | |
Relative humidity at 25 °C without condensation during operation maximum | 95 % | |
Protection class IP | IP20 | |
Design, dimensions and weight |
| |
Module format | Compact module S7-400 single width | |
Width | 25 mm | |
Height | 290 mm | |
Depth | 210 mm | |
Net weight | 0.7 kg | |
Product properties, functions, components general |
| |
Number of units |
| |
| 14 | |
| max. 4 as PN IO ctrl. | |
Performance data open communication |
| |
Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum | 64 | |
Amount of data |
| |
| 8 Kibyte | |
| 8 Kibyte | |
| 8 Kibyte | |
| 2 Kibyte | |
Number of possible connections for open communication |
| |
| 64 | |
Amount of data |
| |
| 1 452 byte | |
Performance data S7 communication |
| |
Number of possible connections for S7 communication |
| |
| 128 | |
| 2 | |
| when using several CPUs | |
Performance data multi-protocol mode |
| |
Number of active connections with multi-protocol mode | 128 | |
Performance data PROFINET communication as PN IO-Controller |
| |
Product function PROFINET IO controller | Yes | |
Number of PN IO devices on PROFINET IO controller usable total | 128 | |
Number of PN IO IRT devices on PROFINET IO controller usable | 64 | |
Number of external PN IO lines with PROFINET per rack | 4 | |
Amount of data |
| |
| 4 Kibyte | |
| 4 Kibyte | |
| 1 433 byte | |
| 1 433 byte | |
| 240 byte | |
| 240 byte | |
Performance data telecontrol |
| |
Protocol is supported |
| |
| Yes | |
Product functions management, configuration |
| |
Product function MIB support | Yes | |
Protocol is supported |
| |
| Yes | |
| Yes | |
| Yes | |
Configuration software |
| |
| STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher | |
Product functions Diagnosis |
| |
Product function Web-based diagnostics | Yes | |
Product functions switch |
| |
Product feature Switch | Yes | |
Product function |
| |
| No | |
| Yes | |
| Yes | |
Product functions Redundancy |
| |
Product function |
| |
| Yes | |
| Yes | |
Protocol is supported Media Redundancy Protocol (MRP) | Yes | |
Product functions Security |
| |
Product function |
| |
| No | |
| Yes | |
| No | |
| Yes | |
| Yes | |
| No | |
Product functions Time |
| |
Product function SICLOCK support | Yes | |
Product function pass on time synchronization | Yes | |
Protocol is supported NTP | Yes |