IM 460-1 Siemens

Область применения
The IM 460-1 interface module is intended for use as a send IM for central connection over short distances of up to 1.5 m. It transfers data from the P-bus only to the expansion racks.
The IM 460-1 is intended for use only in association with the IM 461-1 interface module (in the expansion racks).
Обзор
- Send interface module for central expansion to 1.5 m
- Transmission of P bus
- With voltage supply for expansion units
- Can be plugged into the central controller
- Up to 2 expansion racks can be connected (up to 1 per interface)
- Can be used exclusively with IM 461-1
Дизайн
The IM 460-1 interface module can be inserted into the following central controllers:
- UR1,
- UR2 and
- CR2.
No more than 2 expansion units can be connected (1 per interface). No more than 2 IM 460-1 units can be plugged in per central controller.
The IM 460-1 supplies the modules in the connected expansion units with the 5 V supply voltage (max. 5 A per interface). In this case, there must be no power supply module in the downstream expansion units.
The module has:
- 3 LEDs for indicating faults.
- 2 interfaces for connecting the expansion lines via 468-3 connecting cable.
Технические данные
Order number | 6ES7460-1BA01-0AB0 | |
---|---|---|
TRANSMITT. INTERF.MOD. IM460-1,W/O K BUS | ||
Input current |
| |
from backplane bus 5 V DC, max. | 85 mA | |
Power loss |
| |
Power loss, max. | 425 mW | |
Hardware configuration |
| |
Cable length between first and last interface module, max. | 1.5 m | |
Dimensions |
| |
Width | 25 mm | |
Height | 290 mm | |
Depth | 217 mm | |
Weights |
| |
Weight, approx. | 600 g |