CPU 412H Siemens

Область применения
The CPU 412-5H can be used for the SIMATIC S7-400H and S7-400F/FH. It enables the establishment of an S7-400H high-availability system. It can also be used for the S7-400F/FH fail-safe automation system in conjunction with the F runtime license.
The integrated PROFIBUS DP interfaces enable direct connection as master to the PROFIBUS DP fieldbus.
The integrated PROFINET interface with switch functionality forms the basis for providing 2 externally accessible PROFINET ports. In this way, linear or ring structures can be implemented.
Обзор
- CPU for SIMATIC S7-400H and S7-400F/FH
- Can be used in S7-400H high-availability systems
- Can be used with F runtime license as F-capable CPU in S7-400F/FH safety-related systems
- With integrated PROFIBUS DP master and combined MPI/PROFIBUS DP master interface
- With integrated PROFINET interface (2-port switch)
- Features 2 slots for sync modules
Дизайн
The CPU 412-5H has:
- A powerful processor:
The CPU achieves command execution times as low as 31.25 ns per binary command. - 1 MB RAM (512 KB for program, 512 KB for data);
load memory for user programs and parameterization data of the S7-400H F/FH automation system; high-speed RAM for sequence-relevant sections of the user program - A memory card:
For expanding the integrated load memory. In addition to the program itself, the information contained in the load memory also includes configuration data for the S7-400H F/FH, which is why it requires about twice as much memory space. The result is that:- The integrated load memory is not sufficient for large programs, which is why the memory card is often required.
RAM and FEPROM cards are available (FEPROM for saving data even when power supply is disconnected).
- The integrated load memory is not sufficient for large programs, which is why the memory card is often required.
- Flexible expansion options:
Up to 131 072 digital and 81 932 analog inputs/outputs. - Combined MPI/PROFIBUS DP interface:
The MPI enables the creation of a simple network with up to 32 nodes and a data transfer rate of 187.5 kbit/s. The CPU can establish up to 64 connections to nodes on the communication bus (C bus) and the MPI.
The PROFIBUS DP master interface enables a distributed automation configuration with high speed and simple handling. From the user''s point of view, the distributed I/Os are treated like centralized I/Os (same configuring, addressing and programming). - PROFIBUS DP interface:
The PROFIBUS DP interface allows a redundant, distributed automation configuration offering high speed and ease of use. From the user''s point of view, the distributed I/Os are treated like centralized I/Os (same configuring, addressing and programming). - PROFINET interface with 2 ports (switch):
Support of system redundancy and MRP (Media Redundancy Protocol) - Mode selector:
Designed as a toggle switch. - Diagnostics buffer:
The last 120 alarm and interrupt events are stored in a ring buffer for diagnostic purposes. - Real-time clock:
Diagnostics reports from the CPU are provided with the date and time.
Функции
- Block protection:
In addition to the keylock switch, a password concept protects the user program from unauthorized access. User blocks can also be protected by an encryption process. - Integrated HMI services:
In the case of HMI devices, the user only has to specify the source and destination of the data. These are automatically transferred cyclically by the system. - Integrated communications functions:
- PG/OP communication
- Extended communication (simple and high-availability)
- Master-spare switchover programmed by user.
Parameterizable properties
With the STEP 7 tool "Hardware Configuration" and the installed option package S7-400H, the properties and behavior of the S7-400H including the CPUs can be parameterized, e.g.:
- Multi-point interface MPI:
- Determining node addresses.
- Startup/cyclic behavior.
- Definition of maximum cycle time and communication load.
- Address assignment:
Addressing of the I/O modules. - Retentive areas:
Definition of the number of retentive bit memories, counters, timers, data blocks and clock memories. - Protection level:
Definition of access authorization to program and data. - System diagnostics:
Determination of handling and scope of diagnostics messages. - Watchdog interrupts:
Setting the periodicity. - Configuring of H stations.
Safety-related functions
With the F runtime license, the safety-related F user program can be compiled and run on the CPU. One license is required for each S7-400F/FH system. The scope of delivery includes 2 TÜV (German technical inspectorate) adhesive labels.
Display and information functions
- Status and fault indicators:
LEDs indicate, for example, internal and external faults and operating statuses such as RUN, STOP, startup, "Master" operating mode, redundancy errors, and test function. - Test functions:
The programming device can be used to display signal states in the program execution sequence, modify process variables independently of the user program, output contents of stack memories, run through program steps individually, and disable program sections. - Information functions:
The user can obtain information about the memory capacity and operating mode of the CPU, and the current utilization of the RAM and load memory.
Технические данные
Order number | 6ES7412-5HK06-0AB0 | |
---|---|---|
CPU412-5H PN/DP, 1MB F. S7-400H/F/FH | ||
General information |
| |
Product type designation | CPU 412-5H PN/DP | |
Engineering with |
| |
| As of STEP 7 V5.5 SP2 with HF1 | |
Supply voltage |
| |
Rated value (DC) | ||
| No; Power supply via system power supply | |
Power loss |
| |
Power loss, typ. | 7.5 W | |
Memory |
| |
Work memory |
| |
| 1 Mbyte | |
| 512 kbyte | |
| 512 kbyte | |
Load memory |
| |
| 64 Mbyte | |
| 512 kbyte | |
| 64 Mbyte | |
CPU processing times |
| |
for bit operations, typ. | 31.25 ns | |
for word operations, typ. | 31.25 ns | |
for fixed point arithmetic, typ. | 31.25 ns | |
for floating point arithmetic, typ. | 62.5 ns | |
Counters, timers and their retentivity |
| |
S7 counter |
| |
| 2 048 | |
IEC counter |
| |
| Yes | |
S7 times |
| |
| 2 048 | |
IEC timer |
| |
| Yes | |
Data areas and their retentivity |
| |
Flag |
| |
| 8 192 byte | |
Address area |
| |
I/O address area |
| |
| 8 kbyte | |
| 8 kbyte | |
Process image |
| |
| 8 kbyte | |
| 8 kbyte | |
Hardware configuration |
| |
Slots |
| |
| 2 | |
Time of day |
| |
Clock |
| |
| Yes | |
Operating hours counter |
| |
| 16 | |
Interfaces |
| |
Number of RS 485 interfaces | 2 | |
Number of other interfaces | 2; Fiber-optic interface | |
1. Interface |
| |
Interface type | Integrated | |
Physics | RS 485 / PROFIBUS + MPI | |
Functionality |
| |
| Yes | |
| Yes | |
| No | |
DP master |
| |
| 32 | |
2. Interface |
| |
Interface type | PROFINET | |
Physics | Ethernet RJ45 | |
Number of ports | 2 | |
Functionality |
| |
| No | |
| No | |
| Yes | |
| No | |
| No | |
PROFINET IO Controller |
| |
| 256 | |
3. Interface |
| |
Interface type | Integrated | |
Physics | RS 485 / PROFIBUS | |
Functionality |
| |
| Yes | |
| No | |
DP master |
| |
| 64 | |
4. Interface |
| |
Interface type | Pluggable synchronization submodule (FO) | |
Plug-in interface modules | Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0 | |
5. Interface |
| |
Interface type | Pluggable synchronization submodule (FO) | |
Plug-in interface modules | Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0 | |
Isochronous mode |
| |
Isochronous operation (application synchronized up to terminal) | No | |
Communication functions |
| |
PG/OP communication | Yes | |
Data record routing | Yes | |
S7 routing | Yes | |
Global data communication |
| |
| No | |
S7 basic communication |
| |
| No | |
S7 communication |
| |
| Yes | |
S5 compatible communication |
| |
| Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV) | |
Standard communication (FMS) |
| |
| Yes; Via CP and loadable FB | |
Open IE communication |
| |
| Yes; via integrated PROFINET interface and loadable FBs | |
| 46 | |
| Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs | |
| 46 | |
| Yes; via integrated PROFINET interface and loadable FBs | |
| 46 | |
Web server |
| |
| No | |
Number of connections |
| |
| 48 | |
Configuration |
| |
Programming |
| |
Programming language |
| |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
Know-how protection |
| |
| Yes | |
| Yes; With S7 block Privacy | |
Dimensions |
| |
Width | 50 mm | |
Height | 290 mm | |
Depth | 219 mm | |
Weights |
| |
Weight, approx. | 995 g |