- Supports mixed operation of fail-safe signal modules in safety mode and S7-300 standard modules in an ET 200M when Cat. 4 or SIL 3 has to be achieved.
- The isolation module is not required if the safety class or safety category to be achieved is less than SIL 3 or Cat. 4, respectively.
When Cat. 4/SIL 3 is required, the isolation module must be implemented in the following situations:
Application | Isolation module must be used |
Central use after CPU 31xF-2 DP or CPU 31xF-2 PN/DP | |
| Yes, behind the CPU |
| Yes, after the last standard module and before the first fail-safe module |
Central use after CPU 31xF-2 DP or CPU 31xF-2 PN/DP in an expansion rack | |
| Yes, after the IM 36x |
| Yes, after the last standard module and before the first fail-safe module |
Distributed behind the IM 153-2 with copper connection | |
| Yes, after the IM 153-2 |
| Yes, after the last standard module and before the first fail-safe module |
Distributed behind the IM 153-2 with fiber-optic connection | |
| No |
| Yes, after the last standard module and before the first fail-safe module |
Технические данные
Order number | 6ES7195-7KF00-0XA0 | |
---|---|---|
SEPARATOR MOD. BETW. F- AND STD-MOD. | ||
Weights |
| |
Weight, approx. | 10 g |