SM 336 F analog input modules - Safety Integrated Siemens

Область применения
The modules are used centrally with SIMATIC S7-31xF-2 DP and in the ET 200M distributed I/O device together with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH.
0 to 20 mA and 4 to 20 mA current transmitters (also HART) can be connected as encoders.
Обзор
- Analog inputs for the fail-safe SIMATIC S7 systems
- Applicable in the ET 200M distributed I/O device with IM 153-2 HF as well as centrally with SIMATIC S7-31xF-2 DP
- Properties of the SM 336; F-AI 6 x 0/4 - 20 mA HART:
- 6 analog inputs with galvanic isolation between channels and backplane bus
- Input ranges: 0 to 20 mA, 4 to 20 mA
- Short-circuit proof power supply from 2 or 4-wire transducer via the module
- External encoder supply possible
- Applicable in safety mode
- HART communication
- Firmware update using HW Config
- Identification data
Дизайн
- 6 inputs for current measurement.
- Compact design:
- Group fault display (SF)
- Safety mode display (SAFE)
- Display for channel-specific faults (Fn)
- Display for HART status (Hn)
- Plug options for the 20-pin front connector, protected behind the front door.
- Labeling field on the front door.
- Easy assembly
Assembled like the other ET 200M I/O modules. - User-friendly wiring with 20-pin front connector.
Функции
The analog input module converts analog signals from the process to digital signals for internal processing by the fail-safe SIMATIC S7 CPUs.
The safety functions required for fail-safe operation are integrated in the module.
The following functions are available:
- Resolution 15 bits + sign.
- Measuring ranges:
- 0 to 20 mA or
- 4 to 20 mA or
- 4 to 20 mA (HART)
- Interrupt capability;
the module sends diagnostic interrupts to the CPU of the controller. - Diagnostics;
the module sends extensive diagnostic information to the CPU.
Технические данные
Order number | 6ES7336-4GE00-0AB0 | |
---|---|---|
SM 336, F.AI 6 X 0/4 ... 20MA HART | ||
General information |
| |
Product type designation | SM 336 F-AI 6x0/4 to 20 mA HART | |
Supply voltage |
| |
Rated value (DC) | 24 V | |
Reverse polarity protection | Yes | |
Input current |
| |
From power supply L+, typ. | 150 mA | |
from backplane bus 5 V DC, max. | 90 mA | |
Power loss |
| |
Power loss, typ. | 4.5 W | |
Analog inputs |
| |
Number of analog inputs | 6 | |
permissible input current for current input (destruction limit), max. | 40 mA | |
Input ranges (rated values), currents |
| |
| Yes | |
| Yes | |
Cable length |
| |
| 1 000 m | |
Analog value generation for the inputs |
| |
Integration and conversion time/resolution per channel |
| |
| 16 bit; 15 bits + sign | |
| 20 ms @ 50 Hz, 16.7 ms @ 60 Hz | |
| f=n x (f1+-0.5%) | |
Encoder |
| |
Connection of signal encoders |
| |
| Yes | |
| Yes | |
Errors/accuracies |
| |
Operational error limit in overall temperature range |
| |
| 0.2 %; 40 µA | |
Basic error limit (operational limit at 25 °C) |
| |
| 0.1 % | |
Interrupts/diagnostics/status information |
| |
Alarms |
| |
| Yes | |
Diagnostic messages |
| |
| Yes | |
Potential separation |
| |
Potential separation analog inputs |
| |
| Yes | |
| Yes | |
| Yes | |
Isolation |
| |
Isolation tested with | 370V for 1 min | |
Standards, approvals, certificates |
| |
Highest safety class achievable in safety mode |
| |
| 4 | |
| SIL 3 | |
Connection method |
| |
required front connector | 20-pin | |
Dimensions |
| |
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights |
| |
Weight, approx. | 350 g |