SIPLUS S7-300 SM 326 F digital input modules - Safety Integrated Siemens

Область применения
Fail-safe digital input modules are suitable for connecting
- Switches and 2-wire proximity switches (BEROs)
- Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas
The modules are implemented centrally with SIMATIC S7-31xF-2 DP and in the ET 200M distributed I/O station in combination with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH. They can also be used in non-safety-relevant standard mode and then respond like standard S7-300 modules.
Обзор
- Digital inputs for the fail-safe SIPLUS S7 systems
- For connecting:
- Switches and 2-wire proximity switches
- Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas
- With integral safety functions for fail-safe operation
- Can be used in fail-safe operation
- Centrally: With S7-31xF-2 DP
- Distributed in ET 200M: With SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH
- In standard operation can be used in the same way as S7-300 modules
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Дизайн
Failsafe digital input modules have the following mechanical features:
- Compact configuration:
The rugged plastic housing contains- Green input signal status LEDs
- Green LED for indicating safety mode
- Red group fault LED
- Slot for front connector protected by the front cover
- Labeling area on the front cover
- Easy installation:
Installed in the same way as the other ET 200M I/O modules - User-friendly wiring via front connector
Note:
Cable guide 6ES7 393-4AA10-0AA0 is required in order to operate 6ES7 326-1RF00-0AB0 failsafe digital input modules in hazardous areas.
Функции
Failsafe digital input modules convert the levels of the external digital signals from the process into the internal signal level of the failsafe SIMATIC S7 CPUs.
The safety functions required for failsafe operation are integrated in the modules.
Технические данные
Order number | 6AG1326-1BK02-2AB0 | 6AG1326-1BK02-2AY0 | 6AG1326-1RF01-4AB0 | |
---|---|---|---|---|
SIPLUS S7-300 SM326F DI24 | SIPLUS S7-300 SM326F DI24 | SIPLUS S7-300 SM326F DI8 NAMUR | ||
General information |
|
|
| |
Product type designation | F-DI 8x24VDC Namur | |||
Supply voltage |
|
|
| |
Rated value (DC) | 24 V | 24 V | ||
Input current |
|
|
| |
from load voltage L+ (without load), max. | 450 mA | 450 mA | 160 mA | |
from backplane bus 5 V DC, max. | 100 mA | 100 mA | 90 mA | |
Encoder supply |
|
|
| |
Number of outputs | 4; Isolated | 4; Isolated | 8 | |
Type of output voltage | 8.2 V DC | |||
Output current |
|
|
| |
| 400 mA | 400 mA | ||
Power loss |
|
|
| |
Power loss, typ. | 10 W | 10 W | ||
Digital inputs |
|
|
| |
Number of digital inputs | 24 | 24 | 8 | |
Number of simultaneously controllable inputs |
|
|
| |
all mounting positions |
|
|
| |
| 24 | 24 | 8 | |
| 24; (at 24 V) or 18 (at 28.8 V) | 24; (at 24 V) or 18 (at 28.8 V) | 8 | |
Input voltage |
|
|
| |
| DC | DC | ||
| 24 V | 24 V | ||
| -30 to +5V | -28.8 ... +5V | ||
| +11 to +30V | +11 to +28.8V | ||
Input current |
|
|
| |
| 2 mA | 2 mA | 0.35 to 1.2 mA | |
| 10 mA | 10 mA | 2.1 to 7 mA | |
Input delay (for rated value of input voltage) |
|
|
| |
for standard inputs |
|
|
| |
| 3.4 ms | 3.4 ms | ||
| 3.4 ms | 3.4 ms | ||
for NAMUR inputs |
|
|
| |
| 1.2 to 3 ms | |||
| 1.2 to 3 ms | |||
Cable length |
|
|
| |
| 200 m | 200 m | 200 m | |
| 100 m | 100 m | 100 m | |
Encoder |
|
|
| |
Connectable encoders |
|
|
| |
| Yes; if short-circuit test is deactivated | Yes; if short-circuit test is deactivated | ||
| 2 mA | 2 mA | ||
Interrupts/diagnostics/status information |
|
|
| |
Alarms |
|
|
| |
| Yes | Yes | Yes; Parameterizable | |
Diagnostic messages |
|
|
| |
| Yes | Yes | ||
Ex(i) characteristics |
|
|
| |
Module for Ex(i) protection | Yes | |||
Maximum values of input circuits (per channel) |
|
|
| |
| 3 µF | |||
| 13.9 mA | |||
| 80 mH | |||
| 33.1 mW | |||
| 10 V | |||
| 60V DC/30V AC | |||
| 60 °C | 60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155 | 60 °C | |
Potential separation |
|
|
| |
Potential separation digital inputs |
|
|
| |
| Yes | Yes | Yes | |
| 12 | 12 | ||
| Yes | Yes | Yes | |
| Yes | |||
Isolation |
|
|
| |
Isolation tested with | 500V DC/350V AC | 500V AC for 1 min (internal voltage limiting to ±120V) | ||
Standards, approvals, certificates |
|
|
| |
CE mark | Yes | Yes | Yes | |
UL approval | Yes; File E239877 | Yes; File E239877 | ||
FM approval | Yes; CofC 3028431 | Yes; CofC 3028431 | ||
RCM (formerly C-TICK) | Yes | |||
KC approval | Yes | |||
EAC (formerly Gost-R) | Yes | |||
EN 50155 | Yes; T1 Cat. 1 Cl. A/B horizontal mounting position | |||
Highest safety class achievable in safety mode |
|
|
| |
| AK 6 | AK 6 | ||
| Cat. 4 | Cat. 4 | ||
| SIL 3 | SIL 3 | SIL 2 (single-channel), SIL 3 (two-channel) | |
Ambient conditions |
|
|
| |
Ambient temperature during operation |
|
|
| |
| -25 °C; = Tmin | -25 °C; = Tmin | 0 °C; = Tmin | |
| 60 °C; = Tmax | 60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155 | 60 °C; = Tmax | |
Extended ambient conditions |
|
|
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity |
|
|
| |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | ||
Resistance |
|
|
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | ||
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | ||
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | ||
Connection method |
|
|
| |
required front connector | 40-pin | 40-pin | 1x 40-pin | |
Dimensions |
|
|
| |
Width | 80 mm | 80 mm | 80 mm | |
Height | 125 mm | 125 mm | 125 mm | |
Depth | 120 mm | 120 mm | 120 mm | |
Weights |
|
|
| |
Weight, approx. | 442 g | 442 g | 482 g |