SIPLUS S7-300 SM 326 F digital output modules - Safety Integrated Siemens

Область применения
Fail-safe digital output modules are used centrally with SIMATIC S7-31xF-2 DP, and in the ET 200M distributed I/O device together with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH.
The modules are, for example, suitable for connecting solenoid valves, DC contactors and indicator lights.
In the case of the SM 326 F-DO 10 x DC 24V/2A PP (6ES7 326-2BF10-0AB0), the function "Keep last valid value" can be used optionally in safety mode too. Together with the diagnostics capability of the module, this can be used for cost-optimized implementation of applications in, for example, the area of fire and gas alarm systems (in accordance with EN 54-2/-4 or NFPA72).
Обзор
- Digital outputs for the fail-safe SIMATIC S7 systems
- For connection of solenoid valves, DC contactors and indicator lights
- With integral safety functions for fail-safe operation
- Can be used in fail-safe mode
- Centrally: With S7-31xF-2 DP
- Distributed in ET 200M: With SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Дизайн
Fail-safe digital output modules have the following mechanical features:
- Compact design:
- 2 connections per output for single-channel or redundant actuator control
- Green LEDs for indicating signal states at the outputs
- Green LED for indicating safety operation
- Red LED for group error display
- Connection options for the front connector, protected behind the front door
- Labeling field on the front door
- Simple installation:
installation is the same as for the other I/O modules of the ET 200M - User-friendly wiring via the front connector
- Module width:
- SM 326 F-DO 10 x DC 24V/2A PP (6ES7 326-2BF10-0AB0) single-width (40mm)
- SM 326 F-DO 8 x DC 24V/2A PM (6ES7 326-2BF41-0AB0) double-width (80 mm)
Функции
Failsafe digital output modules convert the internal signal level of the failsafe SIMATIC S7 CPUs into the external signal levels required for the process. The safety functions required for failsafe operation are integrated in the modules.
Технические данные
Order number | 6AG1326-2BF10-2AB0 | 6AG1326-2BF10-2AY0 | 6AG1326-2BF41-2AB0 | 6AG1326-2BF41-2AY0 | |
---|---|---|---|---|---|
SIPLUS S7-300 SM326F 10 DO | SIPLUS S7-300 SM326 10F-DO | SIPLUS S7-300 SM326F DO8 | SIPLUS S7-300 SM326 F DO8 EN50155 | ||
Supply voltage |
|
|
|
| |
Rated value (DC) | 24 V; 1L+ | 24 V; 1L+ | 24 V; 1L+ | 24 V; 1L+ | |
Load voltage L+ |
|
|
|
| |
| 24 V; 2L+, 3L+ | 24 V; 2L+, 3L+ | 24 V; 2L+, 3L+ | 24 V; 2L+, 3L+ | |
Input current |
|
|
|
| |
from supply voltage 1L+, max. | 100 mA | 100 mA | 75 mA | 75 mA | |
from load voltage 2L+ (without load), max. | 100 mA | 100 mA | 100 mA | 100 mA | |
from load voltage 3L+ (without load), max. | 100 mA | 100 mA | 100 mA | 100 mA | |
from backplane bus 5 V DC, max. | 100 mA | 100 mA | 100 mA | 100 mA | |
Power loss |
|
|
|
| |
Power loss, typ. | 6 W | 6 W | 12 W | 12 W | |
Digital outputs |
|
|
|
| |
Number of digital outputs | 10 | 10 | 8 | 8 | |
Short-circuit protection | Yes | Yes | Yes | ||
Limitation of inductive shutdown voltage to | L+ (-33 V) | L+ (-33 V) | |||
Switching capacity of the outputs |
|
|
|
| |
| 5 W | 5 W | 5 W | 5 W | |
Output voltage |
|
|
|
| |
| L+ (-1.0 V) | L+ (-1.0 V) | |||
Output current |
|
|
|
| |
| 2 A | 2 A | 2 A | 2 A | |
| 7 mA | 7 mA | 7 mA | 7 mA | |
| 2.4 A | 2.4 A | 2 A; 2 A for horizontal installation, 1 A for vertical installation | 2 A; with horizontal installation, 1 A with vertical installation | |
| 7 mA | 7 mA | 7 mA | 7 mA | |
| 2.4 A | 2.4 A | 1 A; for horizontal installation | 1 A; for horizontal installation | |
| 0.5 mA | 0.5 mA | 0.5 mA | 0.5 mA | |
Switching frequency |
|
|
|
| |
| 25 Hz | 25 Hz | 30 Hz | 30 Hz | |
| 25 Hz | 25 Hz | 2 Hz | 2 Hz | |
| 10 Hz | 10 Hz | 10 Hz | 10 Hz | |
Total current of the outputs (per group) |
|
|
|
| |
horizontal installation |
|
|
|
| |
| 10 A | 10 A | 7.5 A | 7.5 A | |
| 6 A | 6 A | 5 A | 4 A | |
vertical installation |
|
|
|
| |
| 5 A | 5 A | 5 A | 5 A | |
Cable length |
|
|
|
| |
| 1 000 m | 1 000 m | 200 m; 200 m for SIL3, AK 6, Cat 4 | 200 m; 200 m for SIL3, AK 6, Cat 4 | |
| 600 m | 600 m | 200 m | 200 m | |
Interrupts/diagnostics/status information |
|
|
|
| |
Alarms |
|
|
|
| |
| Yes | Yes | Yes; Parameterizable | Yes; Parameterizable | |
Diagnostic messages |
|
|
|
| |
| Yes | Yes | Yes | Yes | |
Potential separation |
|
|
|
| |
Potential separation digital outputs |
|
|
|
| |
| Yes | Yes | Yes | Yes | |
| 5 | 5 | 4 | 4 | |
| Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | |
Isolation |
|
|
|
| |
Isolation tested with | 370V for 1 min | 500V AC for 1 min (internal voltage limiting to ±120V) | 500V DC/350V AC | 500V AC for 1 min (internal voltage limiting to ±120V) | |
Standards, approvals, certificates |
|
|
|
| |
CE mark | Yes | Yes | Yes | Yes | |
UL approval | Yes; File E239877 | Yes; File E239877 | Yes; File E239877 | ||
FM approval | Yes; CofC 3028431 | Yes; CofC 3028431 | Yes; CofC 3028431 | ||
RCM (formerly C-TICK) | Yes | Yes | Yes | Yes | |
KC approval | Yes | Yes | Yes | Yes | |
EAC (formerly Gost-R) | Yes | Yes | Yes | Yes | |
EN 50155 | Yes; T1 Cat. 1 Cl. A/B horizontal mounting position | No | Yes; T1 Cat. 1 Cl. A/B horizontal mounting position | ||
Highest safety class achievable in safety mode |
|
|
|
| |
| Cat. 4 | Cat. 4 | Cat. 4 | Cat. 4 | |
| SIL 3 | SIL 3 | SIL 3 | SIL 3 | |
Ambient conditions |
|
|
|
| |
Ambient temperature during operation |
|
|
|
| |
| -25 °C | -25 °C; = Tmin | -25 °C | -25 °C; = Tmin | |
| 60 °C | 60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155 | 60 °C | 60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155 | |
Extended ambient conditions |
|
|
|
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity |
|
|
|
| |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |||
Resistance |
|
|
|
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |||
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |||
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |||
Connection method |
|
|
|
| |
required front connector | 40-pin | 40-pin | 40-pin | 40-pin | |
Dimensions |
|
|
|
| |
Width | 40 mm | 40 mm | 80 mm | 80 mm | |
Height | 125 mm | 125 mm | Запрос коммерческого предложения× Сообщение отправлено× В ближайшее время сообщение будет обработано. Письмо с номером обращения отправлено на Ваш почтовый ящик. Спасибо за то, что выбрали Первый ZIP! Что-то пошло не так...× К сожалению, наша система расценила Ваше сообщение как спам. Если это произошло по ошибке, пожалуйста, обратитесь к нам по электронной почте. Приносим извинения за возможные неудобства. |